Call us 24/7+86 15396210640
Welcome to the official website of Lingkong Automation Technology Co., Ltd!
Call us 24/7+86 15396210640

DeltaV™ M-series Traditional I/O

 Decreases capital equipment costs

 Decreases installation time and expense

 Increases productivity

 Increases process availability

Introduction

Traditional I/O is a modular subsystem that offers flexibility 

during installation. It’s designed to be installed in the field, 

near your devices. Traditional I/O is equipped with function 

and field wiring protection keys to ensure that the correct

I/O card is always plugged into the corresponding terminal 

block. Modularity, protection keys, and plug and play 

capabilities make DeltaV™ Traditional I/O a smart choice 

for your process control system. 

Benefits

Decreases capital equipment costs

Full system modularity. The Traditional I/O 

subsystem was designed with your investment in mind. All 

components are fully modular and may be installable 

under power.1 You add I/O interface carriers and I/O 

interfaces in groups of 4, 8, 16, or 32 channels as you 

need them. The modular design enables you to purchase 

the exact amount of I/O cards, 8-wide carriers, 

power/controllers, and 2-wide carriers you need and add 

more DeltaV I/O as your system grows. 

Reduced system footprint. The DeltaV system’s 

state-of-the-art form factor design of the I/O components 

enables you to mount the I/O interface carrier in a junction 

box in the field so you significantly reduce the footprint of 

your equipment and increase valuable control room space 

for other uses. 

Installation. Save on wiring expenses by installing 

Classic Instrumentation in the field, near the actual field 

devices. Mounting the controller with the I/O further 

reduces your wiring expenditures by eliminating the need 

for long runs of multi-cores. The integrated design of the 

Traditional I/O subsystem can eliminate the need for 

marshaling panels. This saves you even more in your total 

capital costs.

The provision of in-line fuses and bussed power saves on 

installation costs compared with external fuses and power 

distribution.

Decreases installation time and expense

Plug-and-play installation saves money. All 

Traditional I/O components plug into the I/O interface 

carrier. You can install the I/O interface carriers to manage 

anticipated growth and postpone the I/O interfaces until 

you’re ready to install your additional field devices.

Phased installation saves time. As soon as you 

mount the I/O interface carrier, you’re ready to begin 

installing the field devices. I/O terminal blocks plug directly 

onto the I/O interface carrier. There is no need to have the 

I/O cards installed. 

1 Refer to Zone 2 installation instructions (12P2046) and/or 

Class 1 Division 2 installation instructions (12P1293) for 

details.

Traditional I/O terminal block.

Keys. Traditional I/O interfaces and terminal blocks have 

I/O function keys. These keys ensure that the correct I/O 

card is always plugged into the corresponding terminal 

block. It’s incredibly easy to use and gives you time to do 

more. 

This design enables you to initially install Traditional I/O 

quickly and efficiently. When you need to replace an I/O 

card, the function key design ensures that you will always 

install it correctly. This keying system provides a safety 

measure by preventing the wrong I/O interface’s being 

installed.

Increases productivity

Real-time, online equipment additions. Online 

addition of new I/O interfaces means your process does 

not get interrupted. As new equipment is added, the 

DeltaV Explorer acknowledges it and assigns it basic 

configuration.

Increases process availability

1:1 Redundancy for Traditional and HART I/O 

cards. DeltaV redundant I/O uses the same Series 2 I/O 

cards as non-redundant I/O. This allows you to leverage 

your investment in installed I/O and in I/O spares. No 

additional configuration is needed when using a redundant 

channel. The redundant terminal blocks provide the same 

field wiring connections as simplex blocks, so there is no 

extra wiring needed. 

Autosense of redundancy. DeltaV autosenses 

redundant I/O, which greatly simplifies the task of adding 

redundancy to the system. The redundant pair of cards is

treated as one card in the system tools.

Automatic Switchover. Should a primary I/O card fail, 

the system automatically switches to the “standby” card 

without user intervention. The operator is given clear 

notification of a switchover at the operator display

Product Description

The Traditional I/O subsystem includes:

 I/O interface carrier (a DIN rail surface mounted) on 

which all I/O related components are installed.

 Bulk AC to 24 VDC power supply for field devices.

 An I/O interface consisting of an I/O card and an I/O 

terminal block.

 A variety of analog and discrete I/O cards enclosed in 

a common form factor that easily plugs into the I/O 

interface carrier.

 A variety of I/O terminal blocks mounted on the I/O 

interface carrier that can be pre-wired before I/O card 

installation.

A Traditional I/O card easily plugs into an I/O carrier

I/O Cards

A variety of analog and discrete I/O cards are available to 

meet your specific requirements. The following cards 

support simplex or redundant installation:

 AI 4-20 mA HART 8 channels

 AO-4-20 mA HART 8 channels

 DI, 24 VDC Dry Contact, 8-channels

 DO 24 VDC High Side, 8-channels

The following I/O cards are supported in simplex format to 

meet your field wiring needs.

 AI 4-20 mA HART 16 channels

 AI Isolated, 4 channels

 RTD, 8-channels

 Thermocouple, 8- channels

 Millivolt, 8-channels

 DI, High Density, 32-channels

 DI 24 VDC Isolated, 8-channels

 Multi-Function, 4 channels (Isolated DI)

 Sequence of Event, 16 channels (DI 24 VDC)

 DI 120 VAC Low Side Detection, 8-channels

 DI 120 VAC Isolated , 8-channels

 DO, High Density, 32-channels

 DO 24 VDC Isolated, 8-channels

 DO 120/230 VAC High Side, 8 channels

 DO 120/230 Isolated, 8 channels

All I/O cards are enclosed in a common form factor that 

plugs into the I/O interface carrier. The housing is clearly 

labeled with the enclosed I/O card type. All cards have 

power and internal error indicators. Eight channel cards 

have clearly visible channel status LEDs.

All cards meet ISA G3 corrosion specifications by the 

careful selection of superior electronic components and 

the use of conformal coating.

Pulse Counters are available on most DI cards. The 

supported maximum frequency varies from 0.1 Hz on AC 

signals to 75 or 120 Hz on 24 VDC inputs. For higher 

pulse counts up to 50 KHz, use the Multi-Function card’s 

high speed pulse input. 

DeltaV provides control module level time stamping for log 

events and alarms. For greater event resolution the 16 

channel Sequence of Events DI card can provide signal 

driven events to a resolution of +/- 0.25 ms per card, or 

within 1 ms per controller. Please refer to the Sequence 

of Events PDS for more information on Sequence of Event 

data collection and system options for this feature.

I/O Card Redundancy

Redundant I/O cards are available for critical applications. 

The same card can be used in simplex or redundant 

applications. When installed on a two-wide redundant 

terminal block, the cards are recognized as a redundant 

pair by the controller. The controller scans each card and 

determines which card is acting as the active interface. 

When a fault is detected, the system automatically 

switches to the standby I/O card. 

DeltaV Control modules reference simplex and redundant 

I/O channels identically and there is no special 

configuration required to take advantage of redundancy. 

Switchover of a redundant I/O card is completed within 

two scans of the I/O bus. Make-before-break contacts 

ensure digital field instruments remain powered and the 

process is undisturbed. Analog output signals are briefly 

driven by both cards for < 5 ms during switchover of the 

card.

Hardware Alerts automatically report hardware integrity 

errors for both the primary and secondary cards. Any 

event that causes a switchover is also reported 

automatically through the system hardware alerts and is 

logged in the Event Chronicle. 

Events that can cause a switchover include.

 Hardware failure within the active card.

 Communications failure between the active card and 

the controller.

 Detection of a fault in the field wiring

A switchover may also be initiated from the diagnostics 

explorer, and the health and status of both cards and their 

channels are available in the diagnostics explorer.

The system automatically commissions a new standby 

card. In safe areas, failed cards can be replaced under 

power. In hazardous areas, appropriate installation 

procedures must be followed.

 Fused 8-Channel Terminal Block

 AI 8-Channel Terminal Block

 AI 16-channel Terminal Block

 4-wire AI 16-channel Terminal Block

 Discrete 32-Channel Terminal Block 

 Isolated Input Terminal Block

 RTD/Resistance Terminal Block

 Thermocouple Terminal Block

The following redundant I/O terminal blocks are available 

on some I/O interfaces, allowing a pair of cards to be 

installed as a redundant pair.

 Redundant AI 8-Channel Terminal Block 

 Redundant AO 8-Channel Terminal Block

 Redundant Discrete 8-Channel Terminal Block 

The table on the following page lists the compatible 

terminal blocks for each card, along with the cards unique 

key positions. The first terminal block listed is the 

recommended terminal block. 

In addition to standard signal wiring, some cards may also 

be ordered with Mass Termination blocks that allow these 

cards to be connected to M-Series Mass Connection 

Solution or to third party wiring solution, mounted in an 

adjacent cabinet in order to meet special signal 

conditioning or for optimizing field wiring solutions. Please 

refer to the PDS M-series Mass Connection Solution or to 

the Alliance Program website for details on approved 3rd

party products.

 10-pin Mass Termination Block 

 16-pin Mass Termination Block 

 24-pin Mass Termination Block

 40-pin Mass Termination Block

The keying mechanism consists of two keying posts that 

rotate and lock into the terminal block base. Each post 

has 6 positions: A-F and 1-6. Each card is assigned a 

unique key which is marked on the side of the I/O card:

Terminal Block keying example

The keys prevent installation of an incorrect card, and the 

graphical information on the card makes it easy to 

determine if a keyed slot will accept a particular card.

There are 8 different I/O terminal blocks available to meet 

the wiring needs of field signals. 

 8-Channel Terminal Block

DeltaV™ Electronic Marshalling for Migrations

DeltaV™ Electronic Marshalling for Migrations

„ I/O anywhere you need it

„ Single channel granularity

„ Replaces legacy I/O in place

„ Fully redundant architecture

„ Complete DeltaV™ solution

„ Plug and play I/O

DeltaV™ CHARM I/O Cards (CIOC) mounted on a Migration Panel.

DeltaV CHARM I/O Baseplate Migration Panel.

Introduction

DeltaV™ Electronic Marshalling delivers a new level of control 

system I/O performance with unprecedented flexibility and 

ease of use. The CHARM I/O card (CIOC) supports up to 

96 individually configurable channels and when mounted 

horizontally in conjunction with a legacy system migration 

will allow for direct replacement of legacy hardware within 

existing cabinets. Now you can migrate to DeltaV without 

having to add cabinets, custom cables, or extra marshalling. 

All communications are completely redundant from the 

channel (CHARM) to the DeltaV controller.

Benefits

I/O anywhere you need it: The DeltaV CIOC provides 

unprecedented flexibility in control system I/O topology. 

Now you can mount your DeltaV I/O in the same space as your 

legacy I/O for a direct 1-to-1 replacement. Without adding 

any new cabinets of DeltaV hardware you can replace all your 

legacy equipment leaving behind a complete DeltaV solution.

Single Channel granularity: The CHARM I/O architecture 

allows each individual channel to be characterized for the 

requirements of the field device. Any instrument signal can be 

wired to any terminal block. The channel is then electronically 

marshalled by installing the appropriate CHARM and assigning 

the channel to one of four controllers. Legacy I/O terminations 

are no longer a concern because of multiple channel types 

from a single termination panel. Just install the proper CHARM 

to characterize the I/O as found on the legacy panels. No more 

engineering and splitting signals from a single legacy panel to 

multiple DeltaV I/O cards.

Replaces legacy I/O in place: DeltaV Electronic Marshalling 

goes where no one else’s I/O can. Install the CHARMs migration 

panel above, below, or even in front of your legacy termination 

panel and move your wires inches to complete your migration 

to DeltaV. Since the CHARMs migration panel is a standard 

CHARMs baseplate, it talks to the CIOC the same as the 

standard vertical installation through the cable interface. 

This allows you to mount the migration panel in the best 

location to facilitate a clean system cutover and not have to 

“stretch” your I/O cables to a new termination. As an added 

bonus, install CHARMs vertical if your wiring allows for it in 

certain areas. Now you can mount your I/O in any orientation 

as best fits your current migration layout and needs.

Fully redundant communications: The CIOC architecture is 

fully redundant. This starts with the two I/O cards on a carrier. 

The carrier has redundant communication modules for primary 

and secondary network connections. There are two 24 V DC 

input power connections. The carrier connects to the CHARMs 

Baseplates and provides redundant power and communication 

buses to the CHARMs. Everything is redundant down to the 

individual channel.

Complete DeltaV solution: Migrate from your legacy system 

with the comfort that when complete you will have a complete 

DeltaV solution, not a combination of standard and custom 

hardware/software to support. Every piece of the migration 

panel is standard DeltaV hardware and can be supported with 

the same personnel and spare equipment that every other 

CHARMs and DeltaV installation uses.

Plug and play I/O: The DeltaV CIOC has been designed for 

ease of use, both in physical installation and its software tools. 

Components snap together with secure DIN-rail latches and 

interlocking carrier connectors. Insert the CHARMs and auto 

sense the node to create the I/O definition automatically in 

your DeltaV configuration database. CHARMs use a self-keying 

system to automatically set a channel for a specific CHARM 

type. Users cannot mistakenly insert a CHARM into the wrong 

terminal block. Assign all, one, or any number of channels to a 

controller with a simple click and drag.

CHARM and Terminal Block.

Field power is provided through a redundant 24V DC bus to 

each CHARM, with up to 100 mA per CHARM. Higher current 

Discrete Channels can be powered through integrated power 

injection bus local to each CHARM Baseplate.

Product Description

Electronic Marshalling for Migrations hardware includes:

„ CHARM I/O Carrier (DIN-rail mounted and supports 

redundant pair of CHARM I/O Cards).

„ CHARM I/O Card (CIOC) provides communication between 

CHARMs and the Ethernet I/O network to M-series, S-series, 

and PK controllers. The CIOC has Achilles Communications 

Certification Level 1 and the redesigned CIOC2 has more 

computing power and Achilles Communications Certification 

Level 2. The CIOC2 is a drop-in replacement for the CIOC.

„ CHARM Baseplate (DIN-rail mounted with interleaving power 

and bus connectors. Supports 12 CHARMs and their terminal 

blocks, as well as connection for injected field power).

„ CHARM Terminal Block (removable terminal block 

providing terminal connections to field wiring and 

physical latch for CHARM).

„ CHARMs (Characterization Module for each field signal. 

Provides basic analog to digital conversion, connectivity 

to redundant communication bus, and fault isolation).

„ Cable Extenders that provide flexibility in carrier mounting.

„ Baseplate terminators (provides bus terminations for 

redundant I/O bus).

„ 19” Migration Panels (provides DIN-rail mounting for two 

migration CIOC’s or two baseplates and cable extenders 

for installation into your standard 19” legacy cabinets).

CIOC Migration Panel

The CHARM I/O card carrier is supposed to be mounted 

on a vertical DIN-rail and can communicate with up to 

eight CHARM Baseplates mounted vertically or on migration 

panels and connected to each other through extender cables. 

The bus terminators are attached to the last baseplate.

Baseplate Migration Panel

Each CHARMs Migration Baseplate Assembly is 

ordered pre-loaded with 24 terminal blocks that are 

ready to receive field wires from 2-, 3- , and 4-wire devices. 

Electronic Marshalling eliminates the need to scramble the 

field wiring or to partition the I/O to match signals to channel 

types of specific cards. Simply connect field signals in an orderly 

fashion as desired. Insert the appropriate CHARM into each 

terminal block to complete the field circuit and the signal 

is ready to be used by any, up to four controllers.

For each Migration CIOC installation you will need to 

determine the quantity and connector cable length as 

well as the appropriate quantity of top and/or bottom 

baseplate terminators.

The Migration CIOC assembly has a height of 6 EIA units 

(10.5 inches) and is designed to be mounted at the top 

of the migration cabinet and connected to the CHARM 

baseplate assemblies through the cables and cable extenders. 

It should be noted that the CIOC can be mounted on vertical 

DIN-rail anywhere in the cabinet (front, back, side, top, 

middle, bottom) and connected to the CHARM baseplate 

assembly the same way. NOTE: the CIOC cannot be mounted 

on a horizontal DIN-rail.

The Migration CHARM baseplate assembly has a height of 

3 EIA units (5.25 inches) which allows for each installation 

to determine the mounting location within each cabinet. 

The user can decide to reuse existing wire way / cable tray, 

mount each assembly adjacent to each other, or mount with 

spacing between each assembly. DeltaV CHARMs allow for 

installation flexibility by allowing each assembly to be mounted 

as needed to achieve the best result for each customer-specific 

termination installation.

Each CHARM acts as a circuit protection device and field wiring 

disconnects. Signals are current limited or fused to protect 

against wiring faults to ground. Each CHARM provides surge 

protection to meet industry standards in the area of EMC, and is 

designed to fail during overvoltage conditions due to incorrect 

field wiring. Signal faults are isolated to the single CHARM.

CHARMs can be partially ejected to a locked position that 

disconnects the field wiring from the system to perform field 

maintenance actions or to remove power to a field device. 

Activating the CHARM latch ejects the CHARM to the detent 

position. Closing the latch locks the CHARM in place and 

isolates the field wiring for field work.

The CIOC communicates over Ethernet with up to four 

controllers, allowing great flexibility and ease of system 

expansion. Additional controllers can be added to 

accommodate increased control scope and I/O can be 

reassigned without changing the physical wiring. This allows 

you the flexibility required in migrations where over time 

I/O has been landed on one controller only to be used in 

another because of space and or available I/O.

CHARMs can be added to any existing base plate position 

and autosensed online. Additional CIOCs can be added online.

CHARM Types

All CHARM types function on the migration panel. See DeltaV 

Electronic Marshalling PDS and DeltaV IS Electronic Marshalling 

PDS for a complete listing of CHARMs and IS CHARMs.

I/O Terminal Block Options

All IS and non IS I/O Terminal Block types function on the 

migration panel by choosing the right baseplate assembly.

CHARM Keying Posts

Keying Posts function the same.

CHARM I/O Card Hardware

See DeltaV Electronic Marshalling PDS and DeltaV IS Electronic 

Marshalling for a complete description of CIOC Hardware.

CHARM I/O Card Carrier

See DeltaV Electronic Marshalling PDS and DeltaV IS 

Electronic Marshalling PDS for a complete description 

of CIOC Carrier Hardware.

Hardware Specifications

CHARM I/O Migration Panel

Environmental Specifications

Operating Temperature* -40 to 70°C (-40 to 158°F)**

Storage Temperature -40 to 85°C (-40 to 185°F)

Relative Humidity 5 to 95% , non-condensing

Protection Rating IP 20

Airborne Contaminants ISA-S71.04-1985 Airborne Contaminants Class G3

Conformal coating

Shock 10 g ½-sine wave for 11 ms

Vibration 1 mm peak-to-peak from 5 to 13.2 Hz; 

0.7 g from 13.2 to 150 Hz

Dimensions

Height 10.5 in (26.7 cm)

Depth 6.68 in (17.4 cm)

Width 19 in (48.3 cm)

Mounting 19 in (48.3 cm) EIA rails 

6 Rack Units (U) high

Redundant Migration CIOC2 with Copper Ethernet, includes redundant pair of CHARM I/O Card 2, 

CHARM I/O Carrier with Screw Terminals, Copper I/O Ports, CHARMs Baseplate Extender with Bottom 

Cable Connector, a Baseplate Identifier and a Separation Wall

SE6505T03

Redundant Migration CIOC2 with fiberoptic Ethernet, includes redundant pair of CHARM I/O Card 2, 

CHARM I/O Carrier with Screw Terminals, Fiberoptic I/O Ports, CHARMs Baseplate Extender with Bottom 

Cable Connector, a Baseplate Identifier and a Separation Wall

SE6505T04

CHARMs Migration CIOC Panel

19” Migration panel with DIN-rail support for 2 redundant migration CIOCs

SE6503T01

CHARM Baseplates for Migrations

Description Model Number

CHARMs Migration Baseplate Assembly:

„ Two CHARM Baseplates

„ Two CHARM Address Terminal Blocks with screw terminals

„ 24 Standard CHARM Terminal Blocks

„ CHARM Baseplate Extender with Cable Connectors – Top

„ CHARM Baseplate Extender with Cable Connectors – Bottom

„ 19” migration panel with DIN-rail

„ 3 Baseplate Identifiers

SE4601T03

CHARMs Migration Baseplate Assembly with 3-wire DI Fused-Injected Field Power:

„ Two CHARM Baseplates

„ Two CHARM Address Terminal Blocks with screw terminals

„ 24 3-wire DI Fused Injected Power CHARM Terminal Blocks

„ CHARM Baseplate Extender with Cable Connectors – Top

„ CHARM Baseplate Extender with Cable Connectors – Bottom

„ 19” migration panel with DIN-rail

„ 3 Baseplate Identifiers

SE4601T10

CHARMs Migration Baseplate Assembly with Fused-Injected Field Power:

„ Two CHARM Baseplates

„ Two CHARM Address Terminal Blocks with screw terminals

„ 24 Fused Injected Power CHARM Terminal Blocks

„ CHARM Baseplate Extender with Cable Connectors – Top

„ CHARM Baseplate Extender with Cable Connectors – Bottom

„ 19” migration panel with DIN-rail

„ 3 Baseplate Identifiers

SE4601T04

CHARMs Migration Baseplate Panel:

19” Migration panel with DIN-rail support for 2 CHARM Baseplates and Cable Extenders

KL4504X1-BA1

CHARM Baseplates for Migrations

Description Model Number

CHARMs Migration Baseplate Assembly with Relay Output:

„ Two CHARM Baseplates

„ Two CHARM Address Terminal Blocks with screw terminals

„ 24 Relay Output CHARM Terminal Blocks

„ CHARM Baseplate Extender with Cable Connectors – Top

„ CHARM Baseplate Extender with Cable Connectors – Bottom

„ 19” migration panel with DIN-rail

„ 3 Baseplate Identifiers

SE4601T06

IS CHARMs Migration Baseplate Assembly:

„ Two IS CHARM Baseplates

„ Two IS CHARM Address Terminal Blocks

„ 24 IS CHARM Standard Terminal Blocks

„ CHARM Baseplate Extender with Cable Connectors – Top

„ CHARM Baseplate Extender with Cable Connectors – Bottom

„ 19” migration panel with DIN-rail

„ 3 Baseplate Separation Walls

SE4608T02

Important Note:

The IS CHARMs are dimensionally different than non-IS CHARMs. The IS CHARM Baseplates are supposed to be mounted on the same 

19” migration panel than the non-S Baseplates, therefore the IS CHARMs will stick 45 mm further out of the 19” frame than non-IS CHARMs!

CHARM I/O Baseplate Address Plugs

Description Model Number

CHARM Addressing Plugs, includes Address Plugs 1 through 8 SE4602

CHARM Addressing Plugs, includes Address Plugs 1 through 4 SE4613

Prerequisites

DeltaV Electronic Marshalling hardware requires DeltaV v11.3.1 or later software.

CHARM I/O Baseplate Extender, Terminator and Cables

Description Model Number

CHARM Baseplate Extender with Cable Connectors, Top (Male)

includes a Baseplate Identifier and a Baseplate Separation Wall

SE4603T05

CHARM Baseplate Extender with Cable Connectors, Bottom (Female)

includes a Baseplate Identifier and a Baseplate Separation Wall

SE4603T06

CHARM Baseplate Terminator, Top (Male)

includes a Baseplate Identifier and a Baseplate Separation Wall

SE4604T03

CHARM Baseplate Terminator, Bottom (Female)

includes a Baseplate Identifier and a Baseplate Separation Wall

SE4604T04

CHARM Baseplate Cables, includes two 0.5m cables SE4605T02

CHARM Baseplate Cables, includes two 1m cables SE4605T03

CHARM Baseplate Cables, includes two 2m cables SE4605T04

Each vertical DIN-rail requires a DIN-rail stop to lock baseplates in position. Order VE4054DRS, which is a box of 5.

IS CHARM FUSE

Description Model Number

Fuse Holder and Fuse Assembly for 24V DC Power Supply of CHARM I/O CARD SE4610T01*

DeltaV Electronic Marshalling for Migrations

EMERSONTest Platform for Automation System

Abstract

There are different automation systems to control processes in industry. One of them is 

DeltaV, which is a product from Emerson Process Management. Recently, Sandvik 

Coromant, bought the DeltaV automation system for using it in production. To increase 

the knowledge about DeltaV at Sandvik Coromant a project was initiated with the aim to 

create a test platform and a course compendium for self learning. This thesis describes 

how the test platform was developed and its functionality

Testplattform för styrsystemet DeltaV 

Examensarbete vid Skolan för Elektro- och Systemteknik 

Sammanfattning 

För att styra processer i industrin finns det olika styrsystem. Ett av dessa är DeltaV, som 

är en produkt från Emerson Process Management. Nyligen köpte Sandvik Coromant 

styrsystemet DeltaV för att använda det i sin produktion. För att öka kunskapen om 

DeltaV på Sandvik Coromant initierades ett projekt: Att utforma en test plattform och ett 

kurskompendium för självlärning. Denna uppsats beskriver hur tesplattformen har 

utvecklats och dess funktionalitet. 

Foreword

This report presents a Master’s project at the School of Electrical Engineering at the 

Royal Institute of Technology (KTH) in Stockholm, Sweden. 

The project has been performed at Sandvik Coromant in Västberga, Sweden. I want to 

thank Sandvik Coromant for accepting me and Stefan Hedberg and Patrik Schütt for 

their support throughout the project. I would also like to thank my supervisor, Professor 

Håkan Hjalmarsson, at the School of Electrical Engineering, KTH, for his support. 

I have performed this project in collaboration with Daniel Engdahl, who also is a member 

of this project

Chapter 1 

Introduction 

Sandvik Coromant is the world’s leading manufacturer of cutting tools for the 

metalworking industry. Advanced production processes require advanced automation 

systems for the control. 

Production processes normally consist of a number of devices like valves, engines, 

sensors, transmitters and controllers. These devices are controlled and monitored from 

an automation system. 

Sandvik Coromant has recently bought a new automation system, DeltaV, which is a 

product from Emerson Process Management. To increase the knowledge about the 

automation system at Sandvik Coromant, a project was initiated with the aim to create a 

test platform and a course compendium for self learning. 

This chapter describes the problem to be solved, the background to the automation 

system DeltaV and gives the outline for the rest of the report. 

1.1 Problem 

In the following subsections the problem is described. 

1.1.1 Task 

The task in this project was to create a portable test platform for an educational purpose 

for one of the automation systems, DeltaV from Emerson Process Management, that is 

used at Sandvik Coromant. Along with the test platform, there should also be a course 

compendium that describes how to learn DeltaV by using the test platform. The test 

platform and the course compendium should together work as selflearning tools for the 

personell at Sandvik Coromant. The platform should be small enough to be portable, so 

that it can be brought to people who needs to learn DeltaV, independently of where they 

are stationed. 

Since the purpose of the task was not to learn how the production processes work, there 

was not any requirement that the test platform should be similar to any process where 

DeltaV is used at Sandvik Coromant. The only required similarity between the test 

platform and the production processes at Sandvik Coromant was supposed to be that 

similar measurement equipment was used.

1.1.2 Purpose 

The DeltaV automation system has been used at Sandvik Coromant for two years. The 

purpose of creating a test platform was to increase the knowledge of the automation 

system among the personnel. 

Since production processes are in general very costly to interrupt, a test platform was 

needed to experiment with the functions of DeltaV. With the test platform the personnel 

at Sandvik Coromant should be able to learn more about the automation system on their 

own by testing how to control a physical process. The test platform along with the course 

compendium should work as a selflearning tool. 

1.1.3 Previous work 

This is the first test platform and also the first course for DeltaV that has been developed 

at Sandvik Coromant. The manufacturer of DeltaV, Emerson Process Management, 

provides DeltaV courses. However, these courses do not come with a portable test 

platform. 

1.1.4 Description of the problem 

The desire from Sandvik Coromant was to have a physical process, a software with 

control algorithms for controlling the physical process and a course compendium on how 

to learn DeltaV. 

The requirement on the hardware in the physical process was that it should at least 

include basically the same equipment as the production processes that are controlled 

with DeltaV; relays, fuses, pressure transmitter, proximity sensors etc. Naturally, the 

hardware should also include the automation system, DeltaV. The platform should be 

small enough to be portable. 

The requirement on the software part was similarly that it should at least include some 

similar algorithms as the software for the real production processes includes. It was also 

required that the software should include an operator interface in which an operator can 

get the relevant information about the process; alarms indicating that something is 

wrong, diagrams, an illustration of the process where the operator can follow what 

happens etc. 

The requirement on the course compendium was that a person who reads it should be 

able to replicate the control software that was developed in this project. Persons taking 

the course will have the original software as a key, which they should only use if they 

experience significant problems. 

Hence, to meet all requirement from Sandvik Coromant, the finished platform and 

additional educational material should include the following: 

• The DeltaV System with controller cards, I/O cards and fieldbus cards. 

• Devices that are more or less the same as in the production processes at 

Sandvik Coromant where DeltaV is used, for instance proximity sensors or 

pressure transmitters. 

• A software control system containing similar algorithms as the production 

processes at Sandvik Coromant, for instance it might be of great relevance to 

use a PID controller. 

• An operator interface illustration that follows the physical process. The operator 

environment should also contain an alarm list. 

• A course compendium with both general information about functions in DeltaV 

and instructions on how to create the same control system as the one which was 

developed in this project. 

1.1.5 Aim 

The aim of this project was to make a test platform along with a course compendium. 

The test platform should be portable so that it can be brought to people for education in 

DeltaV regardless of where the persons are stationed. This education should give a 

general knowledge on how to use DeltaV and after completing this course the engineers 

should be able to implement simple control systems.

1.2 DeltaV-a DCS automation system 

In industry there are different automation systems; some that are more basic and some 

that are more advanced. This section will give an introduction to automation systems in 

general and the specific automation system, DeltaV, that this project concerns. Figure 

1.1 shows the hardware of the DeltaV automation system.

DeltaV is a DCS automation system. DCS is short for Distributed Control System and it 

is and automation system that has evolved from PLC.[1] 

PLC is short for Programmable Logic Controller. Originally PLC systems replaced old 

automation systems that included many relays. PLC systems did then include only 

discrete signals and when DCS was new, the difference between the two automation 

systems was that DCS also included analog signals. However, today PLC includes both 

analog and discrete signals and the difference between PLC and DCS is vague. Newer 

designs look similar both in hardware and in software.[2] 

The DeltaV automation system consists of one hardware part and one software part. In 

the following subsections both parts willl be explained. 

1.2.1 Controller, I/O and fieldbus cards 

The hardware consists of controller cards, I/O cards and fieldbus cards. 

In the controller a CPU is located and it is in the controller that the program containg 

information on how to control the process is stored. This program is downloaded to the 

controller from a workstation. The I/O cards and the fieldbus cards are capable of 

sending or/and receiving signals to and from the devices. Hence, the I/O cards and 

fieldbus cards send the signals that they get from the devices to the controller and the 

signals that they get from the controller to the devices. The controller also sends 

information to an operator interface, so that the operator of the process can monitor it. 

Figure 1.2 shows an overview of the connections for an automation system.

Figure 1.2. Overview of the connections for an automation system. A device is connected to an I/O card 

or a fieldbus card. The controller communicates with the I/O cards and the fieldbus cards and is connected 

to a workstation. The program is downloaded from a workstation to the controller. 

Figure 1.3. The network is reduced when using a fieldbus. Fieldbus cards allow communication in both 

directions and the wiring is much less when using fieldbus cards. 

In this project three fieldbus cards are used; Foundation Fieldbus, Profibus and ASInterface. Foundation Fieldbus and Profibus handle analogue signals and AS-i only 

handles discrete signals. 

The communication technology for all three fieldbus cards follows a standard model 

called OSI (Open Systems Interconnection). An OSI model divides the functions of a 

protocol into several layers. Each layer uses only the functions of the next layer, and 

only exports functionality to the preceding layer. The main feature of the OSI-model is in 

the interface between layers which dictates the specifications on how one layer interacts 

with another. This enables that a layer written by one manufacturer can operate with a 

layer from another. The OSI model contains seven layers, but the fieldbus model is only 

based on three major layers (layers 1,2 and 7 in the OSI-model). [3]

AS-Interface (AS-i) 

AS-i is the most simple fieldbus. It is designed for connecting binary devices. 

The OSI-model consists of three layers; Transmission Control, Execution Control and 

Application Layer Interface. 

The Transmission Control includes the wiring of the field devices and other components 

in the process. This layer receives messages and encodes them to physical signals. 

The signals which are in NRZ code (non-return-to-zero code) are encoded using 

Manchester II coding and then implemented with APM coding. 

The principle of Manchester encoding is that every bit period has one transition in the 

middle of the period. A positive transition represents a logic one and a negative 

transition represents a logic zero. Transitions that are not in the middle of the bit period 

do not carry any useful information. These transitions only have the purpose to set the 

signal in the state where the mid-bit transition can take place. 

With APM, pulses are created; a positive pulse is created at a low to high edge and a 

negative pulse is created at a high to low edge. In figure 1.4 the coding principle for both 

manchester encoding and APM is shown. [4][5] 

Figure 1.4. Illustration of the principle for the Manchester encoding and APM encoding. The data is coded 

to Manchester code so that a transition occurs in the middle of every bit period. A positive transition 

represents a logic one and a negative transition represents a logic zero. Transitions that are not in the 

middle of the bit period do not carry any useful information. These transitions only have the purpose to set 

the signal in the state where the mid-bit transition can take place. 

The Execution Control is of Master/Slave characteristic. The AS-i card works as the 

network master. The master automatically controls all communication over the AS-i 

cable. The master interrogates all the available AS-i addresses and repeats the process. 

The Application Layer Interface makes it possible to download the DI and DO functions 

to the controller. This enables communication between the controller and the devices. [6] 

Foundation Fieldbus 

The Foundation Fieldbus card used in this project is H1. As compared to another 

foundation fieldbus card H2, the H1 network is a lower speed and lower cost network 

than H2. 

The communication for foundation fieldbus follows the OSI model with three layers; 

Physical Layer, Communication Stack and User Application. 

The Physical Layer includes the wiring of the field devices and other components in the 

process. This layer gets encoded messages from the next layers and converts them into 

physical signals. The signals are encoded using the Manchester Biphase-L technique. 

In manchester Biphase-L code a positive transition in the middle of a bit period 

represents a logic zero and a negative transition in the middle of a bit period represents 

a logic one, see figure 1.5. 

Figure 1.5. Encoding with Manchester Biphase-L technique. In manchester Biphase-L code a positive 

transition in the middle of a bit period represents a logic zero and a negative transition n the middle of a bit 

period represents a logic one [5] 

The Communication Stack is the layer that manages communication between a device 

and a host or the communication between two devices. 

In foundation fieldbus communication with H1, the H1 card works as a Link Active 

Scheduler (LAS). A LAS is a deterministic, centralized bus scheduler that maintains a list 

of transmission times for all the data buffers in all the devices that need to transmit in 

cyclical fashion. [7] Field devices may also have Link Master capabilities and would in 

the case that the H1 card fails, work as LAS. The H1 card is the only primary Link 

Master allowed on the fieldbus segment. No other Link Master is allowed on the

segment or unpredictable results can occur. DeltaV supports one backup Link Master 

device on each fieldbus segment.[8] 

The communication between LAS and publishers and subscribers can be scheduled or 

unscheduled. 

Scheduled communication-The LAS maintains a list of transmit times for all data buffers 

in all connected devices. When it is time for a device to transmit its data, the LAS sends 

a CD (Compel Data) to that device. The device publishes (sends) data to all devices on 

the fieldbus. The devices which are configured to receive the data are called 

subscribers. 

Unscheduled communication- These transmissions are done with PN (Probe Node) or 

PT (Pass Token) and take place between transmissions of scheduled messages. The 

LAS sends a PN (Probe Node) message to see whether any device changes have been 

made. The changes are added to a live list. It is possible for a device to transmit 

unscheduled messages after it has received a PT (Pass Token) from the LAS. 

The User Application is a standard user application defined by Fieldbus Foundation. 

This layer is not defined by the OSI-model. [9] 

Profibus 

The Profibus that is used in the test platform is Profibus DP (Decentralized Periphery). 

Profibus DP is the most common Profibus. 

The OSI-model for Profibus communication consists of three layers; 

The Physical Layer defines the physical transmission characteristics. The signals are 

sent using UART (Universal Asynchronous Receiver/Transmitter). With UART, data are 

transmitted as streams of characters. Every character starts with a start bit (a 0) and 

ends with a stop bit (a 1). The start bit allows the receiver to recoginize the start of a 

new character and the stop bit makes sure that there will be a transition at the start of 

the stop bit. [10] 

The Communication Stack is a communication layer which defines the Bus Access 

Protocoll. In a Profibus DP system the communication type is master/slave and both 

multi-master and mono-master systems are possible. The protocoll used is Media Acces 

Control (MAC), which specifies the procedure when a station is permitted to transmit 

data on the bus. The MAC must ensure that only one station has the right to transmit 

data at a time. 

Hence, the requirements on the MAC protocol are that the following should be 

accomplished: 

• During communication between master stations it must be ensured that each of 

these masters gets sufficient time to execute its communication tasks within a 

precisely defined time interval. 

• Cyclic, real time data transmission is to be implemented as fast and as simple as 

possible for communication between a master and its slaves. [11] 

The multi-master system manages communication by having a token that is sent 

between the masters. When a master has the token, it can communicate with its slaves, 

see figure 1.6. [12] 

Figure 1.6. The multi-master communication of Profibus. The multi-master system manages 

communication by having a token that is sent between the masters. When a master has the token, it can 

communicate with the slaves. 

The User Layer is defined as a standard user layer. [13] 

1.2.2 Description of the Software tools in DeltaV 

The automation system has many different software applications. For this process the 

applications that have been used are: A tool for organizing the database, a tool for 

creating control modules and an animation tool for creating operator interfaces. 

The Database 

A database contains controllers, I/O and fieldbus cards in the system and control 

modules. 

The Control Modules 

In DeltaV the control of the system can be organized in control modules. A control 

module can be very simple and contain only one or two input parameters. It can also be 

more complex with for instance PID-control. 

There are several types of control modules. Which one is used depends on its purpose. 

The most important control modules are; 

• Function Block Diagrams (FBD) 

An FBD is always necessary to be able to send signals from the computer to the 

process or get signals from the process to the computer. An FBD consists of, as 

the name tells us, function blocks. A function block can be an input block, for 

instance it can contain a signal from a temperature transmitter. If this signal value 

should be shown on the operator interface, there must be a reference from the 

module containing this block to the operator interface. For each signal, only one 

input/output block can be used. It is possible to get the signal at another place, for 

instance in a different control module, by referring to it. Other function blocks are, 

for instance, multipliers and PID blocks. 

• Sequential Function Charts (SFC) 

An SFC is a control module for determining the sequence of execution. A SFC 

consists of a bipartite graph (two states are always separated by a transition). In a 

State, actions can be permormed. This means that parameter values can be set, 

for instance a light connected to a relay that gets a signal from the automation 

system can be switched on. Transitions contains the conditions that need to be 

fulfilled for the process to change states. In an SFC references are made to the 

FBDs. For instance, if it is desired to have a transition when the pressure is above 

1200 mbar, there must be a reference to the input block in the specific FBD that 

gets an input from the pressure transmitter. 

The Operator Interface 

The tool for creating an operator interface is object based. It contains images of valves, 

engines, fire etc. The objects can be animated which makes it possible to create an 

operator environment in which the operator can easily get an impression of the state of 

the process. 

1.3 Report Outline 

This report is arranged as follows: 

Chapter 2 – The platform and the course material presents how the hardware as well as 

the software for the test platform have been developed. 

Chapter 3 – Results presents the result, i.e. the finished test platform. 

Chapter 4 – Conclusions presents the conclusions of this project. The chapter also 

presents a few suggestions on how the test platform can be improved.

Chapter 2 

The platform and the course material 

The following chapter will present the platform and the system design; firstly the devices 

that are present and how the physical process works and secondly the course material. 

2.1 The system design 

When choosing the system design the requirements presented in Section 1.2.4 were 

first 

and foremost taken into account. When considering the purpose of the test platform an 

addition was made to the requirements: 

• To make a process that is easy to understand, but that is adequately advanced 

for using advanced control tools in DeltaV. 

With these requirements a system design was developed. The principle of the process is 

briefly described below. Figure 2.1 illustrates of the principle of the process. 

A pressure tank with a needle valve is filled half way up with water. When the control 

system starts, air flows into a tank through a mass flow controller and the pressure in the 

tank is controlled to stabilize around ~1500 mbar. 

When the pressure has been held around 1500 mbar for a specified time a pneumatic 

valve will open and tap out water into an open tank that is placed below the pressure 

tank. The valve will stay open until a level sensor indicates that the tank is full. 

When the open tank is full a heating plate will start to heat up the water. The 

temperature is controlled with on/off controlling to ~35 ºC. 

To continue the process the open tank has to be removed, emptied and put back in 

place. This will restart the process. This can be repeated until the pressure tank is 

empty. 

• Buttons 

The button device consists of one red button with red light and one green button 

with green light. The buttons can also be lit. 

Devices connected to Foundation Fieldbus

• Pressure transmitter 

A pressure transmitter measures and transmits the pressure value. 

• Temperature transmitter 

A temperature transmitter measures and transmits the temperature. 

Devices connected to Profibus

• Mass Flow Controller 

A mass flow controller controls the inflow of gas from one place to another. 

Devices connected to Discrete Out

• Relays 

A relay is a device that can control other devices with on and off. 

 Devices connected to relays 

 Light bulb 

 Heat plate 

• Valve Island 

A Valve Island is a device with several electrically controlled valves. The valves 

are normally closed, but they open when they receive a signal from the controller. 

Devices connected to Discrete In

• Capacitive Proximity Sensor (Level Transmitter) 

A capacitive proximity sensor is used for detecting objects that are proximal to the 

sensor. 

Other objects in the test platform

• Pressure tank 

A pressure tank was constructed for the test platform. It is designed to be able to 

handle a pressure of 10 bar and to contain both water and air. It has four 

connections; one that can be connected to the mass flow controller, one that can 

be connected to the pressure transmitter, one that can be connected to the 

needle valve and one that can be connected to a pneumatic valve. It also has one 

inflow so that it can be filled with water. 

• Open tank 

The open tank is a much less advanced tank than the pressure tank. It is open 

and therefore it must not be able to handle any pressure and it does not have any 

connections. It is metallic so that it can be detected by an inductive proximity 

sensor. 

• Pneumatic Valve 

A pneumatic valve is normally closed, but opens if it is exposed to pressurized air. 

• Compressor / Pressurized air media 

Depending on where the platform is used a compressor or pressurized air media 

is used. A compressor is used when there is no pressurized air media available. 

Since a compressor has a high sound level and in addition is heavy to carry it is 

only meant to be used when there is no other option.

Detailed description of the Physical Process 

1. DeltaV controller, I/O and 

fieldbus cards 

2. Pressure transmitter 

3. Mass Flow Controller 

4. Valve island 

5. Inductive Proximity Sensor 

6. Capacitive Proximity Sensor 

7. Temperature Transmitter 

8. Push buttons 

9. Relays 

10. Heat plate 

11. Light bulb 

12. Pressure tank 

13. Needle valve 

14. Pneumatic valve 

15. Open tank

As mentioned the physical process is a process with no actual purpose. The only 

purpose is to have a physical process to follow while learning how to use DeltaV. In the 

previous subsection all devices and other things in the physical process were described. 

This section will instead focus on how the devices are used to create a functional 

automated process. 

Figure 2.2 illlustrates how the objects in the process are connected. 

Before starting the process, the pressure tank is partly filled with water and the open 

tank is empty. On the button device the red light is on. A compressor that is not included 

in the control should be switched on by the operator. (The compressor could as 

mentioned above be exchanged with pressurized air media). The compressor exposes 

the valve island with pressurized air. 

The process is started by pressing a green button. This button exists both in the 

operator interface and physically on the test platform. When the button is pressed the 

green light on the button device will be switched on and the red light which indicates that 

the process is off will be switched off. The valve island will open the valve that is 

connected to the mass flow controller. The Mass Flow Controller will then be exposed to 

pressurized air. 

The mass flow controller will control the pressure in the pressure tank so that it stabilizes 

at approximately 1500 bar. The control is done with the software with PID control. How 

the PID parameters are set, is described in the Subsection 2.2.2.1. 

When the pressure in the pressure tank has been between 1400 mbar and 1600 mbar 

for one minute, the inductive sensor signals that the open tank is in its place below the 

pressure tank and the capacitive signals that it is not already filled with water, the valve 

island will open the valve that is connected to the pneumatic valve. When the pneumatic 

valve is exposed to the pressurized air from the valve island, it will open and water will 

flow out from the pressure tank. 

The valve on the valve island that is connected to the pneumatic valve will be open until 

the capacitive sensor indicates that the water level is high. The pneumatic valve will 

close when it does no longer get pressurized air from the valve on the valve island. 

If the water temperature is less than 35 C, the heat plate starts heating. The heater will 

only start if there is a tank filled with water on it. 

When the water temperature has reached 35 C, the heating will stop. For the process 

to go on, the open tank has to be removed, and put back. This will bring the process 

back to the state when the pressure in the tank is controlled to be between 1400 and 

1600 mbar. From that state it will continue and the process can go on until the pressure 

tank is empty. 

If the open tank would not have been emptied when the water temperature was higher 

than 35 C, the heating would have started all over again when the temperature is below 

35 C. The heating will always start when the open tank is in place and filled with cold 

water, unless the red button (the emergency button) has been pressed. 

The red button can be pressed at any time in the process and the process will enter its 

standby state. In the stand by state everything is off except for the red light on the button 

device which is on. 

EMERSONS-series Mass Connection Solutions

„ Fast, easy and error-free cabinet wiring

„ Modular design, improves reliability

„ Lowers overall termination footprint

„ Significant labor and work reduction

„ Loop disconnect feature for Analog Signals

„ LED’s and replaceable Fuses for discrete Signals

„ Termination Fault Detection between discrete 

traditional I/O Cards and Mass Connection 

Board Signals

Introduction

The DeltaV™ S-series Mass Connection Solutions provide fast, 

easy and reliable connection from field devices to DeltaV 

simplex and redundant, high density traditional I/O Cards, 

while providing several wiring options. 

The modular design of the Mass Connection Boards further 

helps to lower the overall termination footprint due to flexible 

mounting capabilities.

Ribbon cable connectors will be used to connect the Mass 

Connection Boards easily to the simplex or redundant, high 

density traditional I/O Cards, where loop and termination 

fault diagnostic information are available.

Benefits

Fast, easy way to connect terminals. The DeltaV simplex and 

redundant high density traditional I/O Cards can be easily wired 

to the Mass Connection Boards within seconds. 

No tools are necessary to connect the ribbon cables, so you 

can significantly reduce labor costs by eliminating additional 

cabinet wiring.

Modular design, improves reliability. The modular designed 

Mass Connection Boards are more reliable than other traditional 

solution, by splitting the Signals up, to a max of 16 Signals.

Optimization of space. The DeltaV S-series Mass Connection 

Solutions offer significant space advantages by integrating all 

needed cabinet wiring components on one board.

Significant labor work reduction. No need for cross wiring 

between I/O cards and Mass Connection Boards anymore, due 

to flexible 1:1 ribbon cable based connectivity. 

Significant cost reduction. Since off-the-shelf Ribbon cables 

can be used inside a Cabinet with a max. Length of 3 m, 

significant cost reductions can be achieved. 

In some cases, longer cables are needed for connections 

between two Cabinets. 6m long Standard Round Ribbon Cables 

can be ordered to be used with the Mass Connection Solutions.

Loop Disconnect Features for all Signal Types. For each 

Signal Type, a loop disconnect feature is available on the Mass 

Connection boards. 

On the AI/AO Mass Connection boards, this is realized using a 

specific knife edge disconnect setup with 2mm test holes, in 

this way maintenance or calibration work can be performed 

without disturbing the 4-20 mA loop based Signal.

On the DI/DO Mass Connection boards, this is realized using 

replaceable fuses. In this way, loop power to the field can be 

easily disconnected, during maintenance activities.

Termination Fault Detection. With the DI/DO Mass 

Connection boards, power or cable failures can now be 

detected by DeltaV Diagnostic when used with the new

Plus Cards.

Product Description

AI/AO Plus Mass Connection Board

The AI/AO Plus Mass Connection Board connects to the new 

S-series Plus (simplex or redundant) AI, 16 Channel and AO, 

16 Channel cards by using either two ribbon cables with 24-Pin 

connectors or the 48-Pin special Round Ribbon Cable, which is 

required if the distance is longer than 3m.

Up to 16 Analog, 4-20 mA HART based Field devices can be 

connected to the AI/AO Plus Mass Connection Boards by screw 

terminals. 2- And 4- wire Devices are supported by the 

3- row screw architecture, so you can choose on a Channel 

by Channel basis.

For each Channel, a loop disconnect feature with 2mm test 

holes is implemented. In this way, maintenance or calibration 

work can be performed at any time, without disturbing the 

4-20 mA loop based Signal.

Please refer to the Cross Reference List for your application. 

DI Mass Connection Board (for simplex DI Card)

This DI Mass Connection Solution (set of two boards) connects 

to the existing simplex S-series DI, 32 Channel, 24 VDC, Dry 

Contact cards by using either two ribbon cables with 20-Pin 

connectors or two of the 20-Pin standard Round Ribbon Cable, 

which is required if the distance is longer than 3m.

Up to 16, 24 VDC based discrete input Signals can be connected 

to each of the DI Mass Connection Boards by screw terminals. 

Dry Contact or 24 VDC Isolated Field Signals are supported by 

the 2- row screw architecture.

Yellow LED’s are providing status Indication for each Channel, 

while the replaceable fuses can be used to disconnect loop 

power to the field, during maintenance activities.

Please refer to the Cross Reference List for your application. 

DI Plus Mass Connection Board (for DI Plus Card)

The DI Plus Mass Connection Solution (set of two boards) 

connects to the new redundant S-series Plus DI, 32 Channel, 

24 VDC, Dry Contact cards by using either two ribbon cables 

with 20-Pin connectors or two of the 20-Pin standard Round 

Ribbon Cable, which is required if the distance is longer 

than 3m. 

Up to 16, 24 VDC based discrete input Signals can be 

connected to each of the DI Plus Mass Connection Boards by 

screw terminals. Dry Contact or 24 VDC Isolated Field Signals 

are supported by the 2- row screw architecture.

Yellow LED’s are providing status Indication for each Channel, 

while the replaceable fuses can be used to disconnect loop 

power to the field, during maintenance activities.

A Termination Fault Detection feature is built into each of 

the DI Plus Mass Connection boards which allows the new

redundant S-series Plus DI, 32 Channel, 24 VDC, Dry Contact 

cards to detect power or cable failures on the board. There is a 

jumper on the board to be able to turn this feature off, in case 

rewiring needs to be performed while the process is running. 

The new S-series Plus DI, 32 Channel, 24 VDC, Dry Contact 

card does have two new parameters in the Explorer view, 

one for each cable connection. When these Parameters are 

turned on, DeltaV Diagnostics will mark the status of affected 

Signals accordantly.

Please refer to the Cross Reference List for your application.

DO Plus Mass Connection Board

The DO Plus Mass Connection Solution (set of four boards) 

connects to the existing simplex S-series DO, 32 Channel, 24 

VDC, High-Side cards as well to the new redundant S-series 

Plus DO, 32 Channel, 24 VDC, High-Side cards by using either 

two ribbon cables with 20-Pin connectors or two of the 20-Pin 

standard Round Ribbon Cable, which is required if the distance 

is longer than 3m. Two DO Plus Mass Connection boards 

need to be daisy chained to get to 16 Channels, which can be 

connected back to the card. A short ribbon cable with 20-Pin 

connectors can be used for that purpose too.

Up to 8 Field devices can be connected to each of the DO Plus 

Mass Connection Boards by screw terminals. Either +24 VDC 

high-side relay outputs or voltage free relay contacts can 

be used, pending on the position of the fuse, which can be 

jumpered for this reason.

Yellow LED’s are providing status Indication for each Channel, 

while the replaceable fuses can be used to disconnect loop 

power to the field, during maintenance activities.

A Termination Fault Detection feature is built into each of 

the DO Plus Mass Connection boards which allow the new 

redundant S-series Plus DO, 32 Channel, High-Side cards to 

detect power or cable failures on the board. There is a jumper 

on the board to be able to turn this feature off, in case rewiring 

needs to be performed while the process is running

A-BPowerFlex 700 Adjustable Frequency AC Drive

Product Overview 

The PowerFlex® 700 AC drive offers outstanding performance in an easy-to-use drive that you have come to 

expect from Rockwell Automation. The PowerFlex 700 AC drive is designed to control three-phase induction 

motors in applications with requirements ranging from the simplest speed control to the most demanding 

torque control. The drive has volts per hertz, sensorless vector, and vector control. Vector control includes 

Allen-Bradley’s patented Force Technology, which provides world class motor control.

Flexible Packaging and Mounting

• IP20, NEMA / UL Type 1 – For conventional mounting inside or outside a control cabinet. Conduit plate is removable for easy 

installation and replacement without disturbing conduit.

• IP54, NEMA / UL Type 12 – standalone, wall mount drives are available for dust-tight applications with power ratings 75…200 Hp 

(Frames 5 and 6). 

• IP54, NEMA / UL Type 12 – Flange mount drives with an IP00, NEMA / UL Type Open front. These can be installed in a user supplied 

cabinet to meet IP54, NEMA / UL Type 12. This allows most heat to be exhausted out the back of the cabinet while keeping the cabinet 

protected. Power ratings range 75…200 Hp (Frames 5…6).

• Zero-Stacking™ Drive– Frame 0…6 drives can be mounted next to each other with no reduction of surrounding air temperature rating 50 °C (122 °F). This unique bookshelf design also allows access to one drive without disturbing another.

• Conformal Coating – The drive is coated in an insulator, or non-conducting substance, that helps protect it from moisture, fungus, 

dust, corrosion, abrasion, and other environmental stresses caused by highly polluted atmospheres. The coating improves product

lifetime expectancy when exposure to corrosive environment is present. It helps maintain long-term surface insulation resistance, 

ensuring operational integrity of the assembly.

Space Saving Hardware Features

• Integral EMC Filtering plus built-in DC bus choke common mode cores and common mode capacitors provides a compact, all-in-one 

package solution for meeting EMC requirements. Frames 0…6 only.

• Internal Communications allows you to integrate the drive into the manufacturing process. Status indicators for all internal 

communication options are visible on the cover for easy setup and monitoring of drive communications. You can easily manage 

information from shop floor to top floor and seamlessly integrate their complete system as they control, configure, and collect data.

• Integral Dynamic Brake Transistor delivers a cost-effective means of switching regenerative energy without costly external 

chopper circuits. These internal transistors are available in power ratings 0.5…200 Hp.

• Internal Dynamic Brake Resistor (up to 25 Hp) requires no extra panel space, and supplies a large amount of braking torque for 

short periods.

Easy to Use Human Interface Tools

The PowerFlex 7-Class AC drives provide common Human Interface tools that are familiar and easy to use. These include the LCD Human 

Interface modules and PC-based configuration tools.

Human Interface Module

The LCD Human Interface modules provide:

• Large and easy to read 7 line x 21 character backlit display

• Variety of languages (English, French, German, Italian, Spanish, Portuguese, Dutch)

• Alternate function keys for shortcuts to common tasks

• “Calculator-like” number pad for fast and easy data entry (Full Numeric version only)

• Control keys for local start, stop, speed, and direction

• Remote versions for panel mount application

Connected Components Workbench Software

Connected Components Workbench™ programming and configuration software leverage proven Rockwell Automation and Microsoft® Visual 

Studio® technologies for fast and easy drive configuration, controller programming, and integration with the HMI editor.

The workbench includes:

• an intuitive interface and startup wizards

• localized language support

• online and offline configuration

• context-sensitive help

• supports PowerFlex drives, Micro800™ programmable controllers, and PanelView™ component graphic terminals

Outstanding Control and Performance

Multiple motor control algorithms allow performance that is matched to the application need:

• Volts/Hertz for simple Fan and Pump applications.

• Sensorless Vector for high torque production over a wide speed range.

• Vector for outstanding torque regulation and excellent low speed/zero speed 

performance (w/Vector Control cassette).

The PowerFlex 700 drive’s Vector Control uses Allen-Bradley’s patented Force Technology 

which provides excellent low-speed performance – whether it is operated with or without 

feedback. While this industry-leading control provides the highest level of drive performance, 

it is as easy to use as any general-purpose drive available. 

Drives Features

• Fast-acting Current Limit and Bus Voltage Regulation result in maximum accel/decel without tripping.

• High-speed analog inputs improve drive response to torque or speed commands.

• Programming flexibility allows parameters to be linked within the drive.

• Flying Start delivers smooth and instantaneous connection into rotating loads, regardless of commanded direction, without the need 

for any speed feedback.

• Integral Process PI Control can eliminate the need for a separate process loop controller.

• Inertia Ride-Through offers tripless operation during a prolonged power outage by using the rotating energy that is stored in high 

inertia, low-friction loads.

• Position Indexer/Speed Profiler uses a 16-step indexer to provide point-to-point positioning or velocity profiling based on encoder 

counts, digital inputs, parameter levels, or time.

• TorqProve™ assures control of the load when transferring control between the drive and a mechanical brake.

• Speed Regulation – Open Loop or Closed Loop

– Slip Compensation delivers a minimum 0.5% speed regulation without feedback hardware.

– Droop allows drives to load share without fighting each other.

– Encoder Feedback provides up to 0.001% speed regulation for the tightest application requirements.

• Torque Regulation – Open Loop or Closed Loop

– Open Loop torque regulation provides 5% regulation.

– Encoder Feedback provides 2% regulation and the ability to hold full load at zero speed.

Unsurpassed Capability in Network Communications

PowerFlex drives are fully compatible with the wide variety of Allen-Bradley DPI™ communication adapters, offering the following benefits:

Drive, Fuse, and Circuit Breaker Ratings

The PowerFlex 700 can be installed with input fuses or an input circuit breaker. National and local industrial safety regulations and/or 

electrical codes can determine additional requirements for these installations.

The tables on the following pages provide recommended AC line input fuse and circuit breaker information. See Fusing and Circuit Breakers 

below for UL and IEC requirements. Sizes that are listed are the recommended sizes based on 40 °C (104 °F) and the U.S. NEC. Other country, 

state, or local codes can require different ratings. Tables with DC link fuse recommendations for DC input drives are also provided.

Fusing

The recommended fuse types are listed below. If available current ratings do not match those listed in the tables that are provided, choose 

the next higher fuse rating.

• IEC – BS88 (British Standard) Parts 1 and 2, EN60269-1, Parts 1 and 2(1), type gG or equivalent must be used.

• UL – UL Class CC, T, RK1, or J must be used for Frames 0…6.

Circuit Breakers

The “non-fuse” listings in the following tables include inverse time circuit breakers, instantaneous trip circuit breakers (motor circuit 

protectors) and 140M Motor Protection Circuit Breakers (MPCBs) that are rated for use as self-protected combination motor controller 

(Frames 0…6 only). If one of these is chosen as the desired protection method, the following requirements apply:

• IEC – Both types of circuit breakers and 140M self-protected combination motor controllers (Frames 0…6 only) are acceptable for IEC 

installations.

• UL – Only inverse time circuit breakers and the specified 140M self-protected combination motor controllers (Frames 0…6 only) are 

acceptable for UL installations.

Circuit Breaker – inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.

(5) Motor Circuit Protector – instantaneous trip circuit breaker. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.

(6) Bulletin 140M devices with adjustable current range must have the current trip set to the minimum range that the device does not trip.

(7) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 208V Wye or Delta, 240V Wye or Delta, 480Y/277V or 600Y/347V. Not UL Listed for use on 480V or 600V Delta/

Delta, corner ground, or high-resistance ground systems.

(8) The A1C ratings of the Bulletin 140M devices can vary. See publication 140-TD005 or 140M-TD002.

(9) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(10) UL Type 12/IP54 (flange mount) heat sink ambient temperature rating is 40° C/ambient of unprotected drive portion (inside enclosure) is 55° C. The ambient temperature for the UL Type 12/

IP54 standalone drives is 40° C.

(11) Must remove top label and vent plate, drive enclosure rating is IP00, NEMA / UL Type Open.

(12) Frames 0…4 temperature rating is for NEMA / UL Type Open. The adhesive top label must be removed to operate drive at this temperature. Frames 5 and 6 do not have a top label.

(13) Drives have dual current ratings; one for normal duty applications, and one for heavy-duty applications. The drive can be operated at either rating.

(14) Note: 600V class drives below 77 amps (Frames 0…4) are declared to meet the Low Voltage Directive and UK Low Voltage Regulations. It is the responsibility of the user to determine 

compliance to the EMC Directive and UK EMC Regulations. 

(15) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume that is specified 

in this column. Application-specific thermal considerations can require a larger enclosure.

(16) Temperature rating is for IP20, NEMA / UL Type 1. For IP00, NEMA Type Open the temperature rating is 65 °C for the control board and 40 °C for the heat sink entry air.

(17) 40 °C = 104 °F; 45 °C = 113 °F; 50 °C = 122 °F; 55 °C = 131 °F

Cable Recommendations

Power Cable Types Acceptable for 200…600 Volt Installations

Various cable types are acceptable for drive installations. For many installations, unshielded cable is adequate, provided it can be separated 

from sensitive circuits. As an approximate guide, allow a spacing of 0.3 meters (1 foot) for every 10 meters (32.8 feet) of length. In all cases, 

long parallel runs must be avoided. Do not use cable with an insulation thickness less than or equal to 15 mils (0.4mm/0.015 in.). Use Copper 

wire only. Wire gauge requirements and recommendations are based on 75 °C (167 °F). Do not reduce wire gauge when using higher 

temperature wire. See table below.

Unshielded

THHN, THWN or similar wire is acceptable for drive installation in dry environments provided adequate free air space and/or conduit fill rates 

limits are provided. Do not use THHN or similarly coated wire in wet areas. Any wire that is chosen must have a minimum insulation 

thickness of 15 mils and should not have large variations in insulation concentricity.

Shielded/Armored Cable

Shielded cable contains all general benefits of multi-conductor cable with the added benefit of a copper braided shield that can contain 

much of the noise that is generated by a typical AC drive. Strong consideration for shielded cable should be given in installations with 

sensitive equipment such as weigh scales, capacitive proximity switches and other devices that may be affected by electrical noise in the 

distribution system. Applications with large numbers of drives in a similar location, imposed EMC regulations or a high degree of 

communications/ networking are also good candidates for shielded cable. 

Shielded cable may also help reduce shaft voltage and induced bearing currents for some applications. In addition, the increased impedance 

of shielded cable may help extend the distance that the motor can be located from the drive without the addition of motor protective devices 

such as terminator networks.

Consideration should be given to all general specifications that are dictated by the environment of the installation, including temperature, 

flexibility, moisture characteristics and chemical resistance. In addition, a braided shield should be included and be specified by the cable 

manufacturer as having coverage of at least 75%. An additional foil shield can greatly improve noise containment. 

A good example of recommended cable is Belden 295xx (xx determines gauge). This cable has four (4) XLPE insulated conductors with a 

100% coverage foil and an 85% coverage copper braided shield (with drain wire) surrounded by a PVC jacket.

Other types of shielded cable are available, but the selection of these types may limit the allowable cable length. Particularly, some of the 

newer cables twist four conductors of THHN wire and wrap them tightly with a foil shield. This construction can greatly increase the cable 

charging current required and reduce the overall drive performance. Unless specified in the individual distance tables as tested with the 

drive, these cables are not recommended and their performance against the lead length limits supplied is not known. 

Maximum Motor Cable Lengths

For information on maximum motor cable lengths, see the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, 

publication DRIVES-IN001.

Power Wiring

The PowerFlex 700 has the following built in protective features to help simplify installation:

• Ground fault protection during startup and running ensures reliable operation

• Electronic motor overload protection increases motor life

• Removable MOV to ground and common mode capacitors to ground ensure compatibility with ungrounded systems. These devices 

must be disconnected if the drive is installed on a resistive grounded distribution system, an ungrounded distribution system, a B 

phase grounded distribution system or impedance grounded system. These devices must also be disconnected if the drive power 

source is a regenerative unit (such as a bus supply and brake) or is DC fed from an active converter.

• 6 kV transient protection provides increased robustness for 380…480V system voltages

There are many other factors that must be considered for optimal performance in any given application. The block diagram below highlights 

the primary installation considerations. Consult the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication 

DRIVES-IN001 for detailed recommendations on input power conditioning, dynamic braking, reflected wave protection and motor cable 

types.

A-BAdjustable Frequency AC Drive

Ungrounded Distribution Systems

ATTENTION: PowerFlex 40 drives contain protective MOVs that are 

referenced to ground. These devices must be disconnected if the drive is 

installed on an ungrounded or resistive grounded distribution system.

Disconnecting MOVs

To prevent drive damage, the MOVs connected to ground shall be 

disconnected if the drive is installed on an ungrounded distribution 

system where the line-to-ground voltages on any phase could exceed 

125% of the nominal line-to-line voltage. To disconnect these devices, 

remove the jumper shown in the Figures 1.1 and 1.2.

1. Turn the screw counterclockwise to loosen.

2. Pull the jumper completely out of the drive chassis.

3. Tighten the screw to keep it in place.

Figure 1.1 Jumper Location (Typical)

Solid state equipment has operational characteristics differing from those of 

electromechanical equipment. Safety Guidelines for the Application, Installation 

and Maintenance of Solid State Controls (Publication SGI-1.1 available from your 

local Rockwell Automation sales office or online at http://

www.rockwellautomation.com/literature) describes some important differences 

between solid state equipment and hard-wired electromechanical devices. Because 

of this difference, and also because of the wide variety of uses for solid state 

equipment, all persons responsible for applying this equipment must satisfy 

themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or 

consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative 

purposes. Because of the many variables and requirements associated with any 

particular installation, Rockwell Automation, Inc. cannot assume responsibility or 

liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of 

information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written 

permission of Rockwell Automation, Inc. is prohibited.

Throughout this manual, when necessary we use notes to make you aware of safety 

considerations

Allen-Bradley, Rockwell Automation, and PowerFlex are registered trademarks of Rockwell Automation, Inc. DriveExplorer, DriveExecutive, and SCANport are trademarks of Rockwell Automation, Inc. PLC is a registered trademark of Rockwell Automation, Inc

The information below summarizes the changes to the PowerFlex 40 User Manual since the August 2008 release.

Description of New or Updated Information Page(s)

Minimum Enclosure Volume column and new footnotes added. 1-9, A-2

Drive, Fuse & Circuit Breaker Ratings topic updated. A-1

Electronic Motor Overload Protection description updated. A-4

The information below summarizes the changes to the PowerFlex 40 

User Manual since the April 2008 release.

Manual Updates

Description of New or Updated Information Page(s)

Description of A056 revised. 3-17

Description of A059/A062 revised. 3-19

Fault description for F3 revised. 4-3

A table row for electrical specifications added. A-4

Graphic for the “Network Wiring” section revised. C-1

Second last paragraph in the “Network Wiring” section revised. C-2

Text in the “Writing (06) Logic Command Data” section revised. C-4

Frequency source for logic command 001 of bits 14, 13, and 12 corrected. C-4

Text in the “Writing (06) Reference” section revised. C-5

Parameter Updates

The following parameters have been updated with firmware version 6.xx.

Parameter Number Description Page

[Relay Out Sel] A055 Function of option 20, ParamControl, 

changed.

Option 24, MsgControl, added.

3-16

[Relay Out Sel] A058, A061 Function of option 20, ParamControl, 

changed.

Option 24, MsgControl, added.

3-18

The information below summarizes the changes to the PowerFlex 40 

User Manual since the January 2007 release.

Manual Updates

Description of New or Updated Information Page(s)

Input description and attention text for Multiple Digital Input Connection 

example corrected.

1-22

New method of changing speed reference for IP66, NEMA/UL Type 4X rated 

drives described.

2-2

Description for Up Arrow and Down Arrow keys revised. 2-4

Fault description for F3 revised. 4-3

Graphic for the “Network Wiring” section revised. C-1

Descriptions for bits 6, 7, and 15 of register address 8192 (Logic Command) 

updated.

C-4

New information on reading register address 8192 added. C-4

New information on reading register address 8193 added. C-5

Graphic for the “Connecting an RS-485 Network” section corrected. D-4

New method for inverting sign of PID error added.

New Parameter

The following parameter has been added with firmware version 5.xx.

Parameter Updates

The following parameters have been updated with firmware version 5.xx.

Description of New or Updated Information Page(s)

Input description and attention text for Multiple Digital Input Connection 

example corrected.

1-22

New method of changing speed reference for IP66, NEMA/UL Type 4X rated 

drives described.

2-2

Description for Up Arrow and Down Arrow keys revised. 2-4

Fault description for F3 revised. 4-3

Graphic for the “Network Wiring” section revised. C-1

Descriptions for bits 6, 7, and 15 of register address 8192 (Logic Command) 

updated.

C-4

New information on reading register address 8192 added. C-4

New information on reading register address 8193 added. C-5

Graphic for the “Connecting an RS-485 Network” section corrected. D-4

New method for inverting sign of PID error added. F-6

Parameter Number Description Page

[PID Invert Error] A167 New 3-44

Parameter Number Description Page

[Control Source] d012 Options 7 and 8 added. 3-5

[Start Source] P036 Description revised for option 6. 3-10

[Relay Out Sel] A055 Description revised for option 20. 3-16

[Relay Out Level] A056 Description revised. 3-17

[Opto Outx Sel] A058, A061 Description revised for option 20. 3-18

[Opto Outx Level] A059, A062 Description revised. 3-19

[Internal Freq] A069 Default value for IP66, NEMA/

UL Type 4X drives is 0.0 Hz.

Default value for IP20 rated drives is 

60.0 Hz.

3-22

[PID Trim Hi] A130 Description revised. 3-38

[PID Trim Lo] A131 Description revised. 3-38

ATTENTION: The drive contains high voltage capacitors which take 

time to discharge after removal of mains supply. Before working on 

drive, ensure isolation of mains supply from line inputs [R, S, T (L1, 

L2, L3)]. Wait three minutes for capacitors to discharge to safe voltage 

levels. Failure to do so may result in personal injury or death.

Darkened display LEDs is not an indication that capacitors have 

discharged to safe voltage levels.

!

ATTENTION: Only qualified personnel familiar with adjustable 

frequency AC drives and associated machinery should plan or 

implement the installation, start-up and subsequent maintenance of the 

system. Failure to comply may result in personal injury and/or 

equipment damage.

!

ATTENTION: This drive contains ESD (Electrostatic Discharge) 

sensitive parts and assemblies. Static control precautions are required 

when installing, testing, servicing or repairing this assembly. 

Component damage may result if ESD control procedures are not 

followed. If you are not familiar with static control procedures, 

reference A-B publication 8000-4.5.2, “Guarding Against Electrostatic 

Damage” or any other applicable ESD protection handbook.

!

ATTENTION: An incorrectly applied or installed drive can result in 

component damage or a reduction in product life. Wiring or application 

errors, such as, undersizing the motor, incorrect or inadequate AC 

supply, or excessive ambient temperatures may result in malfunction of 

the system.

!

ATTENTION: The bus regulator function is extremely useful for 

preventing nuisance overvoltage faults resulting from aggressive 

decelerations, overhauling loads, and eccentric loads. However, it can 

also cause either of the following two conditions to occur.

1. Fast positive changes in input voltage or imbalanced input voltages 

can cause uncommanded positive speed changes;

2. Actual deceleration times can be longer than commanded 

deceleration times

However, a “Stall Fault” is generated if the drive remains in this state 

for 1 minute. If this condition is unacceptable, the bus regulator must be 

disabled (see parameter A117). In addition, installing a properly sized 

dynamic brake resistor will provide equal or better performance in most 

cases.

ATTENTION: To avoid an electric shock hazard, ensure isolation of 

mains supply from line inputs [R, S, T (L1, L2, L3)] and wait three 

minutes for capacitors to discharge before removing the external cover. 

Once the cover is removed, verify that the voltage on the bus capacitors 

has discharged before performing any work on the drive. Measure the 

DC bus voltage at the DC– and DC+ terminals on the Power Terminal 

Block (refer to page 1-13 for Power Terminal descriptions). The voltage 

must be zero

Mounting Considerations

Debris Protection

A plastic top panel is included with the drive. Install the panel to prevent 

debris from falling through the vents of the drive housing during 

installation. Remove the panel for IP20, NEMA/UL Type Open 

applications.

Storage

• Store within an ambient temperature range of -40° to +85°C.

• Store within a relative humidity range of 0% to 95%, 

non-condensing.

• Do not expose to a corrosive atmosphere.

AC Supply Source Considerations

General Grounding Requirements

The drive Safety Ground – (PE) must be connected to system 

ground. Ground impedance must conform to the requirements of 

national and local industrial safety regulations and/or electrical codes. 

The integrity of all ground connections should be periodically checked.

Figure 1.3 Typical Grounding

Ground Fault Monitoring

If a system ground fault monitor (RCD) is to be used, only Type B 

(adjustable) devices should be used to avoid nuisance tripping.

Safety Ground – (PE)

This is the safety ground for the drive that is required by code. One of 

these points must be connected to adjacent building steel (girder, joist), a 

floor ground rod or bus bar. Grounding points must comply with national 

and local industrial safety regulations and/or electrical codes.

Motor Ground

The motor ground must be connected to one of the ground terminals on 

the drive.

Shield Termination – SHLD

Either of the safety ground terminals located on the power terminal 

block provides a grounding point for the motor cable shield. The motor 

cable shield connected to one of these terminals (drive end) should also 

be connected to the motor frame (motor end). Use a shield terminating or 

EMI clamp to connect the shield to the safety ground terminal. The 

conduit box option may be used with a cable clamp for a grounding point 

for the cable shield.

When shielded cable is used for control and signal wiring, the shield 

should be grounded at the source end only, not at the drive end.

RFI Filter Grounding

Using single phase drives with integral filter, or an external filter with 

any drive rating, may result in relatively high ground leakage currents. 

Therefore, the filter must only be used in installations with grounded 

AC supply systems and be permanently installed and solidly 

grounded (bonded) to the building power distribution ground. Ensure 

that the incoming supply neutral is solidly connected (bonded) to the 

same building power distribution ground. Grounding must not rely on 

flexible cables and should not include any form of plug or socket that 

would permit inadvertent disconnection. Some local codes may require 

redundant ground connections. The integrity of all connections should be 

periodically checked

Fuses and Circuit Breakers

The PowerFlex 40 does not provide branch short circuit protection. This 

product should be installed with either input fuses or an input circuit 

breaker. National and local industrial safety regulations and/or electrical 

codes may determine additional requirements for these installations. 

Fusing

The PowerFlex 40 has been UL tested and approved for use with input 

fuses. The ratings in the table that follows are the minimum 

recommended values for use with each drive rating. The devices listed in 

this table are provided to serve as a guide.

Bulletin 140M (Self-Protected Combination Controller)/UL489 

Circuit Breakers

When using Bulletin 140M or UL489 rated circuit breakers, the 

guidelines listed below must be followed in order to meet the NEC 

requirements for branch circuit protection.

• Bulletin 140M can be used in single and group motor applications.

• Bulletin 140M can be used up stream from the drive without the 

need for fuses.

Fuses and Circuit Breakers

!

ATTENTION: To guard against personal injury and/or equipment 

damage caused by improper fusing or circuit breaker selection, use only 

the recommended line fuses/circuit breakers specified in this section.

Power Wiring

!

ATTENTION: National Codes and standards (NEC, VDE, BSI, etc.) 

and local codes outline provisions for safely installing electrical 

equipment. Installation must comply with specifications regarding wire 

types, conductor sizes, branch circuit protection and disconnect 

devices. Failure to do so may result in personal injury and/or equipment 

damage.

!

ATTENTION: To avoid a possible shock hazard caused by induced 

voltages, unused wires in the conduit must be grounded at both ends. 

For the same reason, if a drive sharing a conduit is being serviced or 

installed, all drives using this conduit should be disabled. This will help 

minimize the possible shock hazard from “cross coupled” power leads.

Motor Cable Types Acceptable for 200-600 Volt Installations

A variety of cable types are acceptable for drive installations. For many 

installations, unshielded cable is adequate, provided it can be separated 

from sensitive circuits. As an approximate guide, allow a spacing of 0.3 

meters (1 foot) for every 10 meters (32.8 feet) of length. In all cases, 

long parallel runs must be avoided. Do not use cable with an insulation 

thickness less than 15 mils (0.4 mm/0.015 in.). Do not route more than 

three sets of motor leads in a single conduit to minimize “cross talk”. If 

more than three drive/motor connections per conduit are required, 

shielded cable must be used.

UL installations in 50°C ambient must use 600V, 75°C or 90°C wire.

UL installations in 40°C ambient should use 600V, 75°C or 90°C wire.

Use copper wire only. Wire gauge requirements and recommendations 

are based on 75 degree C. Do not reduce wire gauge when using higher 

temperature wire.

Unshielded

THHN, THWN or similar wire is acceptable for drive installation in dry 

environments provided adequate free air space and/or conduit fill rates 

limits are provided. Do not use THHN or similarly coated wire in wet 

areas. Any wire chosen must have a minimum insulation thickness of 15 

mils and should not have large variations in insulation concentricity.

Shielded/Armored Cable

Shielded cable contains all of the general benefits of multi-conductor 

cable with the added benefit of a copper braided shield that can contain 

much of the noise generated by a typical AC Drive. Strong consideration 

for shielded cable should be given in installations with sensitive 

equipment such as weigh scales, capacitive proximity switches and other 

devices that may be affected by electrical noise in the distribution 

system. Applications with large numbers of drives in a similar location, 

imposed EMC regulations or a high degree of communications / 

networking are also good candidates for shielded cable.

Shielded cable may also help reduce shaft voltage and induced bearing 

currents for some applications. In addition, the increased impedance of 

shielded cable may help extend the distance that the motor can be 

located from the drive without the addition of motor protective devices 

such as terminator networks. Refer to Reflected Wave in “Wiring and 

Grounding Guidelines for PWM AC Drives,” publication 

DRIVES-IN001A-EN-P.

Consideration should be given to all of the general specifications 

dictated by the environment of the installation, including temperature, 

flexibility, moisture characteristics and chemical resistance. In addition, 

a braided shield should be included and be specified by the cable 

manufacturer as having coverage of at least 75%. An additional foil 

shield can greatly improve noise containment.

A good example of recommended cable is Belden® 295xx (xx 

determines gauge). This cable has four (4) XLPE insulated conductors 

with a 100% coverage foil and an 85% coverage copper braided shield 

(with drain wire) surrounded by a PVC jacket.

Other types of shielded cable are available, but the selection of these 

types may limit the allowable cable length. Particularly, some of the 

newer cables twist 4 conductors of THHN wire and wrap them tightly 

with a foil shield. This construction can greatly increase the cable 

charging current required and reduce the overall drive performance. 

Unless specified in the individual distance tables as tested with the drive, 

these cables are not recommended and their performance against the lead 

length limits supplied is not known.

A-BPowerFlex 4 and 40 AC Drives

Product Overview

Providing users with powerful motor speed control in a compact, space saving design, the Allen-Bradley® PowerFlex® 4 and 

40 AC drives are the smallest and most cost-effective members of the PowerFlex® family of drives. Available in power ratings 

from 0.2 to 11 kW (0.25 to 15 HP) and in voltage classes of 120, 240, 480 and 600 volts, PowerFlex 4 and 40 are designed 

to meet global OEM and end-user demands for flexibility, space savings, ease of use and are cost-effective alternatives for 

speed control of applications such as machine tools, fans, pumps and conveyors and material handling systems

Packaging and Mounting

• Installation can be a virtual snap using the DIN rail mounting feature on 

A and B frame drives. Panel mounting is also available, providing added 

flexibility.

• Flange mount drives are available to reduce overall enclosure size.

• Zero Stacking™ is allowable for ambient temperatures up to 40 °C, saving 

valuable panel space. 50 °C ambient temperatures are permitted with 

minimal spacing between drives.

• Integral filtering is available on all 230V single phase ratings, providing a 

cost-effective means of meeting EN55011, Class A and B EMC 

requirements. External filters provide compliance to Class A and B 

requirements for all PowerFlex 4 and 40 ratings.

• An optional IP30, NEMA/UL Type 1 conduit box is easily adapted to 

the standard IP20 (NEMA Type Open) product, providing increased 

environmental ratings.

• IP66, NEMA/UL Type 4X/12 (Indoor) for mounting directly in the 

product environment. Listed by UL to resist dust, dirt, etc. and survive 

high pressure water spray. Also certified by NSF to ensure conformity 

with international food equipment standards.

Start Up, Programming and Operation

• An integral keypad provides out of the box operation using the local 

potentiometer and control keys.

• The 10 most common application parameters are contained in the Basic 

Program Group, making programming fast and easy.

• The programming keys have the same function as all other PowerFlex 

drives, so if you can program one PowerFlex drive, you can program them 

all.

• 4 digit display with 10 additional LED indicators provides an intuitive 

display of drive status and information.

• Integral RS-485 communications can be used for programming from a 

PC. It can also be used in a multi-drop network configuration. A serial 

converter module provides connectivity to any controller with a DF1 

port.

• A NEMA/UL Type 4X remote and NEMA/UL Type 1 hand-held 

LCD keypad provide additional programming and control flexibility, 

both featuring the popular CopyCat function

Optimized Performance

• Removable MOV to ground provides trouble-free operation when used on ungrounded 

distribution systems.

• A relay pre-charge limits inrush current.

• Integral brake transistor, available on all ratings (except no brake version), provides 

dynamic braking capability with simple low cost brake resistors.

• DIP switch settable 24V DC sink or source control for control wiring flexibility.

• 150% overload for 60 seconds or 200% overload for 3 seconds provides robust overload 

protection.

• Adjustable PWM frequency up to 16 kHz ensures quiet operation.

Sensorless Vector Performance

PowerFlex 4

• Drive automatically provides auto boost (IR 

compensation) and slip compensation.

• Provides excellent speed regulation and high levels of 

torque across the entire speed range of the drive, and 

improved speed regulation even as loading increases.

Sensorless Vector Control

PowerFlex 40

• Sensorless Vector Control provides exceptional speed 

regulation and very high levels of torque across the 

entire speed range of the drive.

• The Autotune feature allows the PowerFlex 40 to adapt 

to individual motor characteristics.

Performance

• This graph depicts the ability of a PowerFlex 40 drive to 

accelerate into at least 150% load. A PowerFlex 4 will 

perform similarly, but with a slightly higher acceleration 

time.

• At 100% motor load, the drive will run the motor at 

synchronous speed.

• Excellent current regulation.

• Linear acceleration.

• Best in class digital input response time and 

repeatability

Performance

• Sensorless Vector Control develops high torque over a wide speed range 

and adapts to individual motor characteristics.

• Variable PWM allows the drive to output more current at low 

frequencies.

• Integral PID functionality enhances application flexibility.

• Timer, Counter, Basic Logic and StepLogic™ functions can reduce 

hardware design costs and simplify control schemes.

– Timer function: Relay or opto outputs controlled by drive 

performing timer function. Timer is initiated by activating a digital 

input programmed as “Timer Start.”

– Counter function: Relay or opto outputs controlled by drive 

performing counter function. Counter function is activated by a 

digital input programmed as “Counter Input.”

– Basic Logic: Relay or opto outputs controlled by status of digital 

inputs programmed as “Logic Inputs.” Performs basic Boolean logic.

– StepLogic: Logic-based steps using preset speed settings. Each step 

can be programmed for a specific speed, direction and accel/decel 

profile. Drive outputs can be used to indicate which step is being performed.

I/O

• Two (2) Analog Inputs (one unipolar and one bipolar) are 

independently isolated from the rest of the drive I/O. These inputs 

can be toggled between via a digital input.

• Three (3) fixed and four (4) fully programmable Digital Inputs

provide application versatility.

• One (1) Analog Output is DIP switch selectable for either 

0…10V or 0…20mA. This scalable, 10-bit output is suitable for 

metering or as a speed reference for another drive.

• Two (2) Opto Outputs and one (1) form C relay output can be 

used to indicate various drive, motor or logic conditions.

Communications

• Integral communication cards such as DeviceNet™, EtherNet/IP™, 

PROFIBUS™ DP, LonWorks® and, ControlNet™ can improve machine 

performance.

• The DSI Wireless Interface Module (WIM) provides a wireless 

communication interface between a Pocket PC, laptop computer or 

desktop computer equipped with Bluetooth® wireless technology, and any 

Allen-Bradley® product supporting the DSI™ protocol.

• Field installed option allows for future addition of stand-alone drives to a 

network.

• Online EDS file creation with RS NetWorx™ providing ease of set-up on a 

network.

Versatile Programming and Network Solutions

• PowerFlex 4 and PowerFlex 40 are compatible with 

any device that acts as a RTU Master and supports 

standard 03 and 06 RTU commands.

• A network can be configured using PowerFlex 40 

drives with optional communication cards for high 

performance and flexible configuration capabilities.

– BACnet

– ControlNet

– DeviceNet

– EtherNet/IP

– LonWorks

– PROFIBUS DP

• A multi-drive solution can be reached using a single 

PowerFlex 40 DeviceNet option, with the ability for 

up to five drives to reside on one node.

• Integral RS485 communications enable the drives to 

be used in a multi-drop network configuration. A 

serial converter module (SCM) provides connectivity 

to any controller with a DF1 port. The SCM can be 

eliminated if the controller acts as a RTU Master.

PC Programming Software

Through the use of a Serial Converter Module and 

DriveExplorer™ or DriveTools™ SP software, 

programming can be greatly simplified.

DriveExplorer Software

• View and modify drive and adapter parameters in 

a method similar to the file management capability 

of Microsoft Windows Explorer.

• Operate the drive via an on-screen Control Bar, 

which is a tool that allows you to start, stop, and 

change the speed reference of the drive.

• Save, restore and print parameter information.

• Compare current parameters with factory defaults 

or previously saved parameter values.

• Edit, upload and download parameters.

DriveTools SP Software

• Online and offline programming capability

• In-grid and dialog-based parameter editing

• Immediate visual indication of drive and communication status when viewing online drive

• Integrated HTML Help architecture

Installation Considerations

PowerFlex 4 and 40 drives have the following built in protective features to help simplify installation.

• Ground fault protection while starting and running ensures reliable operation

• Electronic motor overload protection increases motor life

• Removable MOV to ground ensures compatibility with ungrounded systems

• 6kV transient protection provides increased robustness for 380…480V system voltages

There are many other factors that must be considered for optimal performance in any given application. The block diagram 

below highlights the primary installation considerations. Consult the PowerFlex 4 or PowerFlex 40 User Manual, 

Publications 22A-UM001 or 22B-UM001 available online at www.rockwellautomation.com/literature, for detailed 

recommendations on input power conditioning, CE conformance (EMC filtering), dynamic braking, reflected wave 

protection, motor cable types and motor cable distances.

Control Wiring

PowerFlex 4

• The control logic is 24V DC and can be set for either 

Sink or Source control via a DIP switch setting.

• Control terminal screws are sized for a conventional 

blade screw driver.

• I/O Terminals 1, 2 and 3 are dedicated for Stop, Start 

and Reverse operation respectively. These I/O 

Terminals can be programmed for 2- or 3-Wire 

operation to meet application requirements.

• I/O Terminals 4 and 5 are programmable and provide 

added flexibility. Programmable functions include:

– Local Control 

– Preset Frequencies

– Jog 

– RS485 Control

– Second Accel/Decel 

– Auxiliary Fault

– Clear Fault

• Speed can be controlled via a 0…10V input or 4…20 

mA input. Both are electrically isolated from the drive.

• One form C relay can be programmed to provide the 

status of a wide variety of drive conditions.

• The drive is shipped with a jumper installed between 

I/O Terminals 01 and 11 to allow out of box operation 

from the keypad.

PowerFlex 40

• The control logic is 24V DC and can be set for either 

Sink or Source control via a DIP switch setting.

• Control terminal screws are sized for a conventional 

blade screw driver.

• I/O Terminals 1, 2 and 3 are dedicated for Stop, Start and 

Reverse operation respectively. These I/O Terminals can 

be programmed for 2- or 3-Wire operation to meet 

application requirements.

• I/O Terminals 5, 6, 7 and 8 are programmable and 

provide added flexibility. Programmable functions 

include Local Control, Jog, Second Accel/Decel, Clear 

Fault, Preset Frequencies, RS485 Control and Auxiliary 

Fault.

• Speed can be controlled via a 0…10V input and/or 4…20 

mA input. Both inputs are independently isolated from 

the rest of the drive and can be used for applications such 

as PID. Voltage input can be programmed for bipolar 

operation.

• The drive is shipped with a jumper installed between I/O 

Terminals 01 and 11 to allow out of box operation from 

the keypad.

Enclosure Options and Approximate Dimensions

A-BPowerFlex 7000 Medium Voltage AC Drive Air-Cooled (’B’ Frame)—ForGe Control

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and 

operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize

themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to 

be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be 

impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use 

or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and 

requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for 

actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software 

described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is 

prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

About This Publication This document provides procedural information for managing daily or 

recurring tasks involving the PowerFlex® 7000 medium voltage ‘B’ frame 

drives (heatsink and heatpipe models).

Download Firmware, AOP, 

EDS, and Other Files 

Download firmware, associated files (such as AOP, EDS, and DTM), and access 

product release notes from the Product Compatibility and Download Center at 

rok.auto/pcdc.

Summary of Changes This publication contains the following new or updated information. This list 

includes substantive updates only and is not intended to reflect all changes.

Who Should Use This 

Manual

This manual is intended for use by personnel familiar with medium voltage 

and solid-state variable speed drive equipment. The manual contains material 

that enables regular operation and maintenance of the drive system.

What Is Not in This Manual This manual provides information specific to maintaining the PowerFlex 7000 

‘B’ frame drive. This document does not include topics such as:

• Physically transporting or siting the drive cabinetry

• Installing or commissioning procedures

• Spare parts lists compiled for your order. 

Rockwell Automation provides the site- and installation-specific electrical and 

design information for each drive during the order process cycle. If they are 

not available on site with the drive, contact Rockwell Automation.

If you have multiple drive types or power ranges, ensure you have the correct 

documentation for each specific PowerFlex 7000 product:

• ‘A’ frame for lower-power air-cooled, configurations (up to 

approximately 1250 hp/933 kW)

• ‘B’ frame for higher-power, air-cooled configurations (standard or 

heatpipe models)

• ‘C’ frame for all liquid-cooled configurations

PowerFlex 7000 Drive Overview

The PowerFlex™ 7000 drive is a general-purpose, standalone, medium voltage 

drive that controls speed, torque, direction, starting, and stopping of standard 

asynchronous or synchronous AC motors. This drive works on numerous 

standard and specialty applications such as fans, pumps, compressors, mixers, 

conveyors, kilns, fan-pumps, and test stands in industries such as 

petrochemical, cement, mining and metals, forest products, power generation, 

and water/waste water. 

The PowerFlex 7000 drive meets most common standards from these 

organizations: 

• National Electrical Code (NEC)

• International Electrotechnical Commission (IEC)

• National Electrical Manufacturers Association (NEMA)

• Underwriters Laboratories (UL)

• Canadian Standards Association (CSA). 

The drive is available with the world’s most common supply voltages at 

medium voltage, from 2400…6600V. The design focuses on high reliability, 

ease of use, and lower total cost of ownership.

Topology The PowerFlex 7000 drive uses a pulse width modulated (PWM) – current 

source inverter (CSI) topology. This topology applies to a wide voltage and 

power range. The power semiconductor switches used are easy-to-series for 

any medium voltage level. Semiconductor fuses are not required for the power 

structure due to the current limiting DC link inductor.

With 6500V PIV rated power semiconductor devices, the number of inverter 

components is minimal. For example, only six inverter switching devices are 

required at 2400V, 12 at 3300…4160V, and 18 at 6600V. 

The PowerFlex 7000 drive also provides inherent regenerative braking for 

applications where the load is overhauling the motor, or where high inertia 

loads are quickly slowed down. The drive uses the following:

• Symmetrical gate commutated thyristors (SGCTs) for machine converter 

switches

• SGCTs for active front-end (AFE) rectifier configurations for the line 

converter switches

• Silicon-controlled rectifiers (SCRs) for 18-pulse rectifier configurations

The PowerFlex 7000 drive provides a selectable option for enhanced torque 

control capabilities and increased dynamic control performance. This highperformance torque control (HPTC) feature delivers 100% torque at zero speed 

and provides torque control through zero speed with smooth direction 

transition.

Rectifier Designs Configurations

The PowerFlex 7000 drive offers three rectifier configurations for ‘B’ frame 

drives:

• Direct-to-Drive™ (AFE rectifier with integral line reactor and CMC)

• AFE rectifier with separate isolation transformer

• 18-pulse rectifier with separate isolation transformer

Direct-to-Drive

Direct-to-Drive technology does not require an isolation transformer or 

multiple rectifier bridges as in voltage source inverter (VSI) topologies offered 

by others. The approach is completely different. Instead of multiple 

uncontrolled rectifiers, a single AFE rectifier bridge is supplied. The rectifier 

semiconductors that are used are SGCTs. Unlike the diodes that are used in 

VSI rectifier bridges, SGCTs are turned on and off by a gating signal. A PWM 

gating algorithm controls the firing of the rectifier devices, similar to the 

control philosophy of the inverter. The gating algorithm uses a specific 

42-pulse switching pattern called selective harmonic elimination (SHE) to 

mitigate the 5th, 7th, and 11th harmonic orders

A small integral line reactor and capacitor addresses the high harmonic orders 

(13th and above) and provides virtually sinusoidal input voltage and current 

waveforms back to the distribution system. This configuration delivers 

excellent line-side harmonic and power factor performance to meet IEEE 519-

1992 requirements and other global harmonic standards in virtually all cases. 

This setup also provides a simple, robust power structure that maximizes 

uptime by minimizing the number of discrete components and the number of 

interconnections required.

A CMC mitigates the common mode voltage seen at the motor terminals, so 

standard (non-inverter duty rated) motors and motor cables can be used. This 

technology is ideal for retrofitting existing motor applications

AFE Rectifier with Separate Isolation Transformer

For applications when the line voltage is higher than the motor voltage, a 

transformer is required for voltage matching. In this case, providing an AFE 

rectifier with a separate isolation transformer is ideal (indoor and outdoor 

transformer versions are offered). The isolation transformer replaces the 

requirement for an integral line reactor and replaces the requirement for a 

CMC that is supplied in the Direct-to-Drive rectifier configuration. However, 

the AFE rectifier, its operation, and advantages are the same as the Direct-toDrive configuration.

Figure 3 – 3300/4160 AFE Rectifier with Separate Isolation Transformer

For high power constant torque applications and/or when the line voltage is 

higher than the motor voltage, a transformer is required for voltage matching 

(indoor and outdoor transformer options are available). The 18-pulse rectifier 

uses SCRs instead of the SGCTs used for an AFE rectifier. When used for high 

power constant torque applications, the 18-pulse rectifier has lower losses than 

the AFE rectifier, making 18-pulse ideal for the highest power requirements. 

The 18-pulse isolation transformer provides the required input impedance and 

addresses common mode voltage just like the separate isolation transformer 

used with the AFE rectifier. However, instead of a PWM rectifier switching 

pattern and a single rectifier bridge, the 18-pulse configuration mitigates line 

side harmonics through harmonic current cancellation in the isolation 

transformer phase shifted secondary windings. The inverter is the same 

configuration for all available rectifier options.

Figure 4 – 3300/4160V 18-pulse Rectifier with Separate Isolation Transformer

Cooling Technology These VFDs are supplied with heatsinks for most configurations and heatpipes 

for the highest-power AFE configurations. While both configurations draw 

heat away from the semiconductors, heatpipes are bigger, more efficient, and 

require larger fans and airflow. 

Information and graphics in this manual show both configurations.

Motor Compatibility The PowerFlex 7000 drive achieves near-sinusoidal current and voltage 

waveforms to the motor, resulting in no significant additional heating or 

insulation stress. Temperature rise in the motor connected to the VFD is 

typically 3 °C (5.5 °F) higher compared to across-the-line operation. Voltage 

waveform has dv/dt of less than 50 V/μs. The peak voltage across the motor 

insulation is the rated motor RMS voltage divided by 0.707. 

Reflected wave and dv/dt issues often associated with VSI drives are a nonissue with the drive. Figure 5 shows typical motor waveforms. The drive uses a 

SHE pattern in the inverter to eliminate major order harmonics, plus a small 

output capacitor (integral to the drive) to eliminate harmonics at higher 

speeds.

Standard motors are compatible without de-rating, even on retrofit 

applications. 

Motor cable distance is virtually unlimited. Rockwell Automation has tested 

this technology for controlling motors up to 15 km (9.3 mi) away from the drive.

Figure 5 – Motor Waveforms at Full Load, Full Speed

Power Component Definition and Maintenance

This section provides an overview of the control components and cabling of 

your PowerFlex® 7000 ‘B’ frame drive. This section also details a number of 

regular or recurring maintenance tasks that will keep your drive in peak 

operating condition.

Figure 20 through Figure 26 identify the control components and cabling of 

your drives. Where appropriate, separate diagrams and instructions are 

available for both the heatsink and the heatpipe ‘B’ frame models. 

For information regarding power wiring and cabling connections (as might be 

necessary for routine maintenance), see the PowerFlex 7000 ‘B’ frame 

installation manual, publication 7000-IN007.

Control Power Off Tests Perform the following checks before applying control power to the drive. 

Rockwell Automation recommends that you complete these checks in the 

sequence they are presented here.

Interlocking

When the input contactor option is purchased, a key interlock is provided to 

prevent access to the medium voltage compartments of the drive unless the 

input isolation switch is locked in the open position.

Where the input switching device is provided by others, Rockwell Automation 

will provide a key interlock on the medium voltage compartment of the drive, 

and a matching interlock for installation by others on the upstream device. The 

interlock shall be installed in a manner that ensures the power to the drive is 

off and the drive is electrically isolated whenever the key is freed.

Although key interlocks shipped with all medium voltage equipment are 

aligned in the factory, they often move out of position during shipping or are 

often misaligned when the cabinet is set down on an uneven floor. 

ATTENTION: Servicing energized industrial control equipment can be 

hazardous. Severe injury or death can result from electrical shock, 

burn, or unintended actuation of control equipment. Hazardous 

voltages can exist in the cabinet even with the circuit breaker in the 

off position. We recommend that you disconnect or lock out control 

equipment from power sources, and confirm discharge of stored 

energy in capacitors. If you must work in the vicinity of energized 

equipment, the safety-related work practices of NFPA 70E, Standard 

for Electrical Safety in the Workplace, must be followed

benderIRDH575 SeriesDigital Ground Fault Monitor / Ground Detector Controller for Ground Fault Location System Ungrounded (Floating) AC/DC Systems

Features

• Universal application in 3(N)AC, AC/DC 

and DC ungrounded systems 20…575 

V/340…760 V

• Response range 1 kΩ…10 MΩ

• Info key for the indication of various 

parameters and the system leakage 

capacitance

• Comprehensive self-monitoring function 

including system fault alarm relay

• Internal/external test and reset button

• Two separate alarm relays, operating 

normally energized or normally de-energized

• Backlit LCD display

• RS-485 interface

• Data memory, system disconnection and 

0/4…20mA current output

• Extendable to ground fault

location system for 1080 circuits

• Adjustable test current for ground fault 

location

Description

The IRDH575 monitors for ground faults in ungrounded AC (20 – 760 V, single- and threephase) and DC (20 – 575 V) by measuring the system’s insulation resistance. Systems with 

extensive power conversion devices, such as rectifiers and variable frequency drives, are 

supported by the IRDH575. The IRDH575 is able to detect ground faults in ungrounded 

systems before leakage current may even be present.

When combined with EDS4… ground fault location devices and the appropriate current 

transformers, the IRDH575 becomes a controller for a ground fault location system.

Function: Ground fault detection

When the insulation resistance from system to ground falls below the set response value, 

the alarm relays switch and the alarm LEDs activate. Two separately adjustable alarm 

contacts can be set to a prewarning and main warning alarm. The measured value is indicated on the LCD display or on an externally connected meter. If the device is set to nonlatching mode, the alarms will clear when the ground fault clears. If the device is set to 

latching mode, the alarms will not reset until the device is reset manually or the supply 

voltage is lost. An external and internal test/reset can be activated remotely or on the device. A comprehensive INFO menu key displays additional information such as the current leakage capacitance and device settings.

The IRDH575 continuously monitors the equipment ground connection and line connections to ensure proper operation. The device’s easy-to-use onboard menu manages all 

settings via the detailed LCD screen.

Function: Ground fault location

When a ground fault is detected, the EDS ground fault location system is activated (this 

feature can be set to require a manual start as well). Each channel of the EDS location device is connected to a particular branch circuit. The IRDH575 begins transmitting a pulsed 

signal. This signal will travel through the channel of the EDS with the ground fault back 

to the IRDH575. If the pulse travels back to the IRDH575, the channel with the ground 

fault will display on both the IRDH575 and the EDS device.

In addition, an optional EDS30… portable ground fault location system can be used to follow the pulse travelling to the source of the ground fault.

Additional functions 

99 timestamped alarm messages may be stored in the non-volatile memory of the 

IRDH575. The device also includes standby contacts when several A-ISOMETER® detectors 

are operating in coupled ungrounded systems.

Two-way data communication is carried out between devices via an RS-485 interface. 

This interface can be connected to a BENDER protocol converter to exchange data across 

other protocols, such as Ethernet, MODBUS, or PROFIBUS.

A 0/4 – 20 mA output can be connected to an external meter or higher-level control system, such as a PLC. 

System design

Each isolated system requires one IRDH575 for ground fault detection and location control. Up to 90 EDS46… devices can be interconnected to the IRDH575. Each EDS device 

can monitor up to 12 separate channels. An optional EDS30…. portable ground fault location system can be used in conjunction with the IRDH575/EDS46… system.

1 – INFO key: Displays pertinent system information

ESC key: Goes back a step inside device’s menu

2 – TEST button: Activates self-test

Arrow up key: Scrolls down inside device’s menu

3 – RESET button: Resets device

Arrow down key: Scrolls down inside device’s menu

4 – MENU key: Activates device’s internal menu

Enter key: Confirm change inside device’s menu

5 – Alarm LED 1 lights: Insulation fault, warning level reached

6 – Alarm LED 2 lights: Insulation fault, alarm level reached

7 – EDS LED lights: Indicates ground fault location is active

8 – EDS alarm LED lights: Indicates EDS ground fault location device is in alarm

9 – LED lights: Indicates system fault alarm

10 – Real-time measurement of insulation resistance in kΩ

11 – Additional information – “s” displayed when device has begin a 

new measurement

12 – Active when EDS4… is connected and in alarm; indicates 

address of EDS4… in alarm

13 – Active when EDS4… is connected and in alarm; indicates 

channel of EDS4… in alarm

14 – Active when EDS4… is connected and in alarm; indicates 

strength of test signal detected by the channel in alarm (mea

sured in mA or µA)

15 – Active when EDS4… is connected. Displays mode of operation 

for ground fault location system. AUTO indicates location system is activated automatically when IRDH575 goes into alarm. 

System may also be set manually on or off.

16 – Polarity of the test current pulse. Point = valid BMS traffic,

H = A new entry has been made in the history.

17 – Text indicating state of device

18 – Analog output: 0…20 mA or 4…20 mA (selectable)

19 – External test button (N/D contact)

20 – External reset button (N/E contact or wire jumper). When the 

terminals are open, the device will reset automatically.

21 – STANDBY contacts. When the contacts are closed, the device 

is forced into standby mode and will not send out a measurement signal.

22 – RS-485 termination (120 Ω) with micro switch S1 and connection 

BMS bus; S1 = ON = BMS bus terminated, S2 = unassigned

23 – Alarm relay: Alarm 1 (A-ISOMETER®)

24 – Alarm relay: Alarm 2 (A-ISOMETER®)

25 – Alarm relay: System fault and EDS alarm (Adr.:1)

1 – A-ISOMETER® IRDH575

2 – RS-485/BMS protocol

3 – EDS460/EDS461

4 – EDS3090/EDS3091

Example: IRDH575 with EDS460 (main circuits)

EDS460 system with IRDH575, EDS460 and measuring current 

transformers W… in a three-phase AC system

1 – 3AC/3NAC/AC 20…575 V

2 – US

 see ordering information, 6 A fuse recommended.

3 – Current transformers, W series

4 – Loads

5 – A-ISOMETER® IRDH575

6 – Ground fault location device EDS460

Example: IRDH575 with EDS461 (control circuits)

1 – DC 20 V…308 V

2 – US

 see ordering information, 6 A fuse recommended.

3 – Current transformers, W…/8000 series

4 – Load PLC

5 – A-ISOMETER® IRDH575

6 – Ground fault location device EDS461

Design of an EDS461 system

The above example shows an EDS461 device being fed by a PLC 

in a DC system. Using an EDS461 device is recommended for PLC 

inputs due to the sensitivity required.

GEInstallation and Maintenance Manual Bently Nevada™ Asset Condition Monitoring

Additional Information 

Notice:

This manual does not contain all the information required to operate and maintain 

the product. Refer to the following manuals for other required information. 

3500 Monitoring System Rack Configuration and Utilities Guide 

(129777-01) 

• guidelines for using the 3500 Rack Configuration software for setting the operating 

parameters of the module 

• guidelines for using the 3500 test utilities to verify that the input and output 

terminals on the module are operating properly 

3500 Monitoring System Computer Hardware and Software Manual 

(128158-01) 

• instructions for connecting the rack to 3500 host computer 

• procedures for verifying communication 

• procedures for installing software 

• guidelines for using Data Acquisition / DDE Server and Operator Display Software

• procedures and diagrams for setting up network and remote communications 

3500 Field Wiring Diagram Package (130432-01) 

• diagrams that show how to hook up a particular transducer 

• lists of recommended wiring 

Operation and Maintenance Manuals for all the modules installed in the 

rack 

Product Disposal Statement

Customers and third parties, who are not member states of the European Union, who are 

in control of the product at the end of its life or at the end of its use, are solely 

responsible for the proper disposal of the product. No person, firm, corporation, 

association or agency that is in control of product shall dispose of it in a manner that is 

in violation of any applicable federal, state, local or international law. Bently Nevada LLC 

is not responsible for the disposal of the product at the end of its life or at the end of its 

use. 

1. Receiving and Handling Instructions 

This will be a short overview of the entire section. 

1.1 Receiving Inspection 

Visually inspect the system for obvious shipping damage. If you detect shipping 

damage, file a claim with the carrier and submit a copy to Bently Nevada, LLC. 

1.2 Handling and Storage Considerations 

Proper handling and storing of printed circuit boards is extremely critical. Circuit 

boards contain devices that are susceptible to damage when exposed to 

electrostatic charges. Damage caused by obvious mishandling of the board will 

void the warranty. To avoid damage, observe the following precautions in the 

order given. 

Application Advisory 

Machinery protection will be lost when 

you remove all power from the rack. 

• Do not discharge static electricity onto the circuit board. Avoid tools or 

procedures that would subject the circuit board to static damage. 

Some possible causes of static damage include ungrounded soldering 

irons, nonconductive plastics, and similar materials. 

• Use a suitable grounding strap (such as 3M Velostat® No. 2060) to 

ground yourself before handling or performing maintenance on a 

printed circuit board. 

• Transport and store circuit boards in electrically conductive bags or 

foil. 

• Use extra caution during dry weather. Relative humidity less than 30% 

tends to multiply the accumulation of static charges on any surface. 

When performed properly, you may remove modules from or install modules into 

the rack while power is applied to the rack. Refer to << Section reference to 

“Module Installation in section 4 >> for the proper procedure

2. General Information 

Monitoring and computerized vibration information systems provide the 

information you need to assess the mechanical condition of rotating and 

reciprocating machinery. These systems continuously measure and monitor 

various supervisory parameters and provide crucial information for early 

identification of machinery problems such as imbalance, misalignment, shaft 

crack, and bearing failures. As such, these systems are an efficient and effective

means of satisfying plant management, engineering, and maintenance concerns 

for: 

• Increasing plant safety by minimizing the occurrence of hazardous 

conditions or catastrophic failures. 

• Improving product quality by minimizing process variances caused by 

improperly operating equipment. 

• Maximizing plant availability by servicing only those machines that 

require it and providing more efficient turnarounds. 

• Reducing plant operating costs by minimizing unplanned shutdowns 

and by making more efficient use of maintenance resources. 

For protection of critical machinery, we highly recommend that you permanently 

install continuous monitoring systems. The term “protection” means that the 

system can shut down machinery on alarm, without human interaction. These 

systems include applicable transducers, each with its own dedicated monitoring 

circuitry and alarm setpoints. The 3500 Monitoring System is the newest addition 

to the family of continuous monitoring systems offered by Bently Nevada, LLC. 

2.1 3500 Monitoring System 

The 3500 is a full-feature monitoring system whose design incorporates the latest 

in proven processor technology. In addition to meeting the above stated criteria, 

the 3500 adds benefit in the following areas: 

• Enhanced operator information 

• Improved integration to plant control computer 

• Reduced installation and maintenance cost 

• Improved reliability 

• Intrinsic Safety (IS) option 

The following sections discuss these benefits in more detail.

2.1.1 Enhanced Operation Information 

The 3500 design includes features to both enhance the operator’s information 

and present this information so that the operator may easily interpret it. These 

features include: 

• Improved data set 

– Overall amplitude 

– Probe gap voltage 

– 1X amplitude and phase 

– 2X amplitude and phase 

– Not 1X amplitude 

• Windows®-based Operator Display Software 

• Data displayed at multiple locations 

2.1.2 Improved Integration to Plant Control Computer

The 3500 improves integration to the plant control computer with: 

• Communication Gateways supporting multiple protocols 

• Time synchronized vibration and process information 

2.1.3 Reduced Installation and Maintenance Costs 

The 3500 system provides the following cost-saving features: 

• Reduced cabling costs 

• Downward product compatibility 

• Improved space utilization 

• Easier configuration 

• Reduced spare parts 

• Improved serviceability 

2.1.4 Improved Reliability 

The 3500 offers several features to improve system reliability. 

• Redundant power supplies available 

• Triple Modular Redundant (TMR) monitors and relay cards available

• Redundant Gateway and Display Modules permitted 

2.1.5 Intrinsic Safety Option 

If you wish to monitor equipment that is located in hazardous atmospheres, the 

3500 Monitoring System has a range of I/O modules with internal zener barriers. 

These modules provide an Intrinsically Safe interface between the 3500 rack and 

the transducers located in the hazardous area. 

2.1.6 Multiple Output Interfaces 

You can conveniently adjust monitor options (such as full scale ranges, 

transducer inputs, recorder outputs, alarm time delays, alarm voting logic, and 

relay configuration) in the field via software. Modular system design employs 

plug-in components which allow easy servicing and expansion. 

The following three independent interfaces are available with the 3500 system: 

• Data Manager Interface (Transient Data Interface External or Dynamic 

Data Interface External) 

• Configuration/Data port 

• Communications Gateway (support for Programmable Logic 

Controllers, Process Control Computers, Distributed Control Systems,

and PC-based Control Systems) 

These interfaces allow you to easily view monitored parameters and their 

statuses in the following ways: 

• System 1® Software 

• Bently Nevada™ 3500 Operator Display Software 

• Remote display panel 

• DCS or PLC display 

Convenient front panel coaxial connectors provide dynamic transducer signals 

and allow you to connect diagnostic or predictive maintenance instruments. 

2.2 Common Features 

The common features of the modules in the 3500 rack include hot insertion or

removal of modules and external and internal termination of the wiring. 

2.2.1 Hot Insertion or Removal of Modules 

When performed properly, you can remove and replace any module while the 

system is under power without affecting the operation of any unrelated modules. 

If the rack has 2 power supplies, removing or inserting a power supply will not 

disrupt the operation of the 3500 rack. See <<Section reverence: “Module 

Installation in section 4 >> for the proper procedure. 

2.2.2 External and Internal Termination 

External termination uses multi-conductor cables to connect the I/O modules to 

the terminal blocks. These blocks simplify connecting many wires to the rack in 

tight areas. External termination is not available on I/O modules with internal 

zener barriers. 

Internal termination lets you connect transducers directly to the I/O modules. 

3500 System Components 

The 3500 Monitoring System consists of modules that fit into a rack. Figure 2-3 

shows a full-size 3500 system rack and system components. Note that the fullsize rack has 14 monitor slot positions. The Mini-rack (not shown) is similar, but 

has 7 monitor slot positions to the right of the power supplies and Rack Interface 

Module. 

1. 1 or 2 power supplies

2. Rack Interface Module (standard, Transient Data Interface, (TDI), Triple Modular Redundant (TMR) and TMR TDI) 

3. Monitoring slot positions: 

– Monitor module

– Keyphasor® module (2 maximum) 

– Relay module 

– Communication Gateway module

– Display module. For the System Face Mount you must install the Display Interface Module in Slot 15.

– 3500/04-01 Earthing Module. Intallations that use Inernal Barrier I/Os require 1 Earthing Module per rack. 

Figure 2-3: 3500 Rack (Full-Size) 

The following sections list the function of each module. Refer to the individual 

operation and maintenance manuals for available options, detailed description, 

operation and maintenance. 

2.3.1 Weatherproof Housing 

The weatherproof housing protects the 3500 rack from adverse environmental 

effects, such as excessive moisture, dirt and grime, and even unclean air. The 

weatherproof housing will not accommodate a Display Unit or VGA Display. 

2.3.2 Rack 

2 types of 3500 racks are available: the full-size 19-inch rack and the compact 12-

inch Mini-rack. Each rack requires you to install the Power Supplies and Rack 

Interface Module (RIM) in specific locations. The full-size version offers 14 

additional rack positions and the Mini-rack offers 7 additional rack positions. You 

may use these positions to install any combination of modules. Both racks 

support Standard (non-redundant) and Triple Modular Redundant (TMR) 

configurations

Application Advisory 

The TMR system will restrict the 

location of certain modules. 

2.3.3 Power Supply 

The Power Supply is a half-height module available in ac and dc versions. You 

can install 1 or 2 power supplies in the rack. Each power supply can power a fully 

loaded rack. When you install 2 power supplies in a rack, the supply in the lower 

slot acts as the primary supply and the supply in the upper slot acts as the 

backup supply. If the primary supply fails, the backup supply will provide power to 

the rack without interrupting rack operation. The 3500 design allows you to 

install any combination of power supply types. 

Overspeed Detection and TMR Monitors require dual power supplies. 

2.3.4 Rack Interface Module 

The Rack Interface Module (RIM) is a full-height module that communicates with

the host (computer), a Bently Nevada™ Communication Processor, and the other 

modules in the rack. The Rack Interface Module also maintains the System Event 

List and the Alarm Event List. You can daisy-chain this module to the Rack 

Interface Modules in other racks and to the Data Acquisition / DDE Server 

Software. The 3500 Monitoring System Computer Hardware and Software Manual

shows how to daisy chain the Rack Interface Modules together. Rack Interface 

Modules are available in Standard, Triple Modular Redundant and Transient Data 

Interface versions. 

2.3.5 Communication Gateway Module 

The Communication Gateway Module is a full-height module that allows external 

devices (such as a DCS or a PLC) to retrieve information from the rack and to set 

up portions of the rack configuration. You can install more than one 

Communication Gateway Module in the same rack. Communication Gateway 

Modules are available for a variety of network protocols. 

2.3.6 Monitor Module 

The Monitor Modules are full-height modules that collect data from a variety of 

transducers. You can install any combination of Monitor Modules in the 3500 

rack. 

2.3.7 Relay Module 

Relay Modules provide relays that you can configure to close or open based on 

channel statuses from other monitors in the 3500 rack. Relay modules are 

available in 4-channel, 16-channel, and 4-channel Triple Modular Redundant 

(TMR) versions. 

The TMR Relay Module is a half-height 4-channel module that operates in a TMR

system. 2 half-height TMR Relay Modules must operate in the same slot. If you 

remove the upper or lower Relay Module or the system declares one of the 

modules as Not OK, then the other Relay Module will control the Relay I/O Module. 

2.3.8 Keyphasor® Module 

The Keyphasor Module is a half-height module that provides power for the 

Keyphasor transducers, conditions the Keyphasor signals, and sends the signals 

to the other modules in the rack. The Keyphasor Module also calculates the rpm 

values sent to the host (computer) and external devices (DCS or PLC) and provides 

buffered Keyphasor outputs. Each Keyphasor Module supports 2 channels. You 

may place up to 2 Keyphasor Modules in a 3500 rack for a maximum of 4 

Keyphasor channels. If you use 2 Keyphasor Modules, you must place them in the 

same full-height slot and the modules will share a common I/O module. 

2.3.9 Display Module 

The 3500 system offers multiple display options. 

The Display Interface Module can display rack data on an LCD-based Interface 

unit or a 3rd-party Modbus® based display unit. 

The VGA Display Module will display rack data on certain touch screen VGA 

Displays. 

The Integrated PC display is a complete rack mount touch screen PC pre-loaded 

with rack configuration software and display utilities. 

2.3.10 Earthing Module 

The Earthing Module is a full-height module that provides a low resistance 

connection (must be less than 1 Ω) from the 3500 rack to the plant’s intrinsically 

safe earth ground. The module operates in conjunction with the 3500 internal 

zener barrier I/O modules. Your application will require 1 Earthing Module per rack 

when internal barrier I/O modules are used. 

2.4 Standard Rack Relay Options 

You can configure the standard (or non-TMR) 3500 rack to have individual relays, 

bussed relays, or a combination of individual and bussed relays. 

2.4.1 Individual Relays 

A rack with individual relays contains 1 or more relay cards for each monitor 

module. You can configure the monitor and relay modules within a 3500 rack in 

many ways. 

Example 1: The application uses 1 relay module 1 monitor module

Table 2-1: 1 Relay Module Used With 1 Monitor Module

Figure 2-4: Typical Standard 3500 Rack with Individual Relays (Full-Size Rack Shown) 

2.4.2 Bussed Relays 

In the Bussed Relays configuration a number of monitor channels share a single 

relay. Use the Rack Configuration Software to define the combination of alarms

that will trigger the relay. Figure 2-5 shows a typical Bussed Relay layout for a

standard 3500 rack. You can [place the monitors and relay modules in any slot as 

long as you link the monitors to the relay module in the Rack Configuration 

Software

3.7.4 Additional Notes 

• Larger scale factors are less susceptible to EMI than smaller scale factors. 

• Larger full-scales are less susceptible to EMI than smaller full-scale. 

• Monitors with narrow bandwidth filter configurations are less susceptible to 

EMI than monitors configured with wide bandwidth. 

• Larger Keyphasor® or hysteresis settings are less susceptible to EMI than 

smaller hysteresis settings. 

• Shorter Alarm delay times may increase monitor susceptibility to transient 

EMI. 

• Environments with higher levels of EMI than tested may cause unpredictable 

monitor readings and may cause system malfunction. 

3.8 Set Rack Jumpers and Switches 

Set the following jumpers and switches before operating the rack: 

• Rack address switch (on the front of the Rack Interface Module) 

• Transducer jumpers on each I/O Module, as required 

• Certain I/O Modules have switches to control their mode of operation. 

Examples include: 

– RIM and Comm Gateway I/O’s that support both RS232 and 

RS422 have a protocol selection switch 

– Overspeed and non-TMR Relay I/O’s have Normally 

Energized/De-energized Relay mode switches 

– Comm Gateway I/O’s that support RS485 have termination 

mode switches 

• Setup phone connection to rack / host (if you use an internal or 

external modem) 

– Phone cable to internal modem in rack 

Search for products

Back to Top
Product has been added to your cart