Call us 24/7+86 15396210640
Welcome to the official website of Lingkong Automation Technology Co., Ltd!
Call us 24/7+86 15396210640

benderWR70x175S(P)…WR200x500S(P) Measuring current transformers

Product description

The highly sensitive WR…S series measuring current transformers of rectangular type 

convert AC currents into evaluable measurement signals, in combination with RCM and 

RCMS series residual current monitors and evaluators. 

In addition, the measuring current transformers can be used in combination with insulation 

fault location systems (EDS) for IT systems. They are designed to measure the locating 

current generated by a PGH locating current injector or an ISOMETER® IRDH. In combination 

with EDS series insulation fault locators the test current is converted into evaluable signals.

The WR…SP series measuring current transformers feature an integrated screening. 

This screening is intended to avoid false tripping of connected RCM… or EDS… devices, 

when high load currents or inrush currents occur in the system being monitored. 

WR…SP series measuring current transformers are particularly suitable for use in busbar 

systems and are designed for load currents ≥ 500 A.

Connection to the respective device is via a two-wire cable.

Device features

• For RCMS460/490 residual current monitoring systems

• For RCM420 residual current monitors

• For EDS470, EDS460/490 and EDS440 insulation fault locators in AC and DC systems

• The WR…SP measuring current transformers are particularly suitable for use in busbar 

systems. This series is to be used for load currents ≥ 500 A.

Standards and approvals

WR70x175S(P)…WR200x500S(P) measuring 

current transformers comply with the device 

standards: 

• DIN EN 60044-1

• IEC 61869

Dimensions (mm) and weights (g)

Type WR70x175S(P)…WR150x350S(P)

Technical data

Insulation coordination acc. to IEC 61869-2

Highest system voltage for electrical equipment Um AC 720 V

Rated impulse withstand voltage Uisol 3 kV

Measuring circuit

Rated transformation ratio 600/1

Rated burden 180 Ω

Rated primary current ≤ 10 A (100 A)

Rated primary current ≥ 10 mA

Nominal power 50 mVA

Rated frequency 50…400 Hz

Internal resistance 5…8 Ω

Secondary overvoltage protection suppressor diode P6KE6V8CP

Accuracy class 5

Rated continuous thermal current 100 A

Rated short-time thermal current 14 kA/1 s

Rated dynamic current 35 kA/30 ms

Environment

Shock resistance IEC 60068-2-27 (device in operation) 15 g/11 ms

Bumping IEC 60068-2-29 (transport) 40 g/6 s

Vibration resistance IEC 60068-2-6 (device in operation) 1 g/10…150 Hz

Vibration resistance IEC 60068-2-6 (transport) 2 g/10…150 Hz

Ambient temperature (during operation) -10…+50 °C

Ambient temperature (during storage) -40…+70 °C

Climatic class acc. to DIN IEC 60721-3-3 3K22

Connection

Connection screw-type terminals

Connection 

rigid/flexible 0.2…4/0.2…2.5 mm²

flexible with ferrules with/without plastic sleeve 0.25…2.5 mm²

Conductor sizes (AWG) 24…12

Connection to the evaluator

single wire ≥ 0.75 mm² 0…1 m

single wire, twisted ≥ 0.75 mm² 0…10 m

shielded cable ≥ 0.6 mm² 0…40 m

Shielded cable (shield on one side connected to PE) recommended: J-Y(St)Y min. 2 x 0.6

Other

Operating mode continuous operation

Mounting any position

Degree of protection, internal components (DIN EN 60529) IP40

Degree of protection, terminals (DIN EN 60529) IP20

Screw mounting M5

Flammability class UL94 V-0

Documentation number D00144

Installation instructions

• Do not pass shielded cables through the measuring current 

transformer.

• As a general principle, the PE conductor and low-resistance 

conductor loops must not be passed through the measuring 

current transformer!

GEInstallation and Maintenance Manual

Copyright 1995. Bently Nevada, LLC. 

All rights reserved.

The information contained in this document is subject to change without notice. 

The following are trademarks of General Electric Company in the United States and other 

countries: 

Bently Nevada, System 1, Keyphasor 

The following are trademarks of the legal entities cited: 

Velostat is a trademark of 3M Company. 

Windows is a tradmemark of Microsoft Corporation. 

Modbus is a trademark of Modbus-IDA. 

Notice:

This manual does not contain all the information required to operate and maintain 

the product. Refer to the following manuals for other required information. 

3500 Monitoring System Rack Configuration and Utilities Guide 

(129777-01) 

• guidelines for using the 3500 Rack Configuration software for setting the operating 

parameters of the module 

• guidelines for using the 3500 test utilities to verify that the input and output 

terminals on the module are operating properly 

3500 Monitoring System Computer Hardware and Software Manual 

(128158-01) 

• instructions for connecting the rack to 3500 host computer 

• procedures for verifying communication 

• procedures for installing software 

• guidelines for using Data Acquisition / DDE Server and Operator Display Software

• procedures and diagrams for setting up network and remote communications 

3500 Field Wiring Diagram Package (130432-01) 

• diagrams that show how to hook up a particular transducer 

• lists of recommended wiring 

Operation and Maintenance Manuals for all the modules installed in the 

rack 

Product Disposal Statement

Customers and third parties, who are not member states of the European Union, who are 

in control of the product at the end of its life or at the end of its use, are solely 

responsible for the proper disposal of the product. No person, firm, corporation, 

association or agency that is in control of product shall dispose of it in a manner that is 

in violation of any applicable federal, state, local or international law. Bently Nevada LLC 

is not responsible for the disposal of the product at the end of its life or at the end of its 

use. 

1. Receiving and Handling Instructions 

This will be a short overview of the entire section. 

1.1 Receiving Inspection 

Visually inspect the system for obvious shipping damage. If you detect shipping 

damage, file a claim with the carrier and submit a copy to Bently Nevada, LLC. 

1.2 Handling and Storage Considerations 

Proper handling and storing of printed circuit boards is extremely critical. Circuit 

boards contain devices that are susceptible to damage when exposed to 

electrostatic charges. Damage caused by obvious mishandling of the board will 

void the warranty. To avoid damage, observe the following precautions in the 

order given. 

Application Advisory 

Machinery protection will be lost when 

you remove all power from the rack. 

• Do not discharge static electricity onto the circuit board. Avoid tools or 

procedures that would subject the circuit board to static damage. 

Some possible causes of static damage include ungrounded soldering 

irons, nonconductive plastics, and similar materials. 

• Use a suitable grounding strap (such as 3M Velostat® No. 2060) to 

ground yourself before handling or performing maintenance on a 

printed circuit board. 

• Transport and store circuit boards in electrically conductive bags or 

foil. 

• Use extra caution during dry weather. Relative humidity less than 30% 

tends to multiply the accumulation of static charges on any surface. 

When performed properly, you may remove modules from or install modules into 

the rack while power is applied to the rack. Refer to << Section reference to 

“Module Installation in section 4 >> for the proper procedure. 

2. General Information 

Monitoring and computerized vibration information systems provide the 

information you need to assess the mechanical condition of rotating and 

reciprocating machinery. These systems continuously measure and monitor 

various supervisory parameters and provide crucial information for early 

identification of machinery problems such as imbalance, misalignment, shaft 

crack, and bearing failures. As such, these systems are an efficient and effective

means of satisfying plant management, engineering, and maintenance concerns 

for: 

• Increasing plant safety by minimizing the occurrence of hazardous 

conditions or catastrophic failures. 

• Improving product quality by minimizing process variances caused by 

improperly operating equipment. 

• Maximizing plant availability by servicing only those machines that 

require it and providing more efficient turnarounds. 

• Reducing plant operating costs by minimizing unplanned shutdowns 

and by making more efficient use of maintenance resources. 

For protection of critical machinery, we highly recommend that you permanently 

install continuous monitoring systems. The term “protection” means that the 

system can shut down machinery on alarm, without human interaction. These 

systems include applicable transducers, each with its own dedicated monitoring 

circuitry and alarm setpoints. The 3500 Monitoring System is the newest addition 

to the family of continuous monitoring systems offered by Bently Nevada, LLC. 

2.1 3500 Monitoring System 

The 3500 is a full-feature monitoring system whose design incorporates the latest 

in proven processor technology. In addition to meeting the above stated criteria, 

the 3500 adds benefit in the following areas: 

• Enhanced operator information 

• Improved integration to plant control computer 

• Reduced installation and maintenance cost 

• Improved reliability 

• Intrinsic Safety (IS) option 

The following sections discuss these benefits in more detail.

2.1.1 Enhanced Operation Information 

The 3500 design includes features to both enhance the operator’s information 

and present this information so that the operator may easily interpret it. These 

features include: 

• Improved data set 

– Overall amplitude 

– Probe gap voltage 

– 1X amplitude and phase 

– 2X amplitude and phase 

– Not 1X amplitude 

• Windows®-based Operator Display Software 

• Data displayed at multiple locations 

2.1.2 Improved Integration to Plant Control Computer

The 3500 improves integration to the plant control computer with: 

• Communication Gateways supporting multiple protocols 

• Time synchronized vibration and process information 

2.1.3 Reduced Installation and Maintenance Costs 

The 3500 system provides the following cost-saving features: 

• Reduced cabling costs 

• Downward product compatibility 

• Improved space utilization 

• Easier configuration 

• Reduced spare parts 

• Improved serviceability 

2.1.4 Improved Reliability 

The 3500 offers several features to improve system reliability. 

• Redundant power supplies available 

• Triple Modular Redundant (TMR) monitors and relay cards available

2.1.5 Intrinsic Safety Option 

If you wish to monitor equipment that is located in hazardous atmospheres, the 

3500 Monitoring System has a range of I/O modules with internal zener barriers. 

These modules provide an Intrinsically Safe interface between the 3500 rack and 

the transducers located in the hazardous area. 

2.1.6 Multiple Output Interfaces 

You can conveniently adjust monitor options (such as full scale ranges, 

transducer inputs, recorder outputs, alarm time delays, alarm voting logic, and 

relay configuration) in the field via software. Modular system design employs 

plug-in components which allow easy servicing and expansion. 

The following three independent interfaces are available with the 3500 system: 

• Data Manager Interface (Transient Data Interface External or Dynamic 

Data Interface External) 

• Configuration/Data port 

• Communications Gateway (support for Programmable Logic 

Controllers, Process Control Computers, Distributed Control Systems,

and PC-based Control Systems) 

These interfaces allow you to easily view monitored parameters and their 

statuses in the following ways: 

• System 1® Software 

• Bently Nevada™ 3500 Operator Display Software 

• Remote display panel 

• DCS or PLC display 

Convenient front panel coaxial connectors provide dynamic transducer signals 

and allow you to connect diagnostic or predictive maintenance instruments. 

2.2 Common Features 

The common features of the modules in the 3500 rack include hot insertion or

removal of modules and external and internal termination of the wiring. 

2.2.1 Hot Insertion or Removal of Modules 

When performed properly, you can remove and replace any module while the 

system is under power without affecting the operation of any unrelated modules. 

If the rack has 2 power supplies, removing or inserting a power supply will not

disrupt the operation of the 3500 rack. See <<Section reverence: “Module 

Installation in section 4 >> for the proper procedure. 

2.2.2 External and Internal Termination 

External termination uses multi-conductor cables to connect the I/O modules to 

the terminal blocks. These blocks simplify connecting many wires to the rack in 

tight areas. External termination is not available on I/O modules with internal 

zener barriers

3500 System Components 

The 3500 Monitoring System consists of modules that fit into a rack. Figure 2-3 

shows a full-size 3500 system rack and system components. Note that the fullsize rack has 14 monitor slot positions. The Mini-rack (not shown) is similar, but 

has 7 monitor slot positions to the right of the power supplies and Rack Interface 

Module. 

1. 1 or 2 power supplies

2. Rack Interface Module (standard, Transient Data Interface, (TDI), Triple Modular Redundant (TMR) and TMR TDI) 

3. Monitoring slot positions: 

– Monitor module

– Keyphasor® module (2 maximum) 

– Relay module 

– Communication Gateway module

– Display module. For the System Face Mount you must install the Display Interface Module in Slot 15.

– 3500/04-01 Earthing Module. Intallations that use Inernal Barrier I/Os require 1 Earthing Module per rack. 

Figure 2-3: 3500 Rack (Full-Size) 

The following sections list the function of each module. Refer to the individual 

operation and maintenance manuals for available options, detailed description, 

operation and maintenance. 

2.3.1 Weatherproof Housing 

The weatherproof housing protects the 3500 rack from adverse environmental 

effects, such as excessive moisture, dirt and grime, and even unclean air. The 

weatherproof housing will not accommodate a Display Unit or VGA Display. 

2.3.2 Rack 

2 types of 3500 racks are available: the full-size 19-inch rack and the compact 12-

inch Mini-rack. Each rack requires you to install the Power Supplies and Rack 

Interface Module (RIM) in specific locations. The full-size version offers 14 

additional rack positions and the Mini-rack offers 7 additional rack positions. You 

may use these positions to install any combination of modules. Both racks 

support Standard (non-redundant) and Triple Modular Redundant (TMR) 

configurations. 

2.3.3 Power Supply 

The Power Supply is a half-height module available in ac and dc versions. You 

can install 1 or 2 power supplies in the rack. Each power supply can power a fully 

loaded rack. When you install 2 power supplies in a rack, the supply in the lower 

slot acts as the primary supply and the supply in the upper slot acts as the 

backup supply. If the primary supply fails, the backup supply will provide power to 

the rack without interrupting rack operation. The 3500 design allows you to 

install any combination of power supply types. 

Overspeed Detection and TMR Monitors require dual power supplies. 

2.3.4 Rack Interface Module 

The Rack Interface Module (RIM) is a full-height module that communicates with

the host (computer), a Bently Nevada™ Communication Processor, and the other 

modules in the rack. The Rack Interface Module also maintains the System Event 

List and the Alarm Event List. You can daisy-chain this module to the Rack 

Interface Modules in other racks and to the Data Acquisition / DDE Server 

Software. The 3500 Monitoring System Computer Hardware and Software Manual

shows how to daisy chain the Rack Interface Modules together. Rack Interface 

Modules are available in Standard, Triple Modular Redundant and Transient Data 

Interface versions. 

2.3.5 Communication Gateway Module 

The Communication Gateway Module is a full-height module that allows external 

devices (such as a DCS or a PLC) to retrieve information from the rack and to set 

up portions of the rack configuration. You can install more than one 

Communication Gateway Module in the same rack. Communication Gateway 

Modules are available for a variety of network protocols. 

2.3.6 Monitor Module 

The Monitor Modules are full-height modules that collect data from a variety of 

transducers. You can install any combination of Monitor Modules in the 3500 

rack. 

2.3.7 Relay Module 

Relay Modules provide relays that you can configure to close or open based on 

channel statuses from other monitors in the 3500 rack. Relay modules are 

available in 4-channel, 16-channel, and 4-channel Triple Modular Redundant 

(TMR) versions. 

The TMR Relay Module is a half-height 4-channel module that operates in a TMR

system. 2 half-height TMR Relay Modules must operate in the same slot. If you 

remove the upper or lower Relay Module or the system declares one of the 

modules as Not OK, then the other Relay Module will control the Relay I/O Module. 

2.3.8 Keyphasor® Module 

The Keyphasor Module is a half-height module that provides power for the 

Keyphasor transducers, conditions the Keyphasor signals, and sends the signals 

to the other modules in the rack. The Keyphasor Module also calculates the rpm 

values sent to the host (computer) and external devices (DCS or PLC) and provides 

buffered Keyphasor outputs. Each Keyphasor Module supports 2 channels. You 

may place up to 2 Keyphasor Modules in a 3500 rack for a maximum of 4 

Keyphasor channels. If you use 2 Keyphasor Modules, you must place them in the 

same full-height slot and the modules will share a common I/O module. 

2.3.9 Display Module 

The 3500 system offers multiple display options. 

The Display Interface Module can display rack data on an LCD-based Interface 

unit or a 3rd-party Modbus® based display unit. 

The VGA Display Module will display rack data on certain touch screen VGA 

Displays. 

The Integrated PC display is a complete rack mount touch screen PC pre-loaded 

with rack configuration software and display utilities. 

2.3.10 Earthing Module 

The Earthing Module is a full-height module that provides a low resistance 

connection (must be less than 1 Ω) from the 3500 rack to the plant’s intrinsically 

safe earth ground. The module operates in conjunction with the 3500 internal 

zener barrier I/O modules. Your application will require 1 Earthing Module per rack 

when internal barrier I/O modules are used. 

2.4 Standard Rack Relay Options 

You can configure the standard (or non-TMR) 3500 rack to have individual relays, 

bussed relays, or a combination of individual and bussed relays. 

2.4.1 Individual Relays 

A rack with individual relays contains 1 or more relay cards for each monitor 

module. You can configure the monitor and relay modules within a 3500 rack in 

many ways. 

Example 1: The application uses 1 relay module 1 monitor module. 

Table 2-1: 1 Relay Module Used With 1 Monitor Module 

2.5 Intrinsic Safety — The 3500 Internal Barrier System 

To provide Intrinsically Safe (IS) vibration and process variable monitoring, the 

3500 system has a range of I/O modules with internal zener barriers. When you 

install these modules in a 3500 rack with a 3500/04-01 Earthing Module, they 

provide an integrated solution for explosion protection for approved Bently 

Nevada transducer systems that are located within all classifications of 

hazardous areas (surface industries other than mining). 

2.5.1 3500 Internal Barrier System Restrictions 

• You must install 1 earthing module in each rack in the internal barrier 

system. The earthing module occupies 1 slot position in the rack when it 

uses Internal Barrier I/O modules.

• You must change the grounding configuration of the 3500/15 Power 

Supplies from the default factory setting. See the 3500/15 Operation and 

Maintenance Manual (PN 129767-01) for instructions. 

• You must isolate any RS-232 connection to any 3500 module. Monitors 

that support RS232 connections include Rack Interface Modules, 

Communication Gateways, and the 3500/95 PC Display. See the 3500/20 

Operation and Maintenance Manual (PN 129768-01) for instructions. This 

restriction does not apply to RS422 and RS485 connections to the rack. 

Monitors that support RS422 and/or RS485 connections include the 

3500/20, 3500/90, 3500/92, 3500/93, and 3500/95. 

• You must not use the 3500/94 VGA Display in internal barrier systems. 

• You must not use bussed transducers, as internal barrier systems do not 

allow bussed transducers. See the TMR section of this manual for more 

information. 

2.5.2 3500 Internal Barrier System Features 

• The earthing module supports dual IS Earth connections for cables with 

cross-sectional areas up to 10 mm2. This module lets you test IS Earth

continuity online. 

• The design of the internal barrier I/O modules provides the 2 inches (50 

mm) of separation required between safe and hazardous area field wiring. 

• The connectors for safe areas and hazardous areas have different field 

wiring colors (green for safe and blue for hazardous) and connector 

pitches. This helps to avoid incorrect field wiring installation. 

• Quick connect/disconnect connectors simplify field wiring installation and 

removal. 

4.3 Replacing Modules 

When replacing modules, whether main or I/O, you need not remove power from 

the rack if the following procedures are followed. Refer to applicable steps in the 

procedures above for removing or installing a module. 

4.3.1 Main Modules 

This assumes that you will replace only the main module of a monitor or power 

supply. Before you remove any module, refer to the applicable manual to see how 

this may affect rack behavior, and to identify any special handling requirements 

that you may require for personal safety. 

1. If necessary, upload and save the configuration of the module to be 

replaced. 

2. Remove the main module from the rack. 

3. Install the new main module into the rack. 

4. If necessary, configure the new main module. 

5. Verify operation. 

4.3.2 I/O Modules 

This assumes that you will replace only the I/O module of a monitor or the PIM of 

a power supply. Before you remove any module, refer to the applicable manual to 

see how this may affect rack behavior, and to identify any special handling 

requirements that you may require for personal safety. 

1. If necessary, upload and save the configuration of the module to be 

replaced. 

2. Remove the main module from the rack. 

3. Remove the field wiring from the I/O module. 

4. Remove the old I/O module from the rack. 

5. Install the new I/O module into the rack. 

6. Connect the field wiring to the new I/O module. 

7. Install the main module into the rack. 

8. If necessary, re-configure the main module. 

9. Verify operation

5.1 General Maintenance Instructions 

You cannot repair the boards and components inside of 3500 modules in the field. 

3500 rack maintenance consists of testing module channels to verify that they 

are operating correctly. You should replace modules that are not operating 

correctly with a spare. 

When performed properly, you may remove modules from or install modules into 

the rack while power is applied to the rack. Refer to Section 3 for the proper 

procedure. 

The 3500 Monitoring System is a high precision instrument that requires no 

calibration. The functions of the 3500 modules, however, require verification at

regular intervals. You should verify all modules in the 3500 Monitoring System at 

these maintenance intervals. The procedures in the Maintenance and 

Troubleshooting sections of the module manuals describe the verification and 

troubleshooting process. 

5.2 Choosing a Maintenance Interval 

Use the following approach to choose a maintenance interval: 

1. Start with an interval of 1 year and then shorten the interval if any of the 

following conditions apply: 

• the monitored machine is classified as critical, or 

• the 3500 rack is operating in a harsh environment such as in 

extreme temperature, high humidity, or a corrosive atmosphere. 

2. At each interval, use the results of the previous verifications and ISO 

Procedure 10012-1 to adjust the interval. 

benderAC/DC sensitive residual current monitor RCMA475LY

Residual current monitor

RCMA475LY

AC/DC sensitive residual current monitor

for TN and TT systems (AC, DC, pulsating DC currents)

Product description

The AC/DC sensitive residual current monitor RCMA475LY is designed for monitoring 

earthed power supply systems (TN and TT systems) where DC fault currents or residual 

currents continuously greater than zero may occur. These are in particular loads containing 

six-pulse rectifiers or one way rectifiers with smoothing, such as converters, battery chargers, 

construction site equipment with frequency-controlled drives. 

The prewarning stage (50 % of the set response value IΔn1) allow to distinguish between 

prewarning and alarm. Since the values are measured with measuring current transformers, 

the device is nearly independent of the load current and the nominal voltage of the system.

Application

• AC/DC sensitive residual current monitoring in earthed two, three or four conductor 

systems (TN and TT systems)

• AC/DC sensitive current monitoring of single conductors de-energised under normal 

conditions (e.g. N and PE conductors)

• Variable-speed drives

• Uninterruptible power supply systems (UPS)

Function

Residual current monitoring takes place via an internal measuring current transformer. 

When the current respectively the residual current exceeds the set response value, the alarm 

LED lights and the associated alarm relay switches when the set response delay has elapsed.

The alarm messages are stored. The fault memory can be reset by pressing the reset button. 

The device function can be tested using the test button. 

The currently measured value in per cent related to the set response value is indicated on 

the LED bar graph indicator. 

Device features

• Internal measuring current transformer 

ø 18 mm

• Two response values

alarm IΔn1: 30…500 mA (0…700 Hz)

prewarning IΔn2: 50 %/100 % of IΔn1

• Response delay, adjustable 0…10 s 

(prewarning 0/1 s) 

• Two separate alarm relays with one 

changeover contact each

• N/O or N/C operation, selectable 

• Fault memory 

• Combined test/reset button

• Connection external test and reset button

• LED bar graph indicator IΔn 0…100 % 

• Connection external measuring instrument 

IΔn 0…100 % 

• Sealable transparent cover

• External supply voltage

• Type B acc. to IEC/TR 60755

1 – Supply voltage US, see ordering information 

(6 A fuse recommended)

2 – External measuring instrument

3 – External test and reset button “T/R”

4 – Alarm relay (Alarm):

switches when the fault current exceeds the response value of IΔn1.

5 – Alarm relay (prewarning):

switches when the fault current exceeds 50 % or 100 % of IΔn1.

6 – Internal measuring current transformer

Do not route the PE conductor through the measuring current 

transformer!

.

1 – Combined test/reset button “TEST/RESET”; short-time pressing (< 1 s) = RESET, long-time pressing (> 2 s) = TEST.

2 – Power On LED “ON”: lights when the device is in operation 

and flashes when the measuring range is exceeded.

3 – Alarm LED “ALARM”: lights when the fault current exceeds 

the set response value and flashes when 50 % of the set response value are reached.

4 – LED bar graph indicator, shows the measuring value in per 

cent related to the preset response value.

5 – Potentiometer for setting the response delay (0…1 s).

6 – Potentiometer for setting the response value (x 1…10 mA).

Setting of the DIP switches (white = switch position)

7 – Contact 21-22-24 (prewarning)

A – at 50 % of IΔn1

B – at 100 % of IΔn1

8 – Response delay prewarning

A – Delay 1 s

B – Delay 0 s

9 – Alarm relay

A – N/O operation

B – N/C operation

10 – Response range

A – 30 mA x 1…10

B – 50 mA

11 – Response delay

A – Setting value t/s x 10

B – Setting value t/s x 1

Technical data

Insulation coordination acc. to IEC 60664-1

Rated insulation voltage AC 250 V

Rated impulse withstand voltage/pollution degree 4 kV/3

Voltage ranges

Supply voltage US see ordering information

Operating range of US 0.85…1.1 x US

Frequency range of US DC/50…60 Hz

Eigenverbrauch ≤ 3.5 VA

Measuring circuit/response values

Internal measuring current transformer ø 18 mm

Operating characteristics acc. to IEC/TR 60755 Type B

Rated residual operating current IΔn2 (prewarning) 50 %/100 % of IΔn1

Response delay tv 0/1 s

Rated residual operating current IΔn1 (alarm) 30…500 mA

Response delay tv, adjustable 0…10 s

Rated frequency 0…700 Hz

Relative uncertainty of the response value 0…25 %

Hysteresis approx. 25% of the response value

Response time tan at IΔn1 = 1 x IΔn1/2 (tv = 0 s) ≤ 70 ms

Response time tan at IΔn1 = 5 x IΔn1/2 (tv = 0 s) ≤ 40 ms

Displays

LED bar graph indicator 0…100 %

LEDs Power On, prewarning, alarm

Inputs/outputs

Test and reset button internal/external

Cable length for external test and reset button ≤ 10 m

Current source for external measuring instrument 0…100 % DC 0…400 µA

Load ≤ 12.5 kΩ

Switching elements

Number of switching elements 2 x 1 changeover contact

Operating principle, adjustable N/C operation/N/O operation

Electrical endurance, number of cycles 12000

Rated contact voltage AC/DC 150 V

Making capacity AC/DC 5 A

Breaking capacity 2 A, AC 230 V, cos phi = 0.4 

0.2 A, DC 220 V, L/R = 0.04 s

Fault memory ON

Environment/EMC

EMC immunity EN 61543 

EMC immunity EN 61000-6-4

Shock resistance IEC 60068-2-27 (during operation) 15 g/11 ms

Bumping IEC 60068-2-29 (during transport) 40 g/6 ms

Vibration resistance IEC 60068-2-6 (during operation) 1 g/10…150 Hz

Vibration resistance IEC 60068-2-6 (during transport) 2 g/10…150 Hz

Ambient temperature (during operation) -25…+70 °C

Ambient temperature (for storage) -40…+75 °C

Climatic class acc. to DIN IEC 60721-3-3 3K5

Connection

Connection type modular terminals

Connection properties

rigid/flexible 0.2…4/0.2…2.5 mm²

flexible with ferrules without/with plastic collar 0.25…2.5 mm²

Conductor sizes (AWG) 24…12

Other

Operating mode continuous operation

Mounting any position

Degree of protection, internal components (IEC 60529) IP30

Degree of protection, terminals (IEC 60529) IP30

Type of enclosure X475

Enclosure material polycarbonate

Screw mounting 2 x M4

DIN rail mounting acc. to IEC 60715

Installation into standard distribution panels acc. to DIN 43871

Flammability class UL94V-0

Product standards IEC 62020, DIN EN 62020 (VDE 0663)

Operating manual TBP404001

Weight ≤ 350 g

Suitable system components

Basler ElectricDECS-200-1C Digital Excitation Control System

One DECS-200 Digital Excitation Control System can accommodate 32Vdc, 63Vdc, or 125Vdc applications up to 15Adc. This unique flexibility provides precision control of generators of virtually any size. The DECS-200 also incorporates a pulse width modulated power stage, which improves system performances in non-linear load applications.

FEATURES

• Microprocessor-based design

• True RMS sensing, single or three phase

• 32Vdc, 63Vdc, and 125Vdc outputs at 15Adc

• 0.25% Voltage Regulation Accuracy

• Setup from front panel HMI or by PC with Windows® setup software included

• 20 standard stability selections

• User customizable stability selection

• Paralleling compensation

• Underfrequency compensation or V/Hz Ratio Limiter

• Soft start buildup

• Field Current Regulation Mode (Manual Mode)

• Autotracking between operating modes and between DECS-200 units

(optional)

• Minimum Excitation Limiter (Internally generated or customizable)

• On and off-line Maximum Excitation Limiters

• Stator Current Limiter

• Var and Power Factor Controllers

• Exciter Diode Monitoring (EDM)

• Sequence of Events Recording

• Oscillography

FEATURES, continued

• Voltage Matching

• Eight (8) generator protection features

• Programmable output contacts

• Front panel backlit LCD display

• Front panel mounted RS-232 and side RS-485

communications ports

• Modbus™ protocol for RS-485 input allows

communications up to 4000 feet away

• <1% metering accuracy for 12 generator parameters

• Remote set point control via:

– Contact inputs

– Proportional control via ±10Vdc or 4-20mA

– Communications inputs RS-232 (ASCII) or RS-485

 (Modbus™)

• Meets C37.90.1-1989 for Surge Withstand and Fast

Transient

• UL recognized, CSA certified, CE compliant, DNV

certified, GOST-R certified, Byelorussian certified

• U.S. Patent Number 5,294,879

DESCRIPTION

The microprocessor based DECS-200 is a total excitation control system in one enclosure. It contains all the

functionality necessary to limit, control, and protect a

generator from operating outside of the machine’s

capability. A feature of DECS-200’s sophisticated

design allows the nonactive control mode within the

unit to follow the active mode, permitting bumpless

transfer between modes. The optional external tracking

feature also allows for unit-to-unit communication,

permitting autofollowing and transfer between DECS200 units. It can also communicate to a PC via the front

panel RS-232 port for local programming and metering,

and it can communicate via Modbus™ protocol via the

side RS-485 port for communications up to 4000 feet

away from the DECS-200 unit. The DECS-200 has all

the features, functionality, flexibility and programmability expected from a state-of-the-art microprocessor

based product.

APPLICATIONS

The DECS-200 is an excitation control system used to control the output voltage, vars or power factor of a

synchronous generator by varying or controlling the amount of dc excitation applied to the generator’s exciter

field. The DECS-200 is suitable for virtually any size machine

SPECIFICATIONS, continued

Generator Current Sensing Two ac current sensing ranges and two channel (phase) inputs:

• For metering and control: 1A and 5A.

• For cross current compensation: 1A and 5A.

Sensing Burden Voltage: Less than 1VA per phase.

Current: Less than 1VA.

Parallel Compensation: Less than 1VA.

Contact Switching Inputs 11 contact switching inputs are supplied with 24Vdc to accommodate dry

contacts. Contacts are as follows:

• Start • Var/PF Enable

• Stop • Pre-position

• Secondary DECS Enabled (optional) • Raise Switch

• Unit/Parallel Operation • Lower Switch

• AVR Mode • Alarm Rest

• FCR Mode

Remote Set Point Control Two separate analog inputs for remote set point control. Typically used to accept

(Accessory Input) a signal from a Power System Stabilizer. Select one from the configuration menu.

• ±10Vdc

• 4 to 20 milliamperes

COMMUNICATION There are three communication ports, two RS-232 and one RS-485: COM0: RS-232, 9 pin, sub-D connector located on front panel and used to communicate with local computers. 1200 to 19200 baud, 8N1 full duplex, ASCII commands COM1: RS-232, 9 pin, sub-D connector located on right side panel and used to connect primary and backup DECS-200 units. Port is only used for optional autotracking. COM2: RS-485, located on left side panel and used to communicate with local or remote computers or other devices. 1200 to 19200 baud, 8N1 half duplex, Modbus™ protocol

SPECIFICATIONS, continued

REGULATION ACCURACY

AVR Mode: Voltage regulation equals ±0.25% over the load range at rated power factor and constant

generator frequency. Steady state stability equals ±0.1% at a constant load and generator frequency.

Temperature drift equals ±0.5% for 0 to 50°C temperature change. Underfrequency (volts/hertz)

characteristic slope from 0 to 3.0 P.U. is adjustable in 0.1 P.U. increments.

FCR Mode: Field current regulation equals ±1.0% of the nominal value for 10% of the bridge input voltage

change or 20% of the field resistance change.

var Mode: ±2.0% of the nominal VA rating at the rated frequency.

PF Mode: ±0.02 PF in the set point PF for the real power between 10 and 100% at the rated frequency.

(e.g. -set point PF=0.80, PF regulation is from 0.78 to 0.82 PF.)

Internal autotracking(optional): ±0.5% of the nominal field voltage change when transferring.

PARALLEL COMPENSATION Can use either reactive droop or reactive differential (cross-current) compensation. Adjustable from 0 to 30% of the rated generator voltage droop with optional 1 ampere or less or 5 amperes

or less input. Line drop compensation uses this same parameter; however, it is adjustable from -30% to 0.

FIELD OVERVOLTAGE PROTECTION Adjustable in increments of 1.0Vdc from 1.0 to 325Vdc rated output

voltage with a 0.2 to a 0.2 to 30 second inverse time delay settable in increments of 0.1 second.

FIELD OVERCURRENT PROTECTION Adjustable in increments of 0.1Adc steps of rated field current from 0 to

16Adc excitation current setting with an inverse time delay (ANSI C50.13).

EXCITER DIODE MONITOR (EDM) The DECS-200’s EDM can detect open and shorted diodes on brushless

generators. To do this, the DECS-200 requires the user to input the number of generator poles and the number of

exciter poles (both adjustable from 0 to 20 in increments of 2). The open and shorted diode ripple threshold is

adjustable from 0 to 100% of field current. The open diode protection time delay is adjustable from 10 to 60

seconds, and the shorted diode protection time delay is adjustable from 5 to 30 seconds.

GENERATOR UNDERVOLTAGE PROTECTION Adjustable in increments of 1Vac from 0 to 30kV sensing voltage

setting with a 0.5 to 60 second time delay (ANSI C50.13) settable in increments of 0.1 sec.

GENERATOR OVERVOLTAGE PROTECTION Adjustable in increments of 1Vac from 0 to 30kV sensing voltage

with a 0.1 to 60 second time delay (ANSI C50.13) settable in increments of 0.1 second.

GENERATOR LOSS OF FIELD PROTECTION Adjustable in increments of 1 kVar from 0 to 3,000Mvar, with a

0.1 to 9.9 second delay settable in increments of 0.1 second.

LOSS OF SENSING The loss of sensing setting for both balanced and unbalanced generator voltage is adjustable from 0 to 100% of nominal generator voltage. The protection delay is adjustable from 0 to 30 seconds in 0.1

increments.

SOFT START Functional in AVR and FCR with an adjustable rate of 1 to 7200 seconds in one second increments.

SUMMING POINT and TAKEOVER TYPE

OVEREXCITATION LIMITING Limiter response time is less than three cycles.

SUMMING POINT TYPE:

On-Line High Current Level (instantaneous) set point adjustable from 0 to 30.0Adc in 0.1Adc increments. Limiting occurs for a time period ranging from 0 to 10 sec., settable in 1 sec. increments.

Medium Current Level set point adjustable from 0 to 20Adc in 0.1Adc increments.

Limiting occurs for a time period ranging from 0 to 120 seconds, settable in 1 sec. increments.

Low Current Level set point adjustable from 0 to 15Adc in 0.1Adc increments. Limiting occurs

SPECIFICATIONS, continued

Off-Line High Current Level (instantaneous) set point adjustable from 0 to 30Adc in 0.1Adc increments.

Limiting occurs for a time period ranging from 0 to 10 seconds, settable in 1 second increments.

Low Current Level set point adjustable from 0 to 15Adc in 0.1Adc increments. Limiting occurs indefinitely.

TAKEOVER TYPE OEL: The Takeover OEL uses an I2

t characteristic.

On-Line High Level: High Current Level (instantaneous) set point is adjustable from 0 to 30.0Adc in 0.1

Adc increments.

Low Level: Low Current set point is adjustable from 0 to 15.0Adc in 0.1Adc increments. Limint

occurs indefinitely.

Time Dial – This setting determines the inverse time curve selected.

Off-Line High Level – High current level (instantaneous) set point is adjustable from 0 to 30.0Adc in

0.1Adc increments.

Low Level – Low current set point is adjustable from 0 to 15.0Adc in 0.1Adc increments. Limiting

occurs indefinitely.

Time Dial – This setting determines the inverse time curve selected.

UNDEREXCITATION LIMITING Adjustments based on generator ratings.

STATOR CURRENT LIMITING

High Level – High current level set point adjustable from 0 to 60,000Aac in 0.1Aac increments.

Limiting occurs for a time period ranging from 0 to 60 seconds, settable in 0.1 sec. increments.

Low Level – Low current level set point adjustable from 0 to 60,000Aac in 0.1Aac increments.

Limiting occurs indefinitely.

SEQUENCE OF EVENT RECORDING (SER) 127 event reports stored in volatile memory (retrievable via

BESTCOMS). SER triggered by: Input/Output status changes, system operating status changes, and alarm annunciations.

OSCILLOGRAPHY Stores 8 records. Up to 6 variables can be logged in a record. Sampling rate: 600 data points

per log, pre-trigger adjustable from 0 to 599 data points, 4ms to 10sec intervals between data points (2.4sec to

6000sec. total log duration)

MANUAL EXCITATION CONTROL Regulates field current from 0 to 15.0A in increments of 0.1Adc.

VOLTAGE MATCHING Matches utility bus RMS voltage with generator output RMS voltage within ±0.15% of

the generator voltage

REAL TIME CLOCK Time displayed in either 12 hour or 24 hour format and can be selected to allow for daylight

savings timer. The date is selectable for two formats: d-m-y or m/d/y. Requires control power to operate. If power is

lost, the clock will need to be reset.

SURGE WITHSTAND CAPABILITY (SWC) IEEE C37.90.1-1989

FAST TRANSIENT IEEE C37.90.1-1989

HIGH POT. IEEE 421.3

ENVIRONMENTAL

Operating temperature: -40°C to +60°C (-40°F to +140°F) Storage temperature: -40°C to +85°C (-40°F to +185°F)

Salt Fog Per MIL-STD-810E, Method 509.3 (100 hrs. of salt fog, 100 hours of drying time)

Shock 15 Gs in each of three mutually perpendicular planes

Vibration 5-26Hz: 1.2Gs; 27-52Hz: 0.914mm (.036 inch) double amplitude; 53-500Hz: 5.0Gs

Size 8.08″ (205mm) wide x 6.76″ (171mm) deep x 12.0″ (304mm) high

Weight 14 lbs. (6.35kg)

AGENCY UL recognized per Std. 508; UL file number E97035; CSA certified per Std. CAN/CSA-C22.2,

Number 14, CSA file number LR23131; CE compliant, EMC and LVD; Certified per DNV

FEATURES/FUNCTIONS

Voltage Regulation

The DECS-200 regulates the generator RMS voltage to within

0.25% from no-load to full-load. It does this by utilizing digital

signal processing and precise regulation algorithms developed

by Basler Electric, utilizing the experience gained in many years

of manufacturing tens of thousands of digital voltage regulators.

Stability

The DECS-200 utilizes proportional (P), integral (I) and derivative

(D) stability control. DECS-200 has 20 preprogrammed stability

(PID) settings for exciter field applications. This means that a

standard stability setting is already available for most applications/machines. The DECS-200 has a stability range that allows

for customizing the stability settings to fine tune the stability to

provide optimum customized generator transient performance.

Setup software contains PID selection program to assist in

determining the correct PID settings. The DECS-200 provides for

customizing the stability and transient performance of the Min/

Max Excitation Limiter and var/PF controllers by providing

additional stability adjustments.

Underfrequency Limiter or V/Hz Ratio Limiter

DECS-200 is selectable for either Underfrequency Limiter or a

V/Hz Ratio Limiter function. The underfrequency limiter slope can

be tuned to have 0 to 3 times p.u. Volts/Hz, in 0.1Hz increments,

and the corner frequency roll-off point can be set across a range

of 45 to 65Hz, in 0.1Hz increments. This adjustability allows the

DECS-200 to precisely match the operating characteristics of the

prime mover and the loads being applied to the generator. The

Volts/Hz Ratio Limiter clamps the regulation set point to prevent

operation above a V/Hz level that is prescribed by the slope of the

DECS-200. This feature is also useful for other potentially

damaging system conditions such as a change in system voltage

and re-duced frequency situations that exceed the V/Hz ratio.

Soft Start Voltage Buildup

Generator voltage overshoot can be harmful to the generator’s

insulation system if not controlled. DECS-200 has a soft start

feature with a user-adjustable setting to govern the rate at which

the generator voltage is allowed to build up. This reduces the

amount of generator voltage overshoot form nominal operating

voltage during start-up of the generator system.

Paralleling Compensation

DECS-200 has provisions to parallel two or more generators

using reactive droop or reactive differential compensation with

the addition of an external current transformer with secondary

currents of 1 or 5Aac. The current input is rated at less than 1VA.

This low burden means that existing metering CTs can be used

and dedicated CTs are not required.

Set Point Control

DECS-200 has means for external set point adjustment of the

controlling mode of operation. This eliminates the need for

additional equipment like motor operated potentiometers for

remote control or multiple point control for the excitation system.

The operating mode’s set point may be directly controlled by

raise/lower contact inputs or auxiliary inputs of 4-20mA or

±10Vdc. The auxiliary input adjusts the operating mode across its

predetermined adjustment range. The auxiliary input can be

provided from other controlling devices such as a power

system stabilizer. These devices modify the operation of the

DECS-200 to meet specific operating characteristics and requirements for the machine under DECS-200 control. Two more

methods of set point control may be achieved via the RS-232

communication port by using the Windows® based PC software

or by the RS-485 port using Modbus™ protocol. Regardless of

which method of set point is used (contact inputs, auxiliary input

or communications with a PC or PLC), traverse rates of all modes

of operation are independently adjustable. This means an

operator can customize the rate of adjustment and “feel” to meet

his/her needs.

Pre-position Inputs

DECS-200 provides the added flexibility of allowing a predetermined operating point for each mode of operation. With a contact

input to the DECS-200, the operating mode is driven to an

operating or regulation level assigned to that operation mode by

the operator or user. The pre-position inputs operate in one of two

modes, Maintain or Release. The Maintain mode prevents

adjustment of the setpoint as long as the pre-position contact is

closed. The release mode allows adjustment of the setpoint even

though the pre-position is closed. This feature allows the DECS200 to be configured for specific system and application needs.

Field Current Regulation Operating Mode

DECS-200 provides a manual channel of operation called Field

Current Regulation, or FCR, Mode. In this mode, DECS-200

regulates the field current generated by the internal PWM power

stage. It does not rely on the sensing input to DECS-200 and is,

therefore, a good source of backup excitation control when loss

of sensing is detected. In this mode, control of the generator is

totally dependent upon the operator to maintain nominal generator voltage as the load varies on the generator.

Var/Power Factor Controller Operating Mode

DECS-200 has, as another standard feature, two modes of

operation when the generator is in parallel with the utility power

grid. The DECS-200 has both var and PF modes of operation.

When the generator is in parallel with the utility grid, the DECS200 can regulate the var output of the generator to a specific var

level magnitude or it can vary the var output of the generator to

maintain a specific power factor as the kW load varies on the

generator.

Maximum Excitation Limiters

Overexcitation limiting (OEL) operates in all modes except FCR

mode. OEL senses the field current output of the voltage regulator or static exciter and limits the field current to prevent field

overheating. In FCR mode, the DECS-200 only announces that all

conditions for OEL are fulfilled and does not provide limiting. The

DECS-200 provides two types of overexcitation: Summing Point

and Takeover.

Summing Point Type OEL

Three OEL current levels are defined for on-line operation. They

are high, medium, and low. The generator can operate continuously at the low OEL current level and for programmed times at

the high and medium OEL current levels. Two OEL current levels

are defined for off-line (main breaker open) operation. They are

high and low. The generator can operate continuously at the low

OEL current level and for a programmed time at the high OEL

current level.

FEATURES/FUNCTIONS, continued

Takeover Type OEL

The field current level at which limiting occurs is determined by an

inverse time characteristic. Two current levels and a time dial

setting are defined for the takeover-style OEL limiter. Separate

curves may be selected for on-line and off-line operation. If the

system enters an overexcitation condition, the field current is

limited and made to follow the selected curve. The selection of

on-line or off-line OEL levels/curves is determined by an OEL

option selection.

Minimum Excitation Limiter

The minimum excitation limiter limits the amount of excitation

supplied to the field of the generator from dropping below unsafe

operating levels. This prevents the machine from possibly slipping

poles and from damaging the machine. It limits the amount of

vars being absorbed by the machine, based on user-definable

settings. An internally generated Underexcitation Limiting (UEL)

curve can be utilized based on a var level at 0kW, or a

customizable 5 point UEL curve can be selected to match specific

generator characteristics.

Stator Current Limiter

The stator current limiter (SCL) senses the level of stator current

and limits it to prevent stator overheating. The SCL operates in all

modes except FCR. In FCR mode, the DECS-200 only announces

that a stator overcurrent condition exists; it does not provide

current limiting. Two SCL current levels are provided: high and

low. The generator can operate continuously at the low SCL level

but only for a programmed time at the high SCL level.

Internal Autotracking Between DECS-200 Operating

Modes

DECS-200 is an intelligent device that can provide autotracking

(autofollowing) of the controlling mode by the non-controlling

modes. This allows the operator to initiate a controlled, bumpless

transfer of the DECS-200 operating modes, causing minimum

amounts of line disturbance for the power system. This feature

can be used in conjunction with a set of protective relays to

initiate a transfer to a backup mode of operation, such as FCR

mode, upon the detection of a system failure or fault, i.e., loss of

sensing.

External Autotracking between Dual DECS-200 Units

(Optional)

A DECS-200 can also follow (autotrack) a second DECS-200 unit.

The second DECS-200 is put into a specific operating mode and

follows the excitation level of the first. In the unlikely event of a

failure of the first DECS-200, protective relays can initiate a

transfer of control from the first to the second DECS-200.

Protective Functions

There are several protection functions built into the DECS-200

unit. These functions may be used as backup to the primary

protection relays and can be assigned programmable output

contacts via the PC software. The protection features offer fully

adjustable tripping levels and time delays. The protective features

are as follows:

• Generator Overvoltage • Watchdog Timer

• Generator Undervoltage • Loss of Sensing

• Field Overvoltage • Loss of field

• Field Overcurrent • EDM Exciter Diode Monitor

Sequence of Events Recording (SER)

A sequence of event report (SER) is a very powerful tool when

reconstructing the exact timing of an event or disturbance. The

DECS-200 monitors its contact inputs and outputs for a change of

state, system operation changes, and alarm conditions. If any of

these events occurs, the DECS-200 will log that event with a date

and time stamp. Date and time stamping of the event allows the

user to recreate a chain of events in the sequence in which they

occurred. The DECS-200 can store 127 events in volatile

memory, and those events are retrievable using BESTCOMS.

Oscillography (See Figure 6)

The data recording feature can record up to eight (8) oscillographic records stored in volatile memory. The user can select up

to six (6) variables to be monitored when triggered by the DECS200 BESTCOMS, a Logic Trigger, or a Level Trigger. Variables

that can be selected are: generator voltage, current (single

phase), frequency, kW, Power Factor, exciter field voltage, and

current.

The user can utilize the DECS-200 BESTCOMS to trigger and

save a record of a voltage step response during commissioning.

Once commissioned, a logic trigger or level trigger can be used

to activate the data recorder to capture the occurrence for review

at a later time. DECS-200 alarms can also be used to start the

data recorder. When an alarm condition occurs, an oscillographic

record can be stored. A level trigger will initiate a record to be

saved when a variable exceeds a predetermined setting. An

example of this is when the exciter field current exceeds a

predetermined setting.

The oscillographic records are recorded in accordance with the

IEEE Standard Common Format for Transient Data Exchange

(COMTRADE). Basler Electric can provide BESTWAVE, a

COMTRADE viewer, which is a program that will allow the user to

view the oscillography records saved by the DECS-200.

Communications

DECS-200 comes complete with Windows® based PC software.

This software makes the programming and customization of the

DECS-200 easy and fast. The software comes with a PID

selection program that allows the user to select stability settings

quickly and easily in a user-friendly format. The PC software has a

special monitoring function that allows the user to view all

settings, a metering screen for viewing all machine parameters,

and a control screen for remote control of the excitation system.

The RS-485 port supports Modbus™ communications protocol.

This is an open protocol with all registers and operating instructions available in the instruction manual, to make it simple for the

user to develop custom communications-based interface.

Password Protection

All DECS-200 parameters are viewable via the front panel LCD

display, the PC software or via Modbus™ without the need of a

password. If the user wishes to change a setting, the proper

password must be entered to allow access to the parameter. Two

levels of password protection exist, one for global access of all

parameters and one for a limited amount of access to parameters

normally associated with operator control.

FRONT and SIDE PANEL VIEWS

The front panel HMI (Human Machine Interface) is composed of several elements, including a backlit LCD screen, six (6) pushbuttons and six (6) LEDs. The LCD is the primary interface because it conveys the majority of the information between the DECS-200 and the user/operator. Front panel pushbuttons allow the user to view menu screens and modify the various screen settings and operating conditions. The LEDs annunciate their respective states.

A) 64×128 pixel graphic LCD with backlighting. Primary source for receiving information from the DECS or when locally programming settings. Displays operations, set points, loop gains, metering, protection functions, system parameters and general settings. B) Pre-Position LED – Turns ON at the predefined setting (within the limits of the setpoints) of the current mode. C) Lower Limit LED – Turns ON at the minimum set point value of the current (active) mode. D) Upper Limit LED – Turns ON at the maximum set point value of the current mode. E) Scrolling Pushbuttons – Scrolls UP/DOWN/LEFT/RIGHT through the menu tree or when in the EDIT mode, the LEFT/RIGHT scrolling pushbuttons select the variable to change and the UP/DOWN scrolling pushbuttons change the variable. F) Reset Pushbutton – Cancels editing sessions and can be used as a quick-access to the metering screen. G) Serial Port COM0 – D-type 9 pin connector. This port is dedicated to RS-232 (ASCII commands) communication with a computer terminal or PC running a terminal emulation program such as BESTCOMS™. H) Edit Pushbutton – Enables settings changes. When the EDIT pushbutton is first pushed, an LED on the pushbutton turns ON to indicate the edit mode is active. When changes are complete (using the scrolling pushbuttons) and the EDIT pushbutton is pushed again, the LED turns OFF, indicating the changes are saved. If changes are not completed and saved within five minutes, the edit mode is exited without saving changes. I) Null Balance LED – Turns ON when the inactive modes (AVR, FCR, var, or PF) match the active mode. J) Internal tracking LED – All inactive modes (AVR, FCR, var, or PF) track the active mode to accomplish the bumpless transfer when changing active modes.

AlstomT1693EN Technical Manual Rev. 09

Care has been taken with the design of this product to ensure that it is safe. However, in common with all 

products of this type, misuse can result in injury or death. Therefore, it is very important that the 

instructions in this manual and on the product are observed during transportation, commissioning, 

operation, maintenance and disposal.

This technical manual must be regarded as part of the product. It should be stored with the product and 

must be passed on to any subsequent owner or user.

Local safety laws and regulations must always be observed.

Persons working on the product must be suitably skilled and should have been trained in that work for 

these products.

The product is a component designed for incorporation in installations, apparatus and machines.

The product must not be used as a single item safety system. In applications where maloperation of the 

product could cause danger, additional means must be used to prevent danger to persons.

Product approvals and certifications will be invalidated if the product is transported, used or stored outside 

its ratings or if the instructions in this manual are not observed.

Third party approvals to safety standards UL508C and CSA C22.2 No 14 are marked on the product.

In the European Union

• Products within the scope of the Low Voltage Directive, 2014/35/EU are CE marked.

• The product complies with the essential requirements of the EMC directive 2014/30/EU, when 

installed and used as described in this manual. The requirements of the EMC Directive should 

be established before any installation, apparatus or machine which incorporates the product 

is taken into service.

• A machine must not be taken into service until the machine has been declared in conformity 

with the provisions of the Machinery Directive, 2006/42/EC.

INTRODUCTION

1.1 GENERAL DESCRIPTION

An MV3000e DELTA a.c. drive is used to control a motor, generator, or power conditioning application.

It uses a modular approach which allows the use of a small number of common components to create a 

large number of system variants

Advantages Of The Modular System

• The DELTA transistor and rectifier modules are of a standard mechanical design, using the 

same mounting method and dimensions;

• DELTA rectifier and transistor modules can be connected in parallel to provide a wide range of 

power levels;

• Modular construction makes maintenance and repair work simple, and enables rapid module 

replacement;

• DELTA transistor and rectifier modules can be withdrawn on a simple slide system for ease of 

assembly and maintenance.

• Ease of handling – smaller, lighter modules are assembled to form large drives.

DELTA Product Range

• Rectifier module;

• Transistor modules;

• MV3000e Controller

• SMPS (Switch Mode Power Supply) units;

• User I/O termination panel;

• MVM (Mains Voltage Monitor);

• DDM (Drive Data ManagerTM)– Keypad;

• Reactors and transformers;

• Installation accessories (mounting kits and control cables).

ASSOCIATED MANUALS

• T1676 – MV3000e Getting Started Manual (for rectifier fed systems);

• T1679 – MV3000e Software Manual (and Firmware Supplement T2154); 

• T2002 – MV3000e Getting Started Manual (for AEM systems).

The T1676 and T2002 manuals include commissioning and operating details for the complete MV3000e

DELTA drive.

The T1676, T1679 and T2002 manuals should be regarded as part of the DELTA product. Individual DELTA 

component instructions sheets that may also be required are shown below:

• T1694 MVS3007-4002 – Profibus Field Coupler 12 Mb/s;

• T1915 MVS3000-4001 – Drive Data Manager TM (keypad);

• T1916 MVS3001-4001 – Keypad mounting kit;

• T1930 MVC3006-4003 – Mains Voltage Monitor (MVM);

• T1968 MVS3011-4001 – CANbus communications module;

• T1973 MVC3003-40xx – Switch Mode Power Supply (SMPS) Module;

• T2034 MVS3012-400x – Ethernet interface;

• T2100 MVDL800 DELTA Transistor Module;

• T2101 MVDL1000 DELTA Transistor Module;

• T2112 MVC3001-400x – DELTA Controller

Section 1 – Introduction

• Overview of the main concepts used in DELTA drives; 

Section 2 – Specifications

• Common environmental data for the DELTA product range; 

• Gives individual DELTA component data.

Section 3 – Complete Drive Module (CDM) Design

• Guidance for component selection;

• Enclosure design;

• Cooling system design;

Section 4 – Power Drive System (PDS) Design

• Motor requirements;

• Motor and supply cable selection;

• Encoder details.

Section 5 – Complete Drive Module (CDM) Assembly

• Guidance for assembly of DELTA components into an enclosure. 

Section 6 – CDM Commissioning

• Guidance for commissioning the CDM, including electrical safety checks and functional 

testing.

Section 7 – PDS Commissioning

• Guidance for commissioning the CDM in the final location.

Section 8 – Maintenance

• Diagnostic information;

• Preventative maintenance;

• Module replacement.

Section 9 – Disposal

Appendices

• Mechanical drawings of DELTA components; 

• Electrical connection diagrams

• Torque values.

DRIVE CONFIGURATIONS

A DELTA drive consists of two ‘bridges’ – the network bridge and the machine bridge.

Two generic configurations are available, each with a different network topology:

• Diode Front End (DFE) – power transfer from the network to the load only;

• Active Energy Management (AEM) – power transfer to and from the network.

Both the DFE and AEM drives share the same machine bridge topology.

Figure 1–1 is a simplified schematic diagram of a DFE system. Figure 1–2 is a simplified schematic diagram 

of an AEM system.

Circuit diagrams for the various drive configurations are included in Appendix B: Electrical Connection 

Diagrams. 

1.4.1 DFE Network Bridge

A DFE network bridge comprises of one or more diode rectifier modules, plus ancillary components, which 

could include:

• Line reactor;

• Fusing;

• Pre-charge circuit;

• Interbridge transformer;

• D.C. Link inductor.

The network bridge converts the a.c. supply to an unsmoothed d.c. voltage. Power flow is from the network 

supply only.

Harmonic currents produced in the supply system by variable speed drives with uncontrolled rectifier inputs 

may be reduced by changing from 6 pulse to 12 pulse (6 phase) input.

In the case of a 12 pulse input:

• A phase shifting transformer is used to produce the additional 3 phases which are phase 

shifted by 30° as shown in Figure 1–1. These two sets of three phase supplies are rectified by 

two rectifier bridges.

• Instantaneous voltage differences, between the outputs of the two rectifiers, are absorbed by 

an interbridge transformer connected between the two positive outputs of the rectifiers. The 

output to the d.c. link is taken from the centre-tap of the interbridge transformer.

1.4.2 Sinusoidal Front End (AEM Network Bridge)

The network bridge of an AEM drive comprises of one to six DELTA transistor modules. The network bridge 

is combined with the following ancillary components to form a Sinusoidal Front End (SFE):

• Line reactor;

• Fusing;

• PWM filter;

• MVM unit;

• Sharing reactors;

• MV3000e Controller.

The SFE bridge can be used to convert the a.c. supply to a d.c. voltage, but also has the capability to allow 

regeneration of energy back into the network, and as such is required for power generation applications 

(e.g. wind turbines).

The AEM network bridge provides a very clean voltage waveform, but the harmonic content will require 

filtering.

1.4.3 Machine Bridge

The machine bridge converts between a d.c. and an a.c. voltage of variable frequency and amplitude. 

Generally in a DFE system, the power flows from the d.c. link, out into the a.c. load. In an AEM system, power 

flow is bi-directional.

The machine bridge comprises of one to six DELTA transistor modules and the following ancillary 

components:

• Sharing reactors;

• Fusing;

• MV3000e Controller.

2.7.1 Electrical Connections

The connections from the SMPS unit to other equipment in the DELTA drive are as follows:

• One 40 way ribbon cable, supplied as part of the DELTA transistor module;

• A two pin connector plugs into the d.c. link of the associated DELTA transistor module. 

2.8 MV3000E DRIVE DATA MANAGERTM (KEYPAD)

Units covered: MVS3000-4001 (DDM)

 MVS3001-4001 (Installation kit)

The Drive Data ManagerTM, shown in Figure 2–6, is an ergonomically designed keypad which provides the 

functionality to configure a drive system. It also provides motor control and diagnostic functions.

The Drive Data ManagerTM derives its power supply from the MV3000e Controller

An installation kit containing a waterproof gasket and a lead is available separately. The lead for 

connection from the Keypad to the MV3000e controller has a maximum length of 3 m (9.8 ft.). This lead 

length determines the relative positions of the Drive Data ManagerTM and the controller. When supplied 

with a waterproof gasket, it can be mounted on an enclosure door to meet IP 65 enclosure protection.

The specification for the Drive Data ManagerTM and its electrical connections, are included in the T1915 

Instruction Sheet which is supplied with the Drive Data ManagerTM. 

2.9 DELTA RECTIFIER MODULE

Unit covered: MVRL2100-4601. 

MVRL2100-4602. 

In a DELTA drive system, rectifier modules shown in Figure 2–7, are used in network bridges to convert an 

a.c. supply into a rectified, unsmoothed d.c. supply. 

The rectifier module is available in a single rating. Larger rectifier power ratings can be achieved by 

connecting the modules in parallel (derating will be necessary, see Section 2.9.4.1: Parallel Ratings).

Each module has a pair of three-phase, six pulse rectifiers, with individual a.c. input terminals. Two d.c. 

positive terminals and a single d.c. negative output terminal are provided.

The rectifier module may be operated as a 12-pulse network bridge. This configuration is achieved by 

connecting the d.c. positive outputs together through an interbridge transformer and one a.c. input being 

phase-shifted in relation to the other by an external supply transformer.

AlstomEthernet Manual

Preface This document

The Ethernet Manual is the same for all ALSTOM Power Service controllers equipped with Ethernet. Therefore reference to specific controller names such as EPIC or EFFIC will not be used from this point, instead the general term “controller” will be used. This Ethernet Manual contains information for the Designing Engineers on the pre-commissioning of the Ethernet network. It also contains information for Shift Operators on the PC-MTU software, which is a software used for setting up, operating and monitoring an installation of several controllers in the network. The PC-MTU software is linked together with the web pages on the controllers built-in web server. These web pages are the interface used to configure each individual controller. For more information, see Operator’s & Installation Manual.

Related documents

The following documents are related to the Ethernet Manual:

• Ethernet Manual- (this document). 

• EPIC/EFFIC Operator’s & Installation Manual – contains information for all groups of users from the installation and commissioning to daily operation and tuning of the cleaning process. -Shift Supervisor Advanced operation and taking action on all alarms that may occur. -Process Engineer From small to medium scale diversions from factory settings in order to optimize the cleaning process. -Commissioning Engineer All stages of the commissioning. -Installation personnel (mechanical and electrical) Mechanical, electrical and communication installation.

• Ethernet Manual- (this document). • EPIC/EFFIC Operator’s & Installation Manual – contains information for all groups of users from the installation and commissioning to daily operation and tuning of the cleaning process. -Shift Supervisor Advanced operation and taking action on all alarms that may occur. -Process Engineer From small to medium scale diversions from factory settings in order to optimize the cleaning process. -Commissioning Engineer All stages of the commissioning. -Installation personnel (mechanical and electrical) Mechanical, electrical and communication installation.

Ethernet standard

Ethernet is a network standard of communication. The most widely used for LAN communication, Ethernet typically runs at 100 megabytes per second. All new controllers developed by ALSTOM Power Service use the Ethernet standard for communication. The following chapter describes what type of equipment is needed to successfully set up a Ethernet

General information on Ethernet

For general information on Ethernet there is a lot of information available both on the Internet and in published books. A good place to start is one of the following websites:

• Cisco Internetworking Technology Overview for Ethernethttp://www.cisco.com/univercd/cc/td/doc/cisintwk/ito_doc/ethernet.htm 

• Howstuffworks http://computer.howstuffworks.com/ethernet.htm For specific information on Industrial Ethernet standards the Industrial Ethernet Planning and Installation Guide is recommended, can be down loaded from the following website: 

• Iaonawww.iaona.org

Typical Ethernet network

1.3. Ethernet switch

The Ethernet switch shall meet the following standards: • EMC immunity for industry EN 50082-2 or EN 61000-6-2 Alstom Power Service has successfully used the switches from HMS Industrial Networks, Sweden and different types of switches from Hirschman Electronics

1.4. Ethernet hub

Ethernet hub should not be used in a new installation, because it will decrease the performance of the network. With a hub in the network it is also more difficult to calculate the allowed cable lengths

1.5. Connection to controller

The Ethernet board connection on the controller is of the following type: • RJ45 10/100M/bit auto negotiation

1.6. Cables

Cat 5E FTP cables with RJ45 connectors are recommended for the Ethernet network.

1.7. Ethernet ports and protocols

The following Ethernet ports are used

• Port 20, 21 for FTP 

• Port 80 for HTTP 

• Port 502 for Modbus/TCP data 

• Port 3 250 for PC-MTU – IP config 

• Port 49 200, 49 201 for the master functionality and PC-MTU.

1.8. Ethernet routers

Routers should not be installed in the EPIC III Ethernet network. The PCMTU and master functionality will not function properly through it

Setup Ethernet network

The following chapter describes how to install the software and how to setup your Ethernet network. The installation procedure is the same for all ALSTOM Power Service controllers equipped with Ethernet. Therefore reference to specific controller names such as EPIC or EFFIC will not be used from this point, instead the general term “controller” will be used.

Software installation

  1. Insert the PC-MTU software CD into your CD-ROM drive. 2. Follow the installation instructions.

System requirements

• PC with 300 megahertz or higher processor clock speed recommended. 

• Intel Pentium/Celeron family, or AMD K6/Athlon/Duron family, or compatible processor recommended. 

• 128 megabytes (MB) of RAM or higher recommended. 

• Super VGA (1024 x 768) or higher-resolution video adapter and monitor. 

• CD-ROM or DVD drive. 

• Keyboard and Microsoft Mouse or compatible pointing device. 

• Microsoft Windows® 2000 or Microsoft Windows XP® 

• Microsoft Internet Explorer® 6.0 or higher.

2.3. Assigning IP address

The IP address is used to identify each controller on the Ethernet network. Therefore, each controller on the network must have a unique IP address.

2.3.1. The Ethernet board location

To manually assign an IP address to a controller its Ethernet boards dip switches are used. The location of the Ethernet board differs depending on product, see figure 2 below.

2.3.2. Ethernet LEDs

The Ethernet board has four LEDs carrying the following information:

2.3.3. Assigning the IP address to the controller There are many different ways to assign ip addresses, in this manual the three most common will be described in the three following sections. The Ethernet board has a default IP address setting of: IP address:192.168.0.X The X in the IP address can be set from 1 to 255 by the configuration switch on the ethernet board. The switch represents the binary value of the X value in the IP address. Example: The switches are set to 00010100 (20 decimal). The IP address will be set to 192.168.0.20

2.3.4. Using configuration switch 1. Make sure that the controller is switched Off. 2. Use the configuration switch to assign a unique ip number to the controller, a number not used by any other nodes in the network. 3. Switch On the controller. 4. Repeat step 1-3 with all the controllers in the network. 5. Now the IP address of the PC has to be set (the PC that is used for running the PC MTU software and browsing the web pages). 6. On the PC – click the START button and select Control Panel. 7. In Control Panel select Network and Dial-up connections and then Local Area Connection. 8. Select Properties and highlight Internet Protocol (TCP/IP) and select Properties. 9. Click the radio button Specify an IP Address. 10. In the IP address field assign a unique ip number not used by any other nodes in the network to the PC e.g. 192.168.0.100. The Subnet mask will normally be automatically filled in (255.255.255.0). Click OK and close all windows. 11. To complete the setup start the PC-MTU program. 12. From the menu Choose Advanced > Ip config.2.3.5. Using specific IP numbers

  1. To setup the controllers execute step 1-17 in section Using configuration switch on page 7. 2. Assign the specific IP number to each individual controller. 3. Assign the specific Subnet to each individual controller. 4. Assign the specific Gateway to each individual controller. 5. To save the information on the controller flashdisc click on Config nodes. 6. Switch Off all controllers. 7. Reset the configuration switch on all controllers, see figure to the right. 8. Switch On all controllers to start using the values stored in the memory. 9. Execute step 18-19 in section Using configuration switch on page 7.
  2. 2.3.6. Using DHCP 1. To setup the controllers execute step 1-17 in section Using configuration switch on page 7. 2. Mark the checkbox DHCP on all the controllers 3. To save the information on the controller flashdisc click on Config nodes. 4. Switch Off all controllers. 5. Reset the configuration switch on all controllers 6. Switch On all controllers to start using the values stored in the memory. 7. Execute step 18-19 in section Using configuration switch on page 7.

Allied TelesisLayer 2 Ethernet Switch

This guide contains the hardware installation instructions for the AT-8000S/16, AT-8000S/24, AT-8000S/24POE, AT-8000S/48 and AT-8000S/48POE Fast Ethernet Switches.

How This Guide is Organized

This manual contains the following chapters

• Chapter 1 Product Description describes the features and components of the switches. 

• Chapter 2 Installation describes the installation instructions for the switches. 

• Chapter 3 Stacking describes the stacking instructions for the switches. 

• Chapter 4 Initial Configuration describes the instructions for initially configuring the switches. 

• Chapter 5 Troubleshooting provides information on how to resolve problems that might occur with the switches. 

• Appendix A Technical Specifications contain the technical specifications for the switches. 

• Appendix B Translated Safety Standards contain the safety standards for the device.

Document Conventions

This document uses the following conventions to highlight important information:

Contacting Allied Telesis This section provides Allied Telesis contact information for technical support as well as sales or corporate information.

Online Support

You can request technical support online by accessing the Allied Telesis Knowledge Base from the following web site: www.alliedtelesis.com/kb. You can use the Knowledge Base to submit questions to our technical support staff and review answers to previously asked questions.

Email and Telephone Support

For Technical Support via email or telephone, refer to the Allied Telesis web site: www.alliedtelesis.com. Select your country from the list displayed on the website. Then select the appropriate menu tab..

Returning Products

Products for return or repair must first be assigned a Return Materials Authorization (RMA) number. A product sent to Allied Telesis without a RMA number will be returned to the sender at the sender’s expense. To obtain an RMA number, contact the Allied Telesis Technical Support group at our web site: www.alliedtelesis.com/support/rma. Select your country from the list displayed on the website. Then select the appropriate menu tab..

For Sales or Corporate Information

You can contact Allied Telesis for sales or corporate information at our web site: www.alliedtelesyn.com. Select your country from the list displayed on the website. Then select the appropriate menu tab..

Warranty

The AT-8000S has a limited warranty of lifetime (two years PSU and fan). Go to www.alliedtelesis.com/warranty for the specific terms and conditions of the warranty and for warranty registration.

The new AT-8000S series combines the best of the previous L2 series; stackability and affordability. The new AT-8000S series is an entry level managed switch for the SMB, Small Office/Field Office offering managed desktop connectivity. The fiber uplink provides connectivity between workgroups over a larger distances. In addition the AT-8000S series is also equipped with a copper 10/100/1000Base-T port for connectivity to gigabit aggregation switches

The new AT-8000S series combines value with the necessary management features for networked applications. There are five device models which provide different hardware configurations and include the following:

• AT-8000S/16 device which supports 16 built-in 10/100Base-T ports, and a Combo port functionality that supports both copper and SFP interfaces. • AT-8000S/24 device with stacking ports which supports 24 built-in 10/100Base-T ports, two Gigabit stackable and 2 Combo Ports, inclusive of a Combo port functionality that supports both copper and SFP interface. • AT-8000S/24POE device with stacking port which supports 24 built-in 10/100Base-T ports, two Gigabit stackable and 2 Combo Ports, inclusive of a Combo port that supports both copper and SFP interface. The PoE function is supported on RJ-45 ports. • AT-8000S/48 device with stacking ports which supports 48 built-in 10/100Base-T ports, two Gigabit stackable and 2 Combo Ports, inclusive of a Combo port functionality that supports both copper and SFP interface. • AT-8000S/48POE device with stacking port which supports 48 built-in 10/100Base-T ports, two Gigabit stackable and 2 Combo Ports, inclusive of a Combo port that supports both copper and SFP interface. The PoE function is supported on RJ-45 ports

The AT-8000S/24, AT-8000S/24POE, AT-8000S/48 and AT-8000S/48POE can be joined together into a stack of up to six units. For more information, see Chapter 3 Stacking. Device configuration is performed through an Embedded Web Server (EWS) or through a Command Line Interface (CLI). The device management is performed through a DB-9 RS-232 interface.

Features The AT-8000S/16, AT-8000S/24, AT-8000S/24POE, AT-8000S/48 and AT-8000S/48POE features include the following:

• Wirespeed switching traffic across all ports 

• Auto MDI/MDIX enabled 

• 802.1d, 1w, 1s priority tags supported 

• Broadcast storm control 

• IEEE 802.1Q tagged VLANs supported • GARP/GVRP supported 

• Port/MAC based VLANs supported • 802.3ad link aggregation Static and Dynamic (LACP) supported 

• IEEE 802.1P based QoS supported 

• Ingress rate limiting 

• Egress rate shaping (WRR) 

• 802.1x port/MAC based authentication support 

• RFC 2618 RADIUS Authentication • SSL/ SSLv3 

• RFC 1492 TACACS+ • Management ACL support 

• Industry standard CLI 

• Browser based management interface (HTTP) 

• Telnet access supported 

• SNMP v1, v2 and v3 

• RFC1757 RMON support 

• Port Mirroring support 

• PVE • Port Security 

• DHCP support 

• Static IP Multicast support 

• IGMP Snooping

IEEE Standards

– IEEE 802.3 

— 10Base-T 

– IEEE 802.3u 

— 100Base-TX 

– IEEE 802.3ab 

— 1000Base-TX Gigabit Ethernet 

– IEEE 802.3z 

— Full Duplex 

– IEEE 802.3u 

— Auto-Negotiation

– IEEE 802.3x 

— Flow Control, Symmetric and Asymmetric

The AT-8000S/16 front panel is configured as follows:

• 16 10/100Mbps Ports — RJ-45 ports designated as 10/100Base-T. The RJ-45 ports are designated as ports Ports 1 – 16. 

• 1 10/100/1000Base-T Copper Port — There is one copper 10/100/100Base-T port designated on the switch as port 17R. This port is paired with the SFP slot designated on the switch as port 17. Together these two ports form the Combo ports shown in Figure 1. 

• 1 SFP Port — There is one SFP slot supports either a 100Base-FX or a 1000Base-X (fiber) connection and is designated on the switch as port 17. This SFP slot is paired with the 10/100/1000Base-T copper port which is designated on the switch as port 17R. Together these two ports form the Combo ports shown in Figure 1. 

• DB-9 Console port — An asynchronous serial console port supporting the RS-232 electrical specification. The port is used to connect the device to the console managing the device. 

• Reset Button — Button to reset the device. 

• Mode Button — Selects the port LED indications.

AT-8000S/24 Front Panel

The AT-8000S/24 front panel is configured as follows:

• 24 10/100Mbps Ports — RJ-45 ports designated as 10/100Base-T. The RJ-45 ports are designated as ports Ports 1 – 24. 

• 2 10/100/1000Base-T Copper Ports — There are two copper 10/100/100Base-T ports designated on the switch as ports 25R and 26R. These ports are paired with the two SFP slots designated on the switch as ports 25 and 26. Together these four ports form the Combo ports shown in Figure 3.. 

• 2 SFP Ports— There are two SFP slots which support either a 100Base-FX or a 1000Base-X (fiber) connection and are designated on the switch as ports 25 and 26. This SFP slot is paired with the two 10/100/ 1000Base-T copper ports which is designated on the switch as port 25R and 26R. Together these four ports form the Combo ports shown in Figure 3. 

• DB-9 Console port — An asynchronous serial console port supporting the RS-232 electrical specification. The port is used to connect the device to the console managing the device. 

• Reset Button — Button to reset the device. 

• Mode Button — Selects the port LED indications.

AT-8000S/24POE Front Panel

The AT-8000S/24POE front panel is configured as follows:

• 24 10/100Mbps Ports — RJ-45 ports designated as 10/100Base-T. The RJ-45 ports are designated as ports Ports 1 – 24. 

• 2 10/100/1000Base-T Copper Ports — There are two copper 10/100/100Base-T ports designated on the switch as ports 25R and 26R. These ports are paired with the two SFP slots designated on the switch as ports 25 and 26. Together these four ports form the Combo ports shown in Figure 5.. 

• 2 SFP Ports— There are two SFP slots which support either a 100Base-FX or a 1000Base-X (fiber) connection and are designated on the switch as ports 25 and 26. This SFP slot is paired with the two 10/100/ 1000Base-T copper ports which is designated on the switch as port 25R and 26R. Together these four ports form the Combo ports shown in Figure 5. 

• DB-9 Console port — An asynchronous serial console port supporting the RS-232 electrical specification. The port is used to connect the device to the console managing the device. 

• Reset Button — Button to reset the device.

The AT-8000S/48 device front panel is configured as follows: 

• 48 10/100Mbps Ports — RJ-45 ports designated as 10/100Base-T. The RJ-45 ports are designated as ports Ports 1 – 48. 

• 2 10/100/1000Base-T Copper Ports — There are two copper 10/100/100Base-T ports designated on the switch as ports 49R and 50R. These ports are paired with the two SFP slots designated on the switch as ports 49 and 50. Together these four ports form the Combo ports shown in Figure 7.. 

• 2 SFP Ports — There are two SFP slots which support either a 100Base-FX or a 1000Base-X (fiber) connection and are designated on the switch as ports 49 and 50. This SFP slot is paired with the two 10/100/ 1000Base-T copper ports which is designated on the switch as port 49R and 50R. Together these four ports form the Combo ports shown in Figure 7. 

• Mode Button — Selects the port LED indications.

The AT-8000S/48 device front panel is configured as follows: 

• 48 10/100Mbps Ports — RJ-45 ports designated as 10/100Base-T. The RJ-45 ports are designated as ports Ports 1 – 48. 

• 2 10/100/1000Base-T Copper Ports — There are two copper 10/100/100Base-T ports designated on the switch as ports 49R and 50R. These ports are paired with the two SFP slots designated on the switch as ports 49 and 50. Together these four ports form the Combo ports shown in Figure 7.. 

• 2 SFP Ports — There are two SFP slots which support either a 100Base-FX or a 1000Base-X (fiber) connection and are designated on the switch as ports 49 and 50. This SFP slot is paired with the two 10/100/ 1000Base-T copper ports which is designated on the switch as port 49R and 50R. Together these four ports form the Combo ports shown in Figure 7. 

• Mode Button — Selects the port LED indications.

This section contains information for installing the device, and includes the following sections:

• Preparing for Installation

• Installing the Device 

• Connecting the Device 

• Rack Installation

Preparing for Installation

This section provides an explanation for preparing the installation site, and includes the following topics:

• Preparing for Installation 

• Site Requirements 

• Unpacking

Package Contents While unpacking the device, ensure that the following items are included: 

• One AT- 8000S/xx series unit 

• Rubber Feet for desktop installation 

• Rack-mount kit hardware accessories 

• An AC power cable 

• Stacking cable (Yellow color) 

• Console RS-232 cable with DB-9 connector 

• Installation guide on CD 

• Warranty and registration card

To unpack the device perform the following: 1. It is recommended to put on an ESD wrist strap and attach the ESD clip to a metal surface to act as ground. An ESD strap is not supplied with the device. 2. Place the container on a clean flat surface and cut all straps securing the container. 3. Open the container. 4. Carefully remove the device from the container and place it on a secure and clean surface. 5. Remove all packing material. 6. Inspect the product for damage. Report any damage immediately. If any item is found missing or damaged, please contact your local ATI reseller for a replacement.

Installing the Device

The device can be installed on a flat surface or mounted in a rack. This section includes the following topics:

• Desktop or Shelf Installation 

• Rack Installation

Desktop or Shelf Installation

When installing the switch on a desktop or shelf, the rubber feet included with the device should first be attached. Attach these cushioning feet on the bottom at each corner of the device. Ensure the surface is be able to support the weight of the device and the device cables. To install the device on a surface, perform the following: 1. Attach the rubber feet on the bottom of the device. The following figure illustrates the rubber feet installation on the device.

AEROTECHNdrive HP 10/20/30 USER’S MANUAL

General notes concerning the test setup

This product was tested at F-Squared Laboratories, in Burton, OH on April 16-18, 2002. The report numbers are NY011602-01-01E and NY011602-01-02E. The Ndrive HP was tested while powered from a 230VAC source with a brushless servomotor, connected via PMC-15 and BFC-15 (15 foot) cables. In order for the product to conform to the radiated emission standards, the motor cable must be shielded and the shield must be connected to the earth ground. A metal D-style connector with a metal backshell must be used when connecting to the D-style connectors on the Ndrive HP. The shield of the feedback cable must be connected to the metal backshell.

The following modifications ensure compliance:

• Install a snap-on Ferrishield ferrite attenuator, P/N SS28B2034, on the FireWire cable at the unit. 

• Install a Curtis, P/N F1600CA-10, EMI line filter on the AC input. 

• Install two snap-on Ferrishield ferrite attenuators, P/N SS28B2032 and CS28B1984, on the AC cable between the EMI line filter and the Ndrive. 

• Connect earth ground to the mounting screw at the AC input. 

• Install a SCI, 25-pin, D-style, Spectrum EMI filter adapter, P/N SCI-56-725-001, in series with the motor feedback cable at the unit. Current generation units (Revision A) have integral filtering built-in, which should preclude the use of this EMI filter, based upon similar product testing.

Safety related requirements to ensure compliance (exceptions to EN 61010-1):

• The Ndrive must be installed within an enclosure with construction compliant unlimited circuits. 

• The end user is responsible for meeting the final protective ground requirements. • The AC power inlet located on the front of the Ndrive is the power disconnect. The end user is responsible for determining and providing a supply disconnect for the system. 

• The end user is responsible for preventing unexpected startup. 

• Connection requirements are described in the technical documentation provided with the product. The end user is responsible for making the proper connections and meeting any required interlock requirements for the product application. 

• Voltages greater than 60V may be present inside the Ndrive after a discharge time of 5 seconds. 

• The end user must provide protection for power interruption / restoration, if required. 

• The end user must provide earth fault current protection, if required. • The end user must provide protection against lightning and power switching surges, if required. 

• Control and Emergency Stop requirements are to be determined and provided by the end user. 

• Wire and cabling provided with the Ndrive meet Aerotechís electrical and listed environmental requirements. The end user must meet the final requirements.

CHAPTER 1: INTRODUCTION

Aerotechís Network Digital Drives (Ndrive HP) complement the Automation 3200 System (see Figure 1-1). Connected via the IEEE-1394 (FireWireÆ) communication bus, these drives provide deterministic behavior, auto-identification, and easy software setup from the Nmotion SMC software controller. Featuring a high-speed Harvard architecture DSP, the drives have fully digital current and servo loops providing selectable 1-20 kHz servo loop closure, 40 MHz line driver encoder data rate, and an optional Ethernet port for access to third party networked I/O solutions. The Ndrive HP also features an optional on-board brake relay, programmable resolution multiplication up to x 65,536, with a 200 kHz maximum amplified sine wave input frequency, and up to three-axis Position Synchronized Outputs (laser firing). In addition, the use of the commercially standard FireWire communication link makes integration to the Automation 3200 network plug-n-play easy

1.1. Feature Summary

• Software configurable for brush, brushless and stepper motor operation 

• Standard 100 VDC ñ 320 VDC Bus, optional 20 VDC ñ 80 VDC Bus, requires the -AUXPWR option 

• Fully isolated power stage 

• 5 VDC, 500 mA fused user output power for encoder and Hall effect signals, etc. 

• Two mounting orientations optimized for heat transfer or minimal panel space utilization 

• Full protection against the following failure modes:

  1. Control supply under voltage2. Continuous current overload3. Power stage bias supply under-voltage4. Power stage output short circuit (phase to phase and phase to ground)5. DC bus over voltage6. IGBT device over temperature sense• Line driver square wave or analog sine wave quadrature encoder primary position and velocity feedback• Line driver square wave auxiliary quadrature encoder input or output for PSO (laser firing), etc.• 4 opto-isolated user outputs standard• 6 opto-isolated user inputs standard, 2 of which are high speed• 2 differential analog inputs (one standard and one available with the ñIOPSO option)• 2 analog outputs (one standard and one available with the ñIOPSO option)

1.2. Connection Overview

The Ndrive HP consists of two power connections (motor power and input power), three FireWire ports, an optional Ethernet connection, an RS-232/RS-422 connector, LED indicator lamps and two D-Style connectors for Auxiliary I/O (15 and 26 pin) and Motor Feedback (25 pin). An ñIOPSO or -IOPSOH option is also available, which has connectors for PSO, absolute encoder, SSI Net, analog I/O, digital I/O, and user power. Refer to Figure 1-2 for connector locations.

1.3. Functional Diagram

The standard package includes the bus power supply that operates from 85-250 VAC (120 ñ 350 VDC). The power supply is included with the standard package for off-line operation without the need for an isolation transformer. A soft start circuit is included to prevent high inrush currents.

1.4. Ordering Information

The Ndrive HP is available in three models with continuous power, ranging from 1,360 to 4,080 watts. A list of these models, and the available voltage configurations, are shown in Table 1-1. See Table 1-2 for a list of available accessories.

1.5. Specifications 1.5.1. Electrical Specifications

1.5.2. Mechanical Specifications The outline dimensions for the Ndrive HP are shown in Figure 1-4 and Figure 1-5. Units should be separated from each other and surrounded by one inch of free air space. This will also allow the standard 228 mm (9 inch) FireWire cable to interconnect them.

1.5.3. Environmental Specifications

The environmental specifications for the Ndrive HP are listed below.

• Temperature: Ambient Operating – 5° – 40°C (41° – 104°F) Storage – -20 – 70°C (-4 – 158°F) 

• Humidity: Maximum relative humidity is 80% for temperatures up to 31°C. Decreasing linearly to 50% relative humidity at 40°C. Non-condensing. 

• Altitude Up to 2000 m. 

• Pollution Pollution degree 2 (normally only non-conductive pollution). 

• Use Indoor use only

CHAPTER 2: INSTALLATION and CONFIGURATION

This section covers the hardware configurations using the switches, jumpers, connectors, and power connections when used with a brush, brushless, or stepper motor. Wiring, grounding, shielding techniques, and the motor phasing process are also covered. Aside from the obvious requirements of AC input and motor wiring, the only other typical requirement is to set the Ndrive HPs communication channel number via switch S2.

Safety Procedures and Warnings

The following statements apply wherever the Warning or Danger symbol appears within this manual. Failure to observe these precautions could result in serious injury to those performing the procedures and/or damage to the equipment.

2.2. Wiring, Grounding, and Shielding Techniques

To reduce electrical noise in the Ndrive, the user should observe the motor and input power wiring techniques explained in the following sections (suitable for use on a circuit capable of delivering not more than 5,000A, 240V).

2.2.1. Minimizing EMI Interference

The Ndrive HPs are high efficiency PWM amplifiers operating at a 20 kHz switching rate. This switching rate can generate Electromagnetic Interference (EMI) into the MHz band. To minimize this EMI, it is recommended that the motor leads be twisted together with the motor cable grounding wire and surrounded with a foil or braided shield. In addition to the EMI effects, electro-static (capacitive) coupling to the motor frame is very high, requiring the frame to be grounded in order to eliminate a shock hazard. Additional electro-static coupling exists between the three twisted motor leads and the foil shield of the motor cable. This coupling forces high frequency currents to flow through the returning earth ground of the motor cable. To minimize this problem and maintain low levels of EMI radiation, perform the following.

  1. Use shielded cable to carry the motor current and connect the shield to earth ground.2. Use a cable with sufficient insulation. This will reduce the capacitive coupling between the leads that, in turn, reduces the current generated in the shield wire.3. Provide strong earth ground connections to the amplifier, additional heat sink, and the motor. Offering electrical noise a low impedance path to earth ground not only reduces radiated emissions, but also improves system performance.4. If possible, do not route motor cables near cables carrying logic signals and use shielded cable to carry logic signals.5. Ferrite beads or Aerotechís FBF-1 or FBF-2 filter adapters, may be used on the motor leads to reduce the effects of amplifier EMI/RFI, produced by PWM (pulse width modulation) amplifiers. Refer to the FBF-1 and FBF-2 drawings on your software or documentation CD ROM for more information on the ferrite beads.

2.2.2. Minimizing 50/60 HZ Line Interference

Operating the Ndrive HP from an off-line source of 115 VAC or 230 VAC may create some additional issues. There is a potential problem of EMI generated from the switching power stage of the Ndrive propagating through the bridge rectifier and out through the AC1 and AC2 input AC line connections. Back-propagation of noise into the AC lines can be minimized using a line filter (refer to Figure 2-1)

Figure 2-1. Back-Propagation Line Filter Connection

Second, a potential problem that exists with off line connections is 50/60 Hz electrostatic coupling between the frame of the AC motor and the AC1/AC2 AC input power. Since AC1 is referenced to earth ground at the source, the DC bus of the amplifier ìswingsî at 50/60 Hz with respect to the motor frame. The path of current caused by this coupling between the motor frame and the amplifier stage passes through the current feedback sensing devices of the amplifier. Depending on the magnitude of this current, a 50/60 Hz disturbance may be visible in the position error. To eliminate this problem, an isolation transformer can be used to block the 50/60 Hz from being seen by the motor frame (refer to Figure 2-2).

2.3. Power Connections

The Ndrive HP may powered by one or two separate AC voltages. One for motor bus power and optionally a second for control power, as described in the following two subsections. If the optional control power input is present, it must be powered.

2.3.1. Control Power Connections (TB101)

The -AUXPWR option allows the Ndrive HP to remain operational when the motor power is removed, such as when an external emergency stop circuit is required. If the Ndrive HP was purchased with the -AUXPWR option, a separate AC input (TB101) has been included on the amplifier. The internal power supply of the Ndrive HP requires a minimum of 85 VAC input to operate properly. The figure below shows the connection to the separate AC power board. The connection is made to the AC input board with a three terminal connector (Aerotech Part #ECK00213), provided. See Section 2.4. for various typical AC wiring options. TB101 is also typically utilized when an emergency stop circuit is present. See Section 2.10 for a typical ESTOP sense input wiring configuration.

The AUXPWR input is an option that, if present, must be powered. It is typically used when the AC bus input power is less than 85 VAC at TB102 AC1, AC2 (or AC3). TB101 is also typically utilized when an emergency stop circuit is present. Optional Supply Connections to AL1, AL2 and the Protective Ground should be at least 1.02362 mm (#18 AWG) wire rated @ 300 V (3 Amp external fusing may be required for AL2, AL1 is fused internally at 3 Amps).

2.3.2. Motor Power Connections (TB102)

The three-phase motor terminal connections are made at connections A, B, and C. Motor Connections ØA, ØB, ØC and its Protective Ground should be made with 1.62814 mm (#14 AWG) wire rated at 300 V. Motor frame and shield connect to (ground). Input power to the Ndrive is made at the AC1 and AC2 terminals with earth ground connected to (ground). A three-phase power input is also available (AC3, requires 3 Phase Option). Connections at AC1, AC2 and AC3 and its Protective Ground should be made with 1.62814 mm (#14 AWG) wire rated at 300V

2.3.3. 40/80 VDC Power Transformers The TV0.3-56 power transformer is an optional accessory for the Ndrive HP. The transformer allows the generation of 56 VAC from a 115 VAC and 230 VAC source respectively. When rectified by the Ndrive HP, 56 VAC yields an 80 VDC power bus. The TV0.3-28 power transformer is an optional accessory available for the Ndrive HP. This transformer allows for the generation of 28 VAC from a 115 VAC or 230 VAC source, respectively. When rectified by the Ndrive, 28 VAC yields a 40 VDC power bus. The following three figures illustrate the six combinations available for both AC input voltages and all three DC bus voltages, as well as the use of the -AUXPWR option. A TM3 and TM5 transformer package is also available to power up to four Ndrives, providing 300 or 500 watts of power.

APPENDIX B: WARRANTY and FIELD SERVICE

Aerotech, Inc. warrants its products to be free from defects caused by faulty materials or poor workmanship for a minimum period of one year from date of shipment from Aerotech. Aerotech’s liability is limited to replacing, repairing or issuing credit, at its option, for any products that are returned by the original purchaser during the warranty period. Aerotech makes no warranty that its products are fit for the use or purpose to which they may be put by the buyer, where or not such use or purpose has been disclosed to Aerotech in specifications or drawings previously or subsequently provided, or whether or not Aerotech’s products are specifically designed and/or manufactured for buyer’s use or purpose. Aerotech’s liability or any claim for loss or damage arising out of the sale, resale or use of any of its products shall in no event exceed the selling price of the unit. Aerotech, Inc. warrants its laser products to the original purchaser for a minimum period of one year from date of shipment. This warranty covers defects in workmanship and material and is voided for all laser power supplies, plasma tubes and laser systems subject to electrical or physical abuse, tampering (such as opening the housing or removal of the serial tag) or improper operation as determined by Aerotech. This warranty is also voided for failure to comply with Aerotech’s return procedures. Laser Products Claims for shipment damage (evident or concealed) must be filed with the carrier by the buyer. Aerotech must be notified within (30) days of shipment of incorrect materials. No product may be returned, whether in warranty or out of warranty, without first obtaining approval from Aerotech. No credit will be given nor repairs made for products returned without such approval. Any returned product(s) must be accompanied by a return authorization number. The return authorization number may be obtained by calling an Aerotech service center. Products must be returned, prepaid, to an Aerotech service center (no C.O.D. or Collect Freight accepted). The status of any product returned later than (30) days after the issuance of a return authorization number will be subject to review. Return Procedure After Aerotech’s examination, warranty or out-of-warranty status will be determined. If upon Aerotech’s examination a warranted defect exists, then the product(s) will be repaired at no charge and shipped, prepaid, back to the buyer. If the buyer desires an airfreight return, the product(s) will be shipped collect. Warranty repairs do not extend the original warranty period. Returned Product Warranty Determination After Aerotech’s examination, the buyer shall be notified of the repair cost. At such time, the buyer must issue a valid purchase order to cover the cost of the repair and freight, or authorize the product(s) to be shipped back as is, at the buyer’s expense. Failure to obtain a purchase order number or approval within (30) days of notification will result in the product(s) being returned as is, at the buyer’s expense. Repair work is warranted for (90) days from date of shipment. Replacement components are warranted for one year from date of shipment. Returned Product Non-warranty Determination At times, the buyer may desire to expedite a repair. Regardless of warranty or out-ofwarranty status, the buyer must issue a valid purchase order to cover the added rush service cost. Rush service is subject to Aerotech’s approval.

On-site Warranty Repair

If an Aerotech product cannot be made functional by telephone assistance or by sending and having the customer install replacement parts, and cannot be returned to the Aerotech service center for repair, and if Aerotech determines the problem could be warranty-related, then the following policy applies: Aerotech will provide an on-site field service representative in a reasonable amount of time, provided that the customer issues a valid purchase order to Aerotech covering all transportation and subsistence costs. For warranty field repairs, the customer will not be charged for the cost of labor and material. If service is rendered at times other than normal work periods, then special service rates apply. If during the on-site repair it is determined the problem is not warranty related, then the terms and conditions stated in the following “On-Site Non-Warranty Repair” section apply.

On-site Nonwarranty Repair

If any Aerotech product cannot be made functional by telephone assistance or purchased replacement parts, and cannot be returned to the Aerotech service center for repair, then the following field service policy applies: Aerotech will provide an on-site field service representative in a reasonable amount of time, provided that the customer issues a valid purchase order to Aerotech covering all transportation and subsistence costs and the prevailing labor cost, including travel time, necessary to complete the repair.

ABBCommunication GatewayProduct Guide

Features 

• Protocol conversion gateway for substation automation: 

– Process communication: LON-LAG, SPA, IEC 60870-5-103, IEC 61850-8-1, Modbus serial, Modbus TCP, DNP3 serial, DNP3 TCP – Remote communication: IEC 60870-5- 101, IEC 60870-5-104, DNP 3.0 Serial, DNP 3.0 LAN/WAN, SPA Router, External OPC Client (DA, AE) • True IEC 61850 communication gateway: 

– IEC 61850-6 

– Substation Configuration Language (SCL) – IEC 61850 -7 

– Communication modeling and cross-referencing between protocols – IEC 61850-8-1 – Mapping for MMSTCP/IP – Ethernet 

• Configuration: – Efficient and intuitive configuration tool – Cross-referencing between protocols based on the IEC61850-7 models – Drag-and-drop protocol mapping to map complete structures from the source data – Efficient handling of large amounts of data in list views – Tooltips – Remote configuration and administration 

• Communication redundancy (requires optional LAN card) – IEC 62439/PRP (parallel redundance protocol) – SFT (switch fault tolerance) 

• Extensive support for commissioning and diagnostics: – Online diagnostics for different components – Communication diagnostic counters on the network and device level – Real time process data monitoring and controlling for all devices and protocols – Source data monitoring and simulation: – Testing the data mapping for NCCs also with no online IEDs – Simulating complete IEDs – Communication diagnostic event list for all devices and protocols: – Resembles a high level protocol analyser – Monitors the reported values and events and the received control commands 

• Web server for diagnostic information: – Requires only a web browser and a TCP/IP connection – no pre-installations 

• MNS iS connectivity – Connectivity to ABB’s Low Voltage Motor Control Center MNS iS with an OPC server in COM600. COM600 receives data from the MNS iS devies and provides HMI and gateway functionality 

• Security: – User authentication – Individual user accounts – Password authentication – Role-based access control – Host-based firewalls – Communication encryption HTTPS

Application COM610 3.2 is a communication gateway that maps signals between the protection and control IEDs in industrial or utility substations and higher-level systems such as Network Control Centres (NCC) or Distributed Control Systems (DCS). COM610 3.2 sends information for monitoring and controlling the process to NCC and DCS and receives process control commands from them. COM610 3.2 also handles system co-ordination tasks, such as the dynamic assignment of control command authorisation and communication supervision. COM610 3.2 is typically connected to a NCC via a telecontrol protocol, or to a DCS using the OPC Server/Client technology. You can use different protocols to connect process devices to COM610 3.2. COM610 3.2 is a true IEC 61850 gateway and supports all applicable IEC 61850 parts. Fig. 1 displays an overview of a typical utility system with the COM610 Gateway. Fig. 2 displays an industrial system overview.

Application (cont´d) 5 The LON-LAG protocol uses a specific board to connect the fibres, both plastic and glass. COM610 3.2 can have one board, that is, one LON line. It is possible to extend COM610 3.2 by increasing the number of Ethernet interfaces thus increasing the number of Ethernets lines. Connectivity Packages To make the configuration of COM610 3.2 more efficient, Connectivity Packages are available for ABB’s protection and control IEDs. A Connectivity Package includes descriptions of data and signals available in the IED, and the descriptions are used to automatically configure the master communication in the COM610 3.2 gateway. Connectivity Packages for some IEDs are already available, and more will be released in due couse. At present the following Connectivity Packages are available: – REF 541/3/5, REM 543/5, RET 541/3/5 – REF 542plus – REX 521 – RE_610 – SPACOM (Conn Pack v. 2.0 supports SPAJ 140, SPAJ 141, SPAJ 142, SPAJ 144, SPAD 346, SACO 16D1, SACO 16D2, SACO 64D4) COM610 gateway unit’s configurability and functionality depends on the type of communication protocol used for communication between the COM610 and the IEDs. For more details, please refer to the document “Protocols versus Functions for IEDs”, 1MRS756223

The COM610 gateway consists of the OPC Data Access (DA, AE) server and client components. The OPC Servers provide the master/client protocol stacks access to the data in the devices connected with the protocol. The slave/server protocol stacks use the OPC Clients to provide the external systems access to the data available in the OPC Servers.


Available protocols The table below displays the protocols supported by COM610 Gateway. New protocols will be available according to the market demands. The process communication uses the master protocols and the upper level communication uses the slave protocols. For more detailed information on the protocols, refer to the User’s guides listed in References.

System requirements for the Communication Engineering Tool Hardware requirements The Communication Engineering Tool runs on Microsoft® Windows® XP. A PC capable of running this program is usually sufficient also for running the Communication Engineering Tool. Microsoft® .NET Framework 2.0 is required for running the Communication Engineering Tool. It is automatically installed during the installation of the Communication Engineering Tool if it is not already available on the PC. • Free hard disk space required: minimum 500 MB, recommended 1 GB. Technical data Hardware Design • Ruggedised mechanics – No moving parts – no fans, no hard disks • System – Intel® Pentium® M 1.6 GHz – 1 GB SDRAM System Memory – 2 GB Industrial SSD Compact Flash memory • Power supply units: – 76-240 V dc • Interfaces – 3 RS 232 serial ports – 1 RS 232/485 serial port – 2 10/100Base-TX RJ-45 connector – 4 USB 2.0 ports – Optional PCI extensions: – 1 LON interface (Operating temperature 0°C – +70°C) – 8 RS232/485 serial interfaces (Operating temperature 0°C – +55°C) – 2 10/100/1000Base-TX RJ-45 connectors (Operating temperature 0°C – +60°C) • Mechanics and Environment: – Operation -25°C to +70°C – Storage -40°C to +70°C – Dimensions (without fastening brackets): 214 mm (W) x 122.5 mm (H) x 313 mm (D) – Net weight: 6.8 kg – Degree of protection: IP 4x – Operating humidity: 5-95% at +40°C, non-condensing – EMC CE/FCC class B – Anti-vibration and anti-shock tests.

When ordering COM610 3.2, use Fig. 5 to generate the correct ordering code. The ordering code specifies the HW and the SW. If you need an additional PCI card, specify it by selecting the corresponding letter. The standard delivery of a COM610 3.2 includes one communication protocol for the process devices and one communication protocol for a higher-level system. Fig. 5 COM610 ordering code Also specify in the ordering code: – if you need to gather data from a substation using two or three different protocols. – if you need to send data from COM610 using two different protocols. You do not need to specify the protocols in the order. The protocols needed are selected when the COM610 unit is configured. COM610 3.2 is limited only by the number of the slaves and masters ordered. When ordering please state language, simplified Chinese, Russian or Spanish, if not English which is the default language. For more information about ordering and availability, please contact ABB Oy, Distribution Automation. References The product documentation is included on the Communication Engineering Tool CD-ROM. You can also download the latest documents from the www.abb.com/substationautomation.pe tests    .    1:;   :.    &  &:    ;   6     1:;   :6     .    1:;   :.    !  !:    ;   , <  1:;   &:/<&676&4/4 :6<=340 >:#6133>  :#6133    ;; ?:@-3641    ; ’!-.1 COM600 3.2, User’s Guide 1MRS756125 COM605 3.2, Operator’s Guide 1MRS756121 COM610 3.2, Operator’s Guide 1MRS756122 COM615 3.2, Operator’s Guide 1MRS756123 COM605, 615 3.2 HMI Configuration Manual 1MRS756124 LON-LAG Master (OPC) 3.2 1MRS755284 SPA Master (OPC) 3.2 1MRS752275 SPA Router (OPC) 3.2 1MRS755497 Modbus Serial Master (OPC) 3.2 1MRS756126 Modbus TCP Master (OPC) 3.2 1MRS756445 IEC 60870-5-103 Master (OPC) 3.2 1MRS752278 IEC 61850 Master (OPC) 3.2 1MRS755321 External OPC Client Access 3.2 1MRS755564 IEC 60870-5-101 Slave (OPC) 3.2 1MRS755382

ABBACS1000 air-cooled

— ACS1000 air-cooled The flexibility you require. The reliability you expect. Document name ACS1000 air-cooled user manual Document owner ABB Switzerland Ltd. Medium voltage AC drives Document number 3BHS213401 E01 Rev H Number of pages 184 Release date 2020-03-18 — new.abb.com/drives/medium-voltage-ac-drives

1.1 Copyright notice The information in this manual is subject to change without notice. This manual and parts thereof must not be reproduced or copied, or disclosed to third parties, nor used for any unauthorized purpose without written permission from ABB Switzerland Ltd., Medium Voltage Drives. The hardware and software described in this manual is provided under a license and may be used, copied, or disclosed only in accordance with the terms of such license. 

1.2 Equipment covered by this manual This manual covers a standard drive and provides generic information on the drive. The manual does not claim to cover all variations and details of the drive, nor to consider all eventualities that may arise during installation, commissioning, operation and maintenance of the drive. If the drive is adapted to specific customer needs or applications, and handling, installation and operation of the drive are affected by these modifications, information on these modifications is provided in the appropriate documentation (eg, layout drawings, wiring diagrams, technical data, engineering notes). If information is required beyond the instructions in this manual, refer the matter to ABB. 

1.3 Structure of the user documentation The complete set of user documentation of a standard drive consists of this manual and supplementary documentation that is provided in the following appendices: – Appendix A – Additional manuals Appendix A provides manuals about additional equipment delivered with the drive (such as project-specific options such as pulse encoder or fieldbus interfaces), or information on modifications of the standard drive. – Appendix B – Technical data Appendix B contains the technical data sheets of the drive. – Appendix C – Mechanical drawings Appendix C provides the outline drawings of the drive. The drawings are generated according to the customer-specific project. – Appendix D – Wiring diagrams • Appendix D contains the circuit diagrams with information on device identification, cross-reference and device identification conventions. The diagrams are generated according to the customer-specific project. • “Setting of protective devices” is generated according to the customer-specific project. – Appendix E – Parts list The parts list is produced for each project and contains all information to identify a component. – Appendix F – Test reports and certificates Appendix F provides the test reports of the drive. Quality certificates, and codes and standards the drive complies with are added if necessary for the project.

– Appendix G – Signal and parameter table The Signal and parameter table includes descriptions of actual signals, control and status words, and control parameters and their default settings.

Terms and abbreviations The following table lists terms and abbreviations you should be familiar with when using this user manual. Some of the terms and abbreviations used in this user manual are unique to ABB and might differ from the normal usage.

Term/Abbreviation Definition

ACS1000A ACS1000 air-cooled drive AMC circuit board Application and Motor Controller The digital signal processor is the heart of the control system of the drive. Cluster A cluster is a synonym for a group of hardware modules of the drive control system. DDCS Distributed drive control system DDCS is an acronym for a serial communication protocol designed for data transfer via optical fibers. Drive Short form for ACS1000 drive Drive system The drive system includes all equipment used to convert electrical into mechanical power to give motion to the machine. DriveBus Communication link dedicated for ABB drives DriveDebug DriveDebug is part of ABB’s DriveWare® software tools for drives using the DDCS communications protocol. DriveDebug runs on computers with Windows® operating systems. DriveDebug is a specialist’s tool used to diagnose, tune and troubleshoot ABB drives. DriveWindow DriveWindow is a DriveWare® product. DriveWindow is a 32 bit Windows® application for commissioning and maintaining ABB drives equipped with optical communication links. Equipment Frequency converter and related equipment EMC Electromagnetic compatibility All measures to suppress electromagnetic disturbances caused by different electrical equipment in the same electromagnetic environment, and to strengthen the immunity of the equipment to such disturbances. Ground Earth To ground The conducting path (eg, conductor) between the electric equipment (eg, frequency converter) and the earth. The electric equipment is connected to the earth, eg, by a grounding set or a grounding switch. INU Inverter unit of the drive. The INU converts the DC voltage to the required AC motor voltage and frequency. IOEC module The IOEC module is an active input and output device for digital and analog signals. Line voltage RMS voltage of the main power supply of the drive MCB Main circuit breaker The MCB is a major protection device of the drive and is the main connection and disconnection point between the main power supply and the drive. Molykote Brand name for lubricants PCB Printed circuit board

Term/Abbreviation Definition

PCC Point of common coupling The PCC is the point in the electrical power supply system where the responsibility of the utility changes to the industrial customer. The utility is responsible to provide clean voltage and current with respect to harmonic distortion up to the PCC. The industrial customer is responsible not to distort voltage and current by its electrical systems. PID controller Proportional-integral-derivative controller Control loop feedback system for controlling process variables (eg, pressure, flow) PE Protective earth PPCS Power plate communication system PPCS is an acronym for a serial communication protocol designed for data transfer via optical fibers between AMC circuit board and INTerface circuit boards. RTD Resistance temperature detector or device The RTD is a temperature sensor where the change in electrical resistance is used to measure the temperature. Supervisory signal Indicates the operating condition of a circuit or device. SW Software TC Short form for terminal compartment of the drive UPS Uninterruptible power supply Zero speed threshold Used in the manual to indicate that the drive has reached the value “zero speed” that is set in a parameter. The value can be set in the range of 0 and maximum speed (the unit for the speed is rpm).

Trademarks Names that are believed to be trademarks of other companies and organizations are designated as such. The absence or presence of such a designation should however not be regarded as an offense of the legal status of any trademark. The following registrations and trademarks are used in this manual:Trademark Definition Windows® Registered trademark of Microsoft Corporation Industrial IT™ Trademark of ABB DriveWare® Registered trademark of ABB Ethernet® Registered trademark of Xerox Corporation Profibus® Registered trademark of Profibus International (P.I.) Modbus® Registered trademark of the Modbus IDA organization Molykote® Registered trademark of Molykote

1.8 User’s responsibilities It is the responsibility of those in charge of the drive to ensure that each person involved in the installation, operation or maintenance of the drive has received the appropriate training and has thoroughly read and clearly understood the instructions in this manual and the relevant safety instructions. 

1.9 Intended use of equipment Those in charge of the drive must ensure that the drive is only used as specified in the contractual documents, operated under the conditions stipulated in the technical specifications and on the rating plate of the drive, and serviced in the intervals specified by ABB. Use of the drive outside the scope of the specifications is not permitted. Intended equipment use also implies that only spare parts recommended and approved by ABB must be used. Unauthorized modifications and constructional changes of the drive are not permitted. 

1.10 Cyber security disclaimer This product is designed to be connected to and to communicate information and data via a network interface. It is the customer’s sole responsibility to provide and continuously ensure a secure connection between the product and Customer network or any other network (as the case may be). Customer shall establish and maintain any appropriate measures (such as but not limited to the installation of firewalls, application of authentication measures, encryption of data, installation of anti-virus programs, etc) to protect the product, the network, its system and the interface against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB and its affiliates are not liable for damages and/or losses related to such security breaches, any unauthorized access, interference, intrusion, leakage and/or theft of data or information

1.11 Quality certificates and applicable standards The following certificates and conformity declarations are available with ABB: – ISO 9001 and ISO 14001 certificates stating that ABB Switzerland Ltd has implemented and maintains a management system which fulfills the requirements of the normative standards – EC declaration of conformity – List of standards the drive complies wit

16] ANSI Z535.6 American national standard for product safety information in product manuals, instructions, and other collateral materials [17] ISO 3864-2:2004 (E) – Graphical symbols – Safety colors and safety signs – Part 2: Design principles for product safety labels [18] ISO 7010:2011 (E) – Graphical symbols – Safety colours and safety signs – Registered safety sign [19] EN 50110 European standard code for electrical work safety [20] ISO 13849-1 Safety of machinery – Safety-related parts of control systems – Part 1: General principles for design, section 6.2.6 Category 3 [21] IEC 60204-1 Safety of machinery – Electrical equipment of machines – Part 1: General requirements [22] IEC 60721-3-1 Classification of environmental conditions: Classification of groups of environmental parameters and their severities; Storage [23] IEC 60721-3-2 Classification of environmental conditions – Part 3-2: Classification of groups of environmental parameters and their severities – Transportation and Handling [24] IEC 60721-3-3 Classification of environmental conditions – Part 3: Classification of groups of environmental parameters and their severities – Section 3: Stationary use at weatherprotected location [25] IEC 62477-2 Safety requirements for power electronic converter systems and equipment – Part 2: Power electronic converters from 1 000 V AC or 1 500 V DC up to 36 kV AC or 54 kV DC

1.12 Items covered by delivery Delivery typically comprises the following items: – Drive that is shipped in sea freight or airfreight packaging. – Optional components and cabinets – Set of door keys attached to lifting rail (1 in Fig. 1-1) – Set of door keys inside the drive – Rating label (2 in Fig. 1-1) – Box with USB stick (3 in Fig. 1-1), which contains the user manual and related documents. – Strain relief rails – Air exhaust hood – Redundant fan unit (option) – Set of bolts, nuts and washers

1.13 Identifying the delivery The drive and accessories are identified by the type code printed on the rating label. The label provides information on the type of drive, the rated voltage, the frequency and the current of the main and the auxiliary power supply

2.1 Overview Read this material before working on or around the equipment. Failure to do so can result in injury or death! 

2.1.1 Safety standards The following industry standards are observed: – “ANSI Z535.6 American national standard for product safety information in product manuals, instructions, and other collateral materials” [16] – “ISO 3864-2:2004 (E) – Graphical symbols – Safety colors and safety signs – Part 2: Design principles for product safety labels” [17] – “ISO 7010:2011 (E) – Graphical symbols – Safety colours and safety signs – Registered safety sign” [18] – “EN 50110 European standard code for electrical work safety” [19] 2.2 Safety messages The following safety messages are provided to help prevent personal injury and damage to the equipment. The indicated hazard level is based on the ANSI Z535.6 standard.

Damage prevention information

Product safety labels Safety labels are affixed to the drive components to alert personnel of potential hazards when working on the equipment. For more information, see the label placement document for the drive. The instructions on the safety labels must always be followed and the labels must be kept in a perfectly legible condition.

Additional safety labels, including the following, might also be provided: (1) Danger label (2) Caution label (3) Warning label (4) Notice label Electricity hazard This sign can also have additional text below it, eg, “High voltage” Hot surface Crushing of hands No access for people with active implanted cardiac device The magnetic field of the drive can influence the functioning of pacemakers. The pacemaker sign should be installed at the entrance to the drive room or at a minimum distance of 6 m from the drive to stop personnel with pacemakers approaching the drive. Firefighting sign Outlines the procedure when fighting fire in electrical equipment. The sign must be installed well visible near the drive. High voltage sign Must be installed clearly visible at the main circuit breaker in the switchgear room. The sign alerts personnel to the high voltage which can be present on the secondary side of the input transformer until the main circuit breaker has been opened and secured and the drive has been de-energized and grounded.

Search for products

Back to Top
Product has been added to your cart