Change to enter Edit Mode. Use the Right/Left arrow keys to move the cursor under
the digits you want to change. Use the up/down arrow keys to change the digits to the
desired values. In the case of this example, continue this procedure until the display
reads [00150.0]. Use the Right arrow key to move the cursor out past the right
bracket to save the setting. The display then reads FORWARD URV? {00150.0}.
5. Now that all changes have been made, press the Right arrow key. You are asked Go
On-Line? Reply Yes by pressing the Right arrow key. Press the Right arrow key again
to begin displaying flow measurements.
Foundation Fieldbus Protocol
Your transmitter has been preconfigured at the factory to the settings shown in Appendix B.
Compare your needs to the factory configuration and note the changes to the configuration you
must make.
If the transmitter is not connected to a flowtube or IMTSIM, it is necessary to put a jumper wire
between terminals Coil 1 and Coil 2 and also to provide power to the transmitter.
This section describes the procedures to quick start the transmitter from the optional local
keypad/display. Note that after you quick start the transmitter from the local keypad, you should
use the fieldbus host to ensure that parameter values associated with the host are changed to agree
with those changed from the local keypad/display. Otherwise, mismatch errors occur when you
attempt to place the transmitter into Auto mode.
To make changes to the configuration using the local keypad/display, go to 1 TOP LEVEL/Setup
by pressing the Left arrow repeatedly until the display reads 1 TOP LEVEL. Then use the
Up/Down arrow keys to go to 1 TOP LEVEL/Setup. The procedure to change your
configuration is demonstrated by the following example:
Engineering units (EGUs) in GPM (factory default setting)
Forward direction of flow (Unidir positive – factory default setting)
Flow range 0 to 150 GPM
Flowmeter factor of 18.22 (refer to “Determining the Meter Factor” on page 18)
Note that the factory default engineering units is already configured as GPM, so no change is required. 2. Note that the factory Output mode is also already configured as UniDir positive, so no change in the direction is required. 3. You must enter your flow upper range value however. To do this: a. Go to Setup Level 2 by pressing the Right arrow key. Next move to 2 SETUP Outputs with the Down arrow key. Then move to 3 OUTPUTS Output Mode with the Right arrow key
b. Use the Down arrow key to go to 3 OUTPUTS Range Info and the Right arrow
key to go to FORWARD URV? {#####.#} GPM (Default {00100.0}).
c. Press the Shift + Change keys to enter Edit mode. You are asked Go Offline?
Reply Yes by pressing the Right arrow key. The display shows FORWARD URV?
[#####.#] GPM.
d. Use the Right/Left arrow keys to move the cursor under the digits you want to
change. Use the Up/Down arrow keys to change the digits to the desired values. In
the case of this example, continue this procedure until the display reads
[00150.0].
e. Using the Right arrow key, move the cursor under the right bracket and press the
key to enter the URV. The display reads FORWARD URV? {150.0} GPM.
f. Press the key again to move back to 3 OUTPUTS Range Info.
4. Lastly, you have to enter your flowmeter factor. To do this:
a. Use the Left arrow key to move to the Level 2 menu, 2 SETUP Outputs.
b. Press the Down arrow key six times to move to 2 SETUP Calibration and the
Right arrow key to move to the Level 3 menu, 3 CALIBRATION Meter Factor.
See FIgure A-5.
c. Use the Right arrow key to move to MFACTOR FORMAT? {###.######}. This
format can be changed, if necessary, to accommodate the meter factor.
d. Use the Right arrow key to move to METER FACTOR? {###.######} (Default
{012.000000}. Then press Shift + Change to enter Edit mode.
e. Use the Right/Left arrow keys to move the cursor under the digits you want to
change. Use the Up/Down arrow keys to change the digits to the desired values. In
the case of this example, continue this procedure until the display reads
[018.220000]. Use the Right arrow key to move the cursor out past the right
bracket to save the setting. The display then reads METER FACTOR?
{018.219998}. Note that in some cases, as with this example, a slightly different
value appears. The magnitude of this difference is insignificant.
NOTE
To determine the correct meter factor, refer to “Determining the Meter Factor” on
page 18.
f. Press the Right arrow key again. The display reads 3 CALIBRATION Meter
Factor.
5. Now that all changes have been made, press the Left arrow key until you are asked Go
On-Line? Reply Yes by pressing the Right arrow key. To display flow measurement,
press the Right arrow key once more.
! CAUTION
If you change the upper range value or engineering units in the Transducer Block with
the local display pushbuttons without making a corresponding change in the
corresponding Analog Input Blocks from a fieldbus host, a mismatch error occurs and
the Analog Input Block reverts to Out of Service mode.
Determining the Meter Factor
First find the “Cal Factor” or “IMT25 Cal Fact” on the flowtube data label.
If the flowtube data label has a “IMT25 Cal Fact.” listing, use that value as the “Meter Factor.”
If only a “Cal Factor” value is found on the flowtube data label, that value must be multiplied by
the appropriate factor from Table 2 to calculate the “Meter Factor.”
Operation from Keypad/Display Panel
For local operation, configuration, and calibration, all operator entries are made through a
5-button keypad and all data is presented on a 2-line x 16 character LCD display. The
keypad/display of the IMT25 Transmitter is shown in Figure 1. Information on various types of
display is shown in Figure .
Figure 1. IMT25 Magnetic Flow Transmitter — Keypad/Display
All required functions are accomplished by using the four arrow keys alone and in combination
with the Shift key. Table 4 explains the function of each key
Top Level Menu
The Top Level menu displays the following modes – Measurements, Status, Identity, Quick Start
(in FoxCom and HART transmitters), Test Mode, and Setup. You can switch from one to another
in sequence by using the Up/Down arrow keys. To enter the second level menu from a particular
top level screen, press the Right arrow key. To return to the top level from a second level menu
item, press the Left arrow key. The level of the first, second, third, and fourth level menus is
indicated by the digit appearing as the first character in Line 1 of the display; a 1 indicates Level 1
(Top Level), a 2 indicates Level 2, and a 3 indicates Level 3, etc.
The top level menu is shown in Figure 3. For a complete presentation of all menu structures, refer
to Appendix A.
Measurements Mode
The Measurements mode, which is your main operating mode, is displayed upon startup.
Depending on the transmitter configuration, it has up to seven displays, any of which may be set
as the startup default. All screens can be scrolled with the Up/Down arrow keys.
Rate (EGU) — Shows current flow rate (forward or reverse) in the selected
engineering units.
Rate (% Range) — Shows current flow rate (forward or reverse) as a percentage of full
scale URV.
Fwd Tot — Shows current value of the forward totalized flow in engineering units.
Use the Net Tot display to reset.
Rev Tot — Shows current value of the reverse totalized flow in engineering units. Use
the Net Tot display to reset.
Net Tot — Shows current value of the net totalized flow (forward total – reverse total)
in selected engineering units. Press Shift + Reset to reset the displayed total to
zero. Resetting Net Tot also resets Fwd Tot and Rev Tot. It does not reset Gr Tot.
If Reset Totals is passcode protected, the message Enter Passcode appears.
Grand Tot — Shows current value of the grand total flow in engineering units. Press
Shift + Reset to reset the displayed total to zero. Resetting Gr Tot does not reset
Fwd Tot, Rev Tot, and Net Tot. If Reset Totals is passcode protected, the message
Enter Passcode appears.
If the Dual Display feature is configured On, a combination of two of these parameters can be
displayed at once. A typical dual display, in which Line 1 shows flow rate and Line 2 shows the
present forward total, is shown below. Units may not be displayed or may be truncated.
You may step through the displays of each of these parameters with the Up and Down arrow keys.
However, unless you specifically do so, the display defaults to that configured in Setup mode. The
engineering units and formats used in the displays are also configured in Setup mode.
Status Mode
The Status mode enables you to view fourteen system parameters and thus assess the performance
of the loop. You may not edit them in this mode. To step through the displays of the following
parameters, use the up/down arrow keys:
Mode — Shows the present operating mode: On-Line, Off-Line, Override, or
Calibrate. This will normally display On-Line. The other modes will only be
displayed if someone else has changed the mode with an I/A Series Workstation,
PC-Based Configurator, HART Communicator, or fieldbus host. Off-Line means
that it has been taken off-line; Override, that the measurements cannot be relied
upon because one or more of the outputs is at a preset value; and Calibrate, that the
transmitter is in Calibration mode.
Alarm — Shows the most current active alarm. If there are no active alarms but
something is in the history buffer, the display reads Alarms In Buffer. If there are
no active alarms and nothing in the buffer, display reads No Alarms.
Diagnostics — Shows No Diag, Diag Existed, or Diag Exists. If a diagnostic
problem exists, the second line identifies the problem. Help is available with the
Shift + Help keys. An active diagnostic problem cannot be cleared; the problem
must be corrected. Diag Existed means a diagnostic error did occur, but the
condition has cleared and the transmitter is working correctly. However, the Diag icon
will remain on the display until the diagnostic has been acknowledged. To clear, the
transmitter must be in the Status mode with the diag window displayed. Then use the
Shift + Ack keys.
Digital Output — If the transmitter output is in Digital Output mode, the display
shows whether the transmitter is configured for Unidirectional or BiDirectional flow.
If the transmitter is not in Digital Output mode, the screen is not displayed.
NOTE
Digital and Analog Output are mutually exclusive. Only one of the two are displayed
at any one time.
Analog Output — If the transmitter output is in Analog Output mode, the display
shows whether the transmitter is configured for U (unidirectional), U/M1
• (SET) key : Used to change the display mode of the LCD display and to
finalize input.
• (UP) key : Used to change parameters and increment set values.
• (DOWN) key : Used to change parameters and decrement set values.
• (RESET) key : Used to reset alarms set to self-holding.
• Alarm reset is not possible until the output condition has been released.
• An alarm lamp set flashing by the First-out Display function cannot be reset.
(Reset by shorting between the RES and COM terminals.)
• (CHECK) key : The CHECK key is used to adjust the gain while changing set
values with the UP and DOWN keys.
For example, if the CHECK key is pressed while the value 0.1
appears on the MEAS 2 LED display, a value corresponding to the
measurement range × 0.1 can be set.
• Each operation of the CHECK key will multiply the multiplier by 10.
: When the CHECK key is pressed during normal monitoring, the
monitor will go through self-diagnosis in the following sequence :
(1) LCD, LED display test (all lamps light)
(2) Self-diagnosis
(3) Display of diagnosis result (Normal) (Abnormal)
• The diagnosis result for CH1 is indicated on the MEAS 1 display and that for CH2 on
the MEAS 2 display.
• If an abnormality is found as a result of self-diagnosis, the error content is displayed
after approx. 3 seconds.
• In case of more than one abnormality, error contents are displayed at 3-second
intervals.
Error content display
Check items Display
CH1 OK (input abnormal) alarm HIGH
CH2 OK (input abnormal) alarm HIGH
CH1 OK(input abnormal) alarm LOW
CH2 OK(input abnormal) alarm LOW
CH1 A/D input 5V side over
CH2 A/D input 5V side over
CH1 A/D input 0V side over
CH2 A/D input 0V side over
For safe operation…..
Thank you for using our VM-5 Series Monitor. SHINKAWA Sensor Technology applies strict quality control
and inspections to ensure the high reliability of its products.
This instruction manual contains descriptive information, specifications, and operating, setting, and adjusting
procedures.
Please study the contents of this manual and related manuals thoroughly before installing or operating the
equipment, and keep it handy for future reference.
“Safety Conventions”
Please thoroughly study the following section entitled “Safety Conventions” before operating the
equipment.
The safety symbols explained in this section are placed outside the left margin next to the text to which they
apply.
This unit is designed for use by specialists or persons thoroughly familiar with the field.
Make sure that the end user receives the Instruction Manual delivered with this unit.
Before use…..
When the unit is received, inspect it for damage suffered in transport and check
whether it is the item you ordered. In the unlikely event that it was damaged in transport
or does not function according to specifications, please contact the SHINKAWA Office
or dealer nearest you.
Store the unit under the ambient conditions given in the specification.
Avoid places where it is exposed to high humidity or corrosive gases.
Make it a rule to follow the instructions given in this manual.
This manual contains important information designed to prevent personal injury and property damage, and
ensure safe operation of the equipment.
Familiarize yourself with the signs and symbols explained below before proceeding to read the manual, and
observe the instructions given.
■ Explanation of signs
Symbols Explanation
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death
or serious injury.
CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor
or moderate injury. It may also be used to permit for property-damage-only accidents.
◊ “Serious injury” refers to such injuries as loss of eyesight, injuries, burns (due to heat or cold), electric
shock, fractures, and poisoning, that have permanent aftereffects and require hospitalization or long-term
outpatient treatment.
◊ “Moderate or minor injury” refers to such injuries as burns and electric shock that do not require
hospitalization or long-term outpatient treatment. “Property-damage-only accidents” refers to
consequential damage related to destruction of property and damage to the equipment.
■ Explanation of symbols
Symbols Explanation
Indicates a prohibited action.
Details are given in the text next to the symbol.
Indicates a mandatory action.
Details are given in the text next to the symbol.
To ensure safe use of this equipment, strictly observe the safety precautions provided in this manual, as well
as installation methods and methods of use stipulated by laws and regulations. SHINKAWA Sensor
Technology will not be liable for damage, etc. due to methods of use contravening to the instructions provided
here.
■ Safe use
WARNING
Make sure to ground.
May cause electric shock or malfunction.
Make sure to turn the power off before any wiring work.
Will cause electric shock.
CAUTION
Connect the input signal within the voltage range described in the
specification to the input terminals.
Will cause damage and malfunction of the instrument.
Install the monitor unit and its relay module unit in the same location in the
instrument rack.
Will cause damage to the instrument and malfunction of the turbine monitoring system.
A printed circuit board and electronic products may receive damage with
the static electricity of a human body.
Touch the metal part once and discharge your static electricity before
dealing with it.
Will cause damage and malfunction of the instrument.
Do not touch parts and soldered surfaces of the monitor unit.
Will cause damage and malfunction of the instrument.
The monitor unit is a precision instrument.
Take care not to expose it to excessive shock or vibration.
Do not change the parameter settings during operation.
May cause unexpected alarm output.
Do not pull out the face plate during operation.
Will cause damage to the instrument and malfunction of the turbine monitoring system.
Do not measure insulation resistance and dielectric strength other than
those at places specified.
Will cause damage to the instrument.
Do not remodel this monitor unit without permission.
Otherwise the guarantee can not be made.
■ EMC(Electro-magnetic compatibility)
The EMC of each VM-5 Series monitor is evaluated by various noise tests.
However, its characteristics may vary with on environmental conditions such as the magnitude of noise,
ambient temperature, humidity and the arrangement of equipment.
For the above reason, when operating the monitor, please observe the following CAUTION.
CAUTION
The monitor unit should be operated by specialists or personnel who have
knowledge of it.
When a shielded cable is used, the length of the unshielded cable section
should be less than 100mm (3.937in REF.).
For each relay used near this monitor unit, devices related to this monitor
unit or signal cables connecting the monitor unit and these devices, install
a surge killer.
Firmly tighten each screw used for mounting each unit. In additional,
always close the face plate for the monitor unit, then fix it with knurled
screws.
In order to prevent the system from its malfunction when the monitor unit
fails, provide the systematic interlock function.
Do not wire input signal cables in parallel with control and power cables.
It is recommended that separated wire ducts be used for these cables.
Do not use any radio equipment near the monitor unit.
■ Noise filter
Noise transmitted through in each cable may be rejected to some extent by inserting a ferrite core in the cable
(note 1).
If the cable passes through noisy surroundings, it is recommended that such a noise prevention device is used.
GENERAL INFORMATION
OVERVIEW
This is a highly reliable dual channel vibration monitor which monitors the shaft vibration of
rotating machinery.
Both a 10-slot rack mounting type and a single-unit independent type with a built-in power supply
are available so that it can respond flexibly to any system design from medium and small scale
rotating machinery to TSI. The monitor accepts signals detected by a transducer and displays them
on LCD.
It is also possible to set ALERT and DANGER alarm levels independently to detect machine
failures early on and inform the operator of these failures. It has a built-in self-diagnostic function
to inform the operator of input transducer failures, thereby preventing rotating machinery from
false shutdowns.
FEATURES
• Conforms to API St’d 670
• The monitor is available as a single unit independent type or a rack mounting type.
• Has a self-diagnostic function.
• Allows the operator to change each setting even in the field.
• Important information such as measured value, alarm set value and gap voltage is normally
displayed.
• Can isolate recorder output (option).
• LED display / contact output (DANGER / ALERT alarm).
• LED display / contact output (Input abnormal alarm).
• For alarm output wiring proceed as described in the instruction manuals for the
VM-5G Single Unit Instrument Rack and VM-5Y Relay Module Unit used in
combination with this monitor unit.
• If megger test is made on the signal cable between transducer and monitor,
disconnect the cable from transducer and monitor.
Be sure to discharge the charged electric load before connecting the cable to the
transducer and monitor.
If this caution is not adhered to, the transducer and monitor could be damaged.
FIRSTOUT DISPLAY
• Installation in VM-5H3, 5W1 Instrument Rack
Causes the alarm lamp of the channel that first output alarm to flash.
• Installation in VM-5G Single Unit Instrument Rack
Causes the lamp of the alarm first output to flash.
For details refer to 7. PARAMETER SETTING on page 19.
• An alarm lamp set flashing by the First-out Display function cannot be reset by
pressing the RES (RESET) key.
Reset by shorting between the RES and COM terminals.
• It is necessary to keep short circuit of the terminals for more than one (1) second to
operate these functions.
5-9 SEQUENCE FUNCTION
To prevent alarm output due to excessive vibration generated during starting and stopping of the
machine, this function expands the DANGER alarm and ALERT alarm set ranges by shorting
between the SEQ. and COM terminals.
• The machine is not protected if the alarm set value exceeds 110% of the monitor
range due to operation of the sequence circuit.
• It is necessary to keep short circuit of the terminals for more than one (1) second to
operate these functions.
5-10 BYPASS FUNCTION
Used to disable alarm output while setting the alarm parameters, or during maintenance/inspection
work. The alarm BYPASS lamp flashes or lights during this operation. Set by turning the BYPASS
switch to ON.
• While BYPASS FUNCTION is in operation, the machine is not protected.
5-10-1 DANGER BYPASS
Cuts off DANGER alarm. While cut off, the DANGER alarm and BYPASS lamps are flashing.
This function is activated by means of the DANGER BYPASS switch. For details refer to 7.
PARAMETER SETTING on page 19.
• If mounted in the VM-5H3 or VM-5W1 Instrument Rack, all units in the instrument
rack can be set collectively to DANGER BYPASS.
For details refer to VM-5H3 or VM-5W1 Instrument Rack instruction manual.
5-10-2 CH1 BYPASS
DANGER alarm, ALERT alarm, OK alarm, display and recorder output of CH1 are cut off.
While cut off, the OK lamp goes off and the BYPASS lamp lights.
This function can be activated by means of the CH1 BYPASS switch.
For details refer to 7. PARAMETER SETTING on page 19.
5-10-3 CH2 BYPASS
DANGER alarm, ALERT alarm, OK alarm, display and recorder output of CH2 are cut off.
While cut off, the OK lamp goes off and the BYPASS lamp lights.
This function can be activated by means of the CH2 BYPASS switch.
For details refer to 7. PARAMETER SETTING on page 19.
5-11 POWER ON TIMER MODE
Operates for approx. 5sec. after the power is turned on. (for approx. 25 sec. in case of pk-pk
detection). In this mode, all alarm functions are disabled and the BYPASS and OK lamps flash.
5-12 ALARM RELAY MODE
Each alarm contact can be set to either normally de-energized or normally energized.
Alarm contact operation
Monitor power Monitor power ON
OFF Normal state Alarm state
NO contact NORMALLY DE-ENERGIZED OPEN OPEN CLOSE
NO contact NORMALLY ENERGIZED OPEN CLOSE OPEN
NC contact NORMALLY DE-ENERGIZED CLOSE CLOSE OPEN
NC contact NORMALLY ENERGIZED CLOSE OPEN CLOSE
For details refer to 7. PARAMETER SETTING on page 19.
5-13 ALARM RESET MODE
The automatic reset of all alarm output and alarm lamps can be set when the measured value or
input signal return to normal. In addition to above, the self-holding function can be also set for
each alarm output that holds the alarm condition until reset by setting RES key (inside of the front
panel) or by shorting between RES and COM terminal.
• Alarm reset is not possible until the output condition has been released.
• It is necessary to keep short circuit of the terminals for more than one (1) second to
operate these functions.
For details refer to 7. PARAMETER SETTING on page 19.
5-14 MONITOR OUTPUT
For vibration analysis, the vibration waveform signal is output from the BNC connector on the
monitor front panel and buffer output terminal on the rear panel (VM-5G Single Unit Instrument
Rack, VM-5Y Relay Module Unit) via a buffer amplifier.
5-15 RECORDER OUTPUT
An analog signal proportional to the vibration value is output from the terminal block.
5-16 SELF-DIAGNOSTIC FUNCTION
Any failures in the input system, such as sensor short-circuit or imperfect connections, are detected,
then an OK alarm is contact-output and (simultaneously), the OK lamp flashes.
5-17 POWER SEQUENCE
If mounted in the VM-5G Single Unit Instrument Rack, the secondary power supply can be cut off
by shorting between the P-S (POWER SEQUENCE) and COM terminals.
• This function can be used for pulling out or pulling in the monitor unit at the
emergency time. However, do not use for long time shorting of more than one (1)
minute or turning on and off repeatedly.
Also, the parallel connection for the two (2) or more monitors should not be allowed.
5-18 TIMED OK CHANNEL DEFEAT
When on setting, when OK alarm is output, DANGER alarm, ALERT alarm, display, and recorder
output are disabled. DANGER ALERT, display and recorder output are not disabled, in case of
excessive signal input from sensor.
For details refer to 7. PARAMETER SETTING on page 19.
5-19 SUPPRESSION FUNCTION
This function can suppress the measurement around zero measurement point of the monitor by the
effect of the piping vibration or electric noise, etc. during the machine stopping.
The suppression can be set at 0.0 to 10.0 % (0.1% step) of the monitor range.
ex.) If the suppression is set at 2.0%, monitor measurement less than 2.0% shall be output as 0.0%
2 DESCRIPTION OF PARTS 1 LCD display This LCD display serves for display of measured values, alarm set values, sensor set gap voltage value and other set values. 2 DANGER alarm lamp Lit when DANGER alarm is output. 3 ALERT alarm lamp Lit when ALERT alarm is output. 4 OK lamp Flashes (steady light in normal condition) when OK (input abnormal) alarm is output. 5 BYPASS lamp Flashes during DANGER bypass and lights during CHANNEL bypass. 6 Monitor output connector This is a BNC output connector for connection of an oscilloscope to observe the waveform, or for output to other devices such as an analyzer. The input signals from the transducers are output through a buffer amplifier. • Make sure to insulate the monitor output against earth. If not insulated, a 2-point earth system results, which may cause noise interference. 7 Name plate 8 Tag, Ser. No. plate The TAG NO. and SER.NO. are entered on this plate. 9 LCD board 10 Slide frame 11 Main board frame 12 Main board 13 DIN connector (64pin) Connector for connection to the VM-5G Single Unit Instrument Rack or VM-5H3 or VM-5W1 Instrument Rack.
1) 1BY (CH1 BYPASS) Switch
“ON” To select CH1 BYPASS function.
“OFF” Normal monitoring
2) 2BY (CH2 BYPASS) Switch
“ON” To select CH2 BYPASS function.
“OFF” Normal monitoring
3) DBY (DANGER BYPASS) Switch
“ON” To select DANGER BYPASS function.
“OFF” Normal monitoring
4) MS1 (MODE-SELECT1) Switch (normally OFF)
• Set normally to “OFF”. Parameter setting mode is disabled.
5) MS2 (MODE-SELECT2) Switch
“ON”
For setting the alarm reset mode, alarm delay time, alarm relay mode, first-out display,
and timed OK channel defeat.
Also enables setting the address when used in combination with the VM-5H3 or 5W1
Instrument Rack and VM-5P1,2 Communication/Phase Marker Unit or VM-53 Dual
Communication Unit. To PARAMETER SETTING 1.
“OFF”
For changing the set values for DANGER alarm and ALERT alarm, and GAP ALARM,
and adjusting measured value and recorder output zero span.