• IGP10 for compact light weight and direct-to-process

mounting (bracket optionally available)

• IGP20, bracket mounted, for lower ranges, more

material options, and vacuum service

• Field-proven silicon strain gauge technology

• Corrosion-resistant epoxy finish

• Accuracy to ± 0.07 % of span

• Ambient temperature effects to ± 0.2 % URL

per 55 °C (100 °F) change

• Intelligent FOXCOM & HART / 4 to 20 mA version

or economical 4 to 20 mA version

• LCD Indicator / Pushbutton Configurator

to set zero, span, display units, etc.

Optional on Digital / 4 to 20 mA version,

Standard on 4 to 20 mA version

These Intelligent, two-wire transmitters provide precise, reliable, measurement of gauge or absolute

pressure, and transmit a 4 to 20 mA output signal

with a superimposed HART/ FOXCOM digital signal for remote configuration and monitoring.

IGP10 Span, Range and Overrange Limits

IAP10 Span, Range and Overrange Limits

Span

Limits

Code

Span Limits Range Limits Maximum Overrange

kPa psi bar

(kg/cm²) kPa psi bar

(kg/cm²) kPa psi bar

(kg/cm²)

C 7 & 210 1 & 30 0.07 & 2.1 0 & 210 0 & 30 0 & 2.1 310 45 3.15

D 70 & 2100 10 & 300 0.7 & 21 0 & 2100 0 & 300 0 & 21 3100 450 31.5

E 700 & 21000 100 & 3000 7 & 210 0 & 21000 0 & 3000 0 & 210 31000 4500 315

IGP20 Span, Range and Overrange Limits

Span

Limits

Code

Span Limits Range Limits Maximum Overrange

kPa psi bar

(kg/cm²) kPa psi bar

(kg/cm²) kPa psi bar

(kg/cm²)

B 0.87 & 50 0.125 & 7 0.0087 & 0.5 –50 & 50 –7 & 7 –0.5 & 0.5 25000 3625 250

C 7 & 210 1 & 30 0.07 & 2.1 –100 & 210 –14.7 & 30 –1 & 2.1 25000 3625 250

D 70 & 2100 10 & 300 0.7 & 21 –100 & 2100 –14.7 & 300 –1 & 21 25000 3625 250

E 700 & 21000 100 & 3000 7 & 210 –100 & 21000 –14.7 & 3000 –1 & 210 25000 3625 250

Temperature Limits

Fill fluid

Flourinert

Fill fluid

Silicone

Ambient: –29 to 85 °C

(–20 to 185 °F)

–40 to 85 °C

(–40 to 185 °F)

Sensor: –29 to 121 °C

(–20 to 250 °F)

–46 to 121 °C

(–50 to 250 °F)

Gauge, Abs. and d/p Pressure

Accuracy (Includes Linearity, Hystersis, and

Repeatability)

Electronics

Version

Configured

Output Signal

Accuracy in %

of Calib. Span

-D & -T Digital

4 to 20 mA

± 0.07

± 0.1

-I 4 to 20 mA ± 0.2

Ambient Temperature Effect

Total effect for a 55 °C (100 °F) change within Normal Operating Conditions limit is:

Electronics -D, -T: ± 0.2 % of URL

Electronics -I: ± (0.2 % of URL + 0.1 % of span)

For complete specifications, refer to Product Specification

Sheet PSS 2A-1C13 B

Model Codes IGP10

Ambient Temperature Effect

Total effect for a 55 °C (100 °F) change within Normal Operating Conditions limit is:

Electronics -D, -T: ± 0.2 % of URL

Electronics -I: ± (0.2 % of URL + 0.1 % of span)

For complete specifications, refer to Product Specification

Sheet PSS 2A-1C13 B

Gauge, Abs. and d/p Pressure IGP10 – IGP20 – IAP10

CA 2A-1C13 B-(en) 09/1999

1-2

Intelligent Direct Connected Gauge Pressure Transmitter IGP10

Electronics Versions and Output Signal

Intelligent; Digital FoxCom and/or 4 to 20 mA dc, Configurable . . . . . . . . . . . . . . -D

Intelligent; Digital HART and 4 to 20 mA . . . . . . . . . . . . . . . . . . . . . . . . . -T

4 to 20 mA Analog Output, Explosionproof and Intrinsically Safe . . . . . . . . . . . . . -I

Structure Code – Process Connection, Sensor, and Fill Fluid

Process Connection Mat’l Sensor Fill Fluid

316L ss Co-Ni-Cr Silicone. . . . . . . . . . . . . . . . . . . . . . . . 20

316L ss Co-Ni-Cr Fluorinert . . . . . . . . . . . . . . . . . . . . . . . 21

316L ss 316L ss Silicone . . . . . . . . . . . . . . . . . . . . . . . 22

316L ss 316L ss Fluorinert. . . . . . . . . . . . . . . . . . . . . . . 23

Span Limits – Absolute or Gauge Pressure Units, as Applicable

MPa psi bar or kg/cm²

0.007 and 0.21 1 and 30 0.07 and 2.1…………………………C

0.07 and 2.1 10 and 300 0.7 and 21 …………………………D

0.7 and 21 100 and 3000 7 and 210 ………………………..E

Conduit Connection

1/2 NPT Conduit Connection, Both Sides ……………………………..1

PG 13.5 Conduit Connection, Both Sides (available only with Electrical Safety CodesE&N ………2

Electrical Safety (See Electrical Safety Specifications Section)

CENELEC Certified Intrinsically Safe, ia ………………………………..E

CSA Certified …………………………………………….N

EUROPEAN Ex, N, IIC. Nonsparking ………………………………….C

FM Approved …………………………………………….F

SAA Certified, EEx, d, IIC ……………………………………….A

Options

Mounting Bracket Set

Painted Steel Bracket with Plated Steel Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M1

Stainless Steel Bracket with Stainless Steel Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M2

Digital Indicator with Pushbuttons (standard equipment on IGP10-I)

Digital Indicator, Pushbuttons, and Window Cover (for Electr VersionD&T only) . . . . . . . . . . . . . . . . . . . . . -L1

Vent Screw and Block & Bleed Valve

Vent Screw in Process Connection for IGP10/IAP10; or in High Side Process Cover for IGP20. . . . . . . . . . . . . . . V1

Block and Bleed Valve, Carbon Steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V2

Block and Bleed Valve, 316 ss. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V3

Block and Bleed Valve, 316 ss Body w/Monel Trim (NACE Approved) . . . . . . . . . . . . . . . . . . . . . . . . . . . V4

Conduit Thread Adapters

Hawke-Type 1/2 NPT Cable Gland for use with Conduit Connection Code “1” . . . . . . . . . . . . . . . . . . . . . . . A1

Plastic PG 13.5 Connector for use with Conduit Connection Code “2” (available only with Electrical Safety Codes E & N) . A2

M20 Connector for use with Conduit Connection Code “1” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A3

Electronics Housing Features

External Zero Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Z1

Custody Transfer Lock and Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Z2

External Zero Adjustment and Custody Transfer Lock and Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Z3

Factory Configuration

Digital Output (4 to 20 mA Default if not selected) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C1

Full Factory Configuration (Requires Configuration Form to be filled out) . . . . . . . . . . . . . . . . . . . . . . . . . . C2

Miscellaneous Optional Selections

G 1/2 B Manometer Process Connection (Not Available with Option “-V1”) …………………….G

R 1/2 Process Connection (1/2 NPT to R 1/2 Adapter) ……………………………..R

Five Year Warranty …………………………………………….W

Supplemental Customer Tag (Stainless Steel Tag wired onto Transmitter)

Options (continued)

Conduit Thread Adapters

Hawke-Type 1/2 NPT Cable Gland (for use with 1/2 NPT Conduit Connection Code 1) . . . . . . . . . . . . . . . . . . A1

Plastic PG 13.5 Connector (for use with PG 13.5 Conduit Connection Code 2)

(available only with Electrical Safety Codes E & N). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2

M20 Connector (for use with 1/2 NPT Conduit Connection Code 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . A3

Electronics Housing Features

External Zero Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Z1

Custody Transfer Lock and Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Z2

External Zero Adjustment and Custody Transfer Lock and Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Z3

Factory Configuration

Digital Output (4 to 20 mA Default if not selected) (Electr. Version D only) . . . . . . . . . . . . . . . . . . . . . . . . . C1

Full Factory Configuration (Requires Configuration Form) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C2

Ermeto Connectors

Steel, Connecting 6 mm Tubing to 1/4 NPT Process Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E1

Steel, Connecting 12 mm Tubing to 1/2 NPT Process Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E2

316 ss, Connecting 6 mm Tubing to 1/4 NPT Process Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E3

316 ss, Connecting 12 mm Tubing to 1/2 NPT Process Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . E4

Miscellaneous Optional Selections

Vent Screw In Side of Process Cover……………………………………..V

Five Year Warranty …………………………………………….W

Supplemental Customer Tag …………………………………………T

(a) Refer to PSS 2A-1Z9 E for option descriptions, and for additional optional features and accessories not listed in Model Code.

(b) See Functional Specifications section for pressure deratings when certain DIN 19213 versions are specified.

(c) Temperature limits derated to 0 and 60°C (32 and 140°F).

(d) Mounting Set option is not available.

Gauge, Abs. and d/p Pressure IGP10 – IGP20 – IAP10

09/1999 CA 2A-1C13 B-(en)

1-5

Intelligent Direct Connected Absolute Pressure Transmitter IAP10

Electronics Versions and Output Signal

Digital FOXCOM or 4 to 20 mA dc, Software Selectable . . . . . . . . . . . . . . . . . -D

Digital HART and 4 to 20 mA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -T

4 to 20 mA Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -I

Structure Code – Process Connection, Sensor, and Fill Fluid

Process Connection Mat’l Sensor Fill Fluid

316L ss Co-Ni-Cr Silicone. . Val. Pkg. . . . . . . . . . . . . . . . . . 20

316L ss Co-Ni-Cr Fluorinert . . . . . . . . . . . . . . . . . . . . . . . 21

316L ss 316L ss Silicone . . . . . . . . . . . . . . . . . . . . . . . 22

316L ss 316L ss Fluorinert. . . . . . . . . . . . . . . . . . . . . . . 23

Span Limits – Absolute or Gauge Pressure Units, as Applicable

MPa psi bar or kg/cm²

0.007 and 0.21 1 and 30 0.07 and 2.1…………………………C

0.07 and 2.1 10 and 300 0.7 and 21 …………………………D

0.7 and 21 100 and 3000 7 and 210 ………………………..E

Conduit Connection

1/2 NPT Conduit Connection, Both Sides ……………………………..1

PG 13.5 Conduit Connection, Both Sides (available only with Electrical Safety CodesE&N ………2

Electrical Safety (See Electrical Safety Specifications Section)

CENELEC Certified Intrinsically Safe, ia ………………………………..E

CSA Certified …………………………………………….C

EUROPEAN Ex, N, IIC. Nonsparking ………………………………….N

FM Approved …………………………………………….F

SAA Certified, EEx, d, IIC ……………………………………….A

Options

Mounting Bracket Set

Painted Steel Bracket with Plated Steel Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M1

Stainless Steel Bracket with 316 ss Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M2

Indicator with Pushbuttons (standard equipment on IGP10-I)

Digital Indicator, Pushbuttons, and Window Cover (for Electr VersionD&T only) . . . . . . . . . . . . . . . . . . . . . -L1

Vent Screw and Block & Bleed Valve

Vent Screw in Process Connection for IGP10/IAP10; or in High Side Process Cover for IGP20. . . . . . . . . . . . . . . V1

Block and Bleed Valve, Carbon Steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V2

Block and Bleed Valve, 316 ss. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V3

Block and Bleed Valve, 316 ss Body w/Monel Trim (NACE Approved) . . . . . . . . . . . . . . . . . . . . . . . . . . . V4

Conduit Thread Adapters

Hawke-Type 1/2 NPT Cable Gland for use with Conduit Connection Code “1” . . . . . . . . . . . . . . . . . . . . . . . A1

Plastic PG 13.5 Connector for use with Conduit Connection Code “2” (available only with Electrical Safety Codes E & N) . A2

M20 Connector for use with Conduit Connection Code “1” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A3

Electronics Housing Features

External Zero Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Z1

Custody Transfer Lock and Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Z2

External Zero Adjustment and Custody Transfer Lock and Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Z3

Factory Configuration

Digital Output (4 to 20 mA Default if not selected) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C1

Full Factory Configuration (Requires Configuration Form to be filled out) . . . . . . . . . . . . . . . . . . . . . . . . . . C2

Miscellaneous Optional Selections

G 1/2 B Manometer Process Connection (Not Available with Option “-V1”) …………………….G

R 1/2 Process Connection (1/2 NPT to R 1/2 Adapter) ……………………………..R

Five Year Warranty …………………………………………….W

Supplemental Customer Tag (Stainless Steel Tag wired onto Transmitter) ..